background image

5

15

½”

4 x M12

A2-70

10

20

¾”

4 x M12

A2-70

15

25

1”

4 x M12

A2-70

20

40

1½”

4 x M16

A2-70

27

50

2”

4 x M16

A2-70

45

65

-

4 x M16

A2-70

60

80

3”

8 x M16

A2-70

60

100

4”

8 x M16

A2-70

45

-

6”

8 x M20

A2-70

85

15

½”

½”

B7

9

20

¾”

½”

B7

13

25

1”

½”

B7

18

40

1½”

½”

B7

21

50

2”

⅝”

B7

41

65

-

⅝”

B7

52

80

3”

⅝”

B7

52

100

4”

⅝”

B7

38

-

6”

¾”

B7

68

NEOTECHA

 NTB-NTC BALL VALVES

INSTALLATION AND MAINTENANCE INSTRUCTIONS

FACE-TO-FACE BODY DIMENSIONS

DN

DIN-PN 16

ANSI-150 lbs

JIS-10K

mm

inches

mm

mm

mm

15

½”

130

108

130

20

¾”

150

117

150

25

1”

160

127

160

40

1½”

200

165

200

50

2”

230

178

230

65

2½”

290

290 (DIN dimension)

290

80

3”

310

203

310

100

4”

350

229

350

150

6”

480

ANSI-dim. 229 
with extension

267

480

ANSI-dim. 229 
with extension

6.7.1 Face-to-face body dimensions for NTB-NTC ball valves

RECOMMENDED TORQUES

DN

Bolts 

metric

Class

Torque

mm

inches

Nm

6.9.1 Recommended tightening torques for NTB-NTC ball valves DIN-PN 16 and JIS-10K

RECOMMENDED TORQUES

DN

Bolts

Class

Torque

mm

inches

UNC

lbf·ft

6.9.2 Recommended tightening torques for NTB-NTC ball valves ANSI B 16.10 class 150 (lbs)

6.8 Step-by-step valve installation

1.  Check that the distance between flanges matches the face-to-face dimension of the ball valve. 

Before installing the valve, spread the mounting flanges apart sufficiently using a suitable tool.

2.  Remove the protective caps and position the ball valve in the pipeline. When installing a 

C valve, check that the arrow points in the direction of flow.

3.  Insert the fixing bolts.
4.  Tighten the flange bolts hand-tight as the tool holding the flanges apart is gradually removed. 

Make sure that the flanges remain correctly aligned.

5.  Tighten all flange bolts in opposite pair sequence. Refer to following table for tightening 

torques.

6.9 Recommended tightening torques for mounting flange bolts

Summary of Contents for Neotecha NTB

Page 1: ...hat the user is qualified to Qualified Personnel level Operating staff must be given appropriate training in the operating and maintenance instructions 2 SAFETY Please also read through these notes carefully 2 1 General potential danger due to a Failure to observe the instructions b Improper use c Insufficiently qualified personnel 2 2 Correct use 2 2 1 Area of application Ball valves are bubble t...

Page 2: ...utions should be taken to protect against burns due to high or freezing temperatures In particular insulated gloves should be worn when using the hand lever for example In case of fire the mechanical strength of the PTFE seals is no longer guaranteed above 200 C 2 2 5 Usage restrictions Before the valve is installed a check should be made on the extent to which the coating of the surfaces is resis...

Page 3: ... information should be carefully noted down each time Ball valves in the size range DN 15 to DN 25 have a standard rating plate with no CE mark Ball valves in the size range DN 40 to DN 150 are provided with a rating plate with a CE mark Additional identification on the valve in accordance with DIN 19 such as DN PN manufacturer s logos of the Neotecha AG company The identification of the valve bod...

Page 4: ... the hand lever can be provided with limit switches which indicate open or closed For installation in exposed places shaft extensions in various lengths are available for all sizes 6 6 Bolted joints in the pipeline All flange bolts must be used even on low pressure systems The specified tightening toques for the bolts must always be adhered to 6 7 Body variants NTB and NTC ball valves have the sam...

Page 5: ... mm inches Nm 6 9 1 Recommended tightening torques for NTB NTC ball valves DIN PN 16 and JIS 10K RECOMMENDED TORQUES DN Bolts Class Torque mm inches UNC lbf ft 6 9 2 Recommended tightening torques for NTB NTC ball valves ANSI B 16 10 class 150 lbs 6 8 Step by step valve installation 1 Check that the distance between flanges matches the face to face dimension of the ball valve Before installing the...

Page 6: ...t is installed or existing protective equipment repaired 9 USE 9 1 Operation general NTB series ball valves should only be used in the fully open or fully closed position as they are not designed for flow regulation Intermediate settings can result in turbulence leading to vibrations in the pipeline system which then generates noise If the flow has to be regulated an NTC series C valve should be u...

Page 7: ...the information in accordance with the rating plate fitted on the mounting flange when ordering seals and other spare parts 14 DISPOSAL Hand in the correctly cleaned valve to the scrap material recycling plant Badly cleaned valves can cause severe burning of the hands and other parts of the body If the valve is passed on to a third party the manufacturer no longer guarantees the valve 10 SERVICING...

Page 8: ...son logo are trademarks and service marks of Emerson Electric Co All other marks are the property of their respective owners The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or the...