Mentor MP User Guide
113
Issue: 3 www.controltechniques.com
Parameter
Range(
Ú
)
Default(
Ö
)
Type
6.01
Stop mode
0 to 2
1
RW Uni
US
6.03
Main loss ride through
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.04
Start/stop logic select
0 to 4
4
RW Uni
US
6.08
Hold zero speed
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.09
Catch a spinning motor
0 to 1
1
RW Uni
US
6.12
Enable stop key
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.13
Enable forward/reverse key
0 to 2
0
RW Uni
US
6.15
Drive enable
OFF (0) or On (1)
On (1)
RW Bit
US
6.16
Electricity cost per kWh
0.0 to 600.0 currency units per kWh
0.0
RW Uni
US
6.17
Reset energy meter
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.18
Time between filter changes
0 to 30,000 hrs
0
RW Uni
US
6.19
Filter change required / change done
OFF (0) or On (1)
OFF (0)
RW Bit
PT
6.20
Powered-up time: years.days
0 to 9.364 Years.Days
RW Uni
NC PT
6.21
Powered-up time: hours.minutes
0 to 23.59 Hours.Minutes
RW Uni
NC PT
6.22
Run time: years.days
0 to 9.364 Years.Days
RO Uni
NC PT PS
6.23
Run time: hours.minutes
0 to 23.59 Hours.Minutes
RO Uni
NC PT PS
6.24
Energy meter: MWh
±9999 MWh
RO Bi
NC PT PS
6.25
Energy meter: kWh
±999 kWh
RO Bi
NC PT PS
6.26
Running cost
±32000
RO Bi
FI NC PT
6.27
Time before filter change due
0 to 30,000 hrs
RO Uni
NC PT PS
6.28
Select clock for trip log time stamping
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.29
Hardware enable
RO Bit
NC PT
6.30
Sequencing bit: Run forward
OFF (0)
RW Bit
NC
6.31
Sequencing bit: Jog
RW Bit
NC
6.32
Sequencing bit: Run/reverse
RW Bit
NC
6.33
Sequencing bit: Forward/reverse
RW Bit
NC
6.34
Sequencing bit: Run
RW Bit
NC
6.35
Forward limit switch
RW Bit
NC
6.36
Reverse limit switch
RW Bit
NC
6.37
Sequencing bit: Jog reverse
RW Bit
NC
6.39
Sequencing bit: Not stop
RW Bit
NC
6.40
Enable sequencer latching
RW Bit
US
6.41
Drive event flags
0 to 65535
0
RW Uni
NC
6.42
Control word
0 to 32767
0
RW Uni
NC
6.43
Control word enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.45
Force cooling fan to run at full speed
RW Bit
US
6.49
Disable multi-module drive module
number storing on trip
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.50
Drive comms state
0 to 3
RO Txt
NC PT
6.52
Zero reference interlock
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.54
Run rising edge delay
0 to 25.0s
0.3
RW Uni
US
6.55
Contactor active
OFF (0) or On (1)
RO Bit
NC PT
6.56
Drive active falling edge delay
0 to 255s
0s
RW Uni
US
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save
Summary of Contents for MP105A4
Page 182: ...0476 0000 03 ...