12 Technical data
12.1 Drive technical data
12.1.1 Power and current ratings
The power ratings for the 480V, 575V and 690V configurations are
shown in Table 12-1, Table 12-2 and Table 12-3.
The continuous current ratings given are for a maximum ambient
temperature of 40°C and an altitude of 1000m. For operation at higher
temperatures and altitudes derating is required.
The maximum continuous output current rating of the drive should be
‘derated’ for operation at altitudes above 1000m. The derating is to be
1% derating of rated output current per 100m above 1000m to a
maximum derating of 20% at 3000m.
Table 12-1 480V current ratings
Table 12-2 575V current ratings
* For this rating at 575V, 150% overload time is 20s at 40
°
C and 30s at
35
°
C
Table 12-3 690V current ratings
* For this rating at 690V, 150% overload time is 20s at 40
°
C and 30s at
35
°
C
Maximum continuous input current
The values of maximum continuous input current are given to aid the
selection of cables and fuses. These values are stated for worst-case
conditions.
For current ratings above 1850A then parallel connection of the drives is
required. However, this function is not implemented on firmware
versions V01.05.00 and earlier.
12.1.2 Typical short-term overload limits
The maximum percentage overload limit changes depending on the
selected motor
Variations in motor rated current will result in changes in the maximum
possible overload as detailed in the
Mentor MP
Advanced User Guide
.
Figure 12-1 can be used to determine the maximum overload duration
available for overloads between 100% and 150%. For example the
maximum overload available for a period of 60 seconds is 124%.
Figure 12-1 Maximum overload duration available
Overload of 150% for 30s is available up to a maximum of 10 repetitions
per hour.
Model
AC input
current
DC output current
Typical motor
power
Continuous Continuous
150%
overload
@
400Vdc
@
500Vdc
A
A
A
kW
hp
MP25A4(R)
22
25
37.5
9
15
MP45A4(R)
40
45
67.5
15
27
MP75A4(R)
67
75
112.5
27
45
MP105A4(R)
94
105
157.5
37.5
60
MP155A4(R)
139
155
232.5
56
90
MP210A4(R)
188
210
315
75
125
MP350A4(R)
313
350
525
125
200
MP420A4(R)
376
420
630
150
250
MP550A4(R)
492
550
825
200
300
MP700A4(R)
626
700
1050
250
400
MP825A4(R)
738
825
1237.5
300
500
MP900A4(R)
805
900
1350
340
550
MP1200A4(R)
1073
1200
1800
450
750
MP1850A4(R)
1655
1850
2775
700
1150
Model
AC input
current
DC output current
Typical motor
power
(With Vdc =
630V)
Continuous Continuous
150%
overload
A
A
A
kW
hp
MP25A5(R)
22
25
37.5
14
18
MP45A5(R)
40
45
67.5
25
33
MP75A5(R)
67
75
112.5
42
56
MP105A5(R)
94
105
157.5
58
78
MP155A5(R)
139
155
232.5
88
115
MP210A5(R)
188
210
315
120
160
MP350A5(R)
313
350
525
195
260
MP470A5(R)
420
470*
705
265
355
MP700A5(R)
626
700
1050
395
530
MP825A5(R)
738
825*
1237.5
465
620
MP1200A5(R)
1073
1200
1800
680
910
MP1850A5(R)
1655
1850
2775
1045
1400
Model
AC input
current
DC output Current
Typical motor
power (With
Vdc = 760V)
Continuous Continuous
150%
Overload
A
A*
A
kW
hp
MP350A6(R)
313
350
525
240
320
MP470A6(R)
420
470*
705
320
425
MP700A6(R)
626
700
1050
480
640
MP825A6(R)
738
825*
1237.5
650
850
MP1200A6(R)
1073
1200
1800
850
1150
MP1850A6(R)
1655
1850
2775
1300
1750
NOTE
100
105
110
115
120
125
130
135
140
145
150
155
160
0
10
20
30
40
50
60
70
80
90
10
0
11
0
12
0
13
0
14
0
15
0
16
0
17
0
18
0
20
0
overload duration (seconds)
overload
(%)
NOTE
Summary of Contents for MP105A4
Page 182: ...0476 0000 03 ...