Installation Manual

00825-0100-1600, Rev AB

March 2022

Micro Motion

 1600 Ethernet Transmitters

Ethernet Installations

Summary of Contents for Micro Motion 1600

Page 1: ...Installation Manual 00825 0100 1600 Rev AB March 2022 Micro Motion 1600 Ethernet Transmitters Ethernet Installations ...

Page 2: ...al Product data sheets and manuals are available from the Micro Motion web site at www emerson com Return policy Follow Micro Motion procedures when returning equipment These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees Micro Motion will not accept your returned equipment if you fail to follow Micr...

Page 3: ... 2 Wire the I O channel 17 4 3 Wire the Ethernet channels 23 Chapter 5 Power supply wiring 25 5 1 Wiring the VDC power supply 25 5 2 Wiring the Power over Ethernet PoE power 26 5 3 Wire the power supply using an M12 terminated cable optional 27 Chapter 6 Set up the printer 29 6 1 Set up the printer by changing the printer default IP address 29 6 2 Set up the printer using the printer default IP ad...

Page 4: ...Contents Installation Manual March 2022 00825 0100 1600 4 Micro Motion 1600 Ethernet Transmitters ...

Page 5: ... is not avoided WARNING Serious injury or death could occur if a hazardous situation is not avoided CAUTION Minor or moderate injury will or could occur if a hazardous situation is not avoided NOTICE Data loss property damage hardware damage or software damage can occur if a situation is not avoided There is no credible risk of physical injury Physical access NOTICE Unauthorized personnel can pote...

Page 6: ...e information Micro Motion 1600 Product Data Sheet Micro Motion 1600 with Ethernet Transmitters Configuration and Use Manual Micro Motion 1600 Transmitters Ethernet Rockwell RSLogix Integration Guide Micro Motion Ethernet PROFINET Siemens Integration Guide Sensor installation manual Before you begin Installation Manual March 2022 00825 0100 1600 6 Micro Motion 1600 Ethernet Transmitters ...

Page 7: ...e maximum cable length does not exceed 60 ft 18 m Ensure that you use the following cables for the different connections A twisted pair instrument cable for the Channel B I O connection A suitable shielded or unshielded Cat5e or a higher rated instrumentation cable for the Ethernet connections to connect the meter 1 Note If the transmitter is powered by the PoE connection use shielded Cat5e cables...

Page 8: ...g for the input output and power connections This length would be in addition to the currently installed wiring Confirm you have the additional wiring necessary for the new installation Before removing the existing transmitter be sure to record the configuration data for the currently installed transmitter At initial startup of the newly installed transmitter you will be prompted to configure the ...

Page 9: ...ow Calibration Factor Density calibration factors D1 D2 K1 K2 TC FD 2 3 Power requirements The 1600 supports DC power or Power Over Ethernet POE through the Channel A Ethernet RJ 45 port DC power Power range is 18 30 VDC Typical power is 3 5 watts Maximum power is 8 watts Polarity sensitive POE power Power range is 44 57 VDC Power Delivery PD classification is 3 Cable sizing formula M 18V R x L x ...

Page 10: ...2 4 1600 transmitters in Ethernet networks Install the 1600 Ethernet transmitter in a star network using an industrial rated shielded Ethernet cable Make sure that each cable is no longer than 328 ft 100 m Connect the 1600 Ethernet transmitter to the host system via a LAN Local Area Network and not a WAN Wide Area Network Follow all network security best practices Planning Installation Manual Marc...

Page 11: ...smitters are installed in a star network Figure 2 1 1600 star network A Programmable Logic Controller PLC B 1600 with Ethernet output C External Ethernet switch Installation Manual Planning 00825 0100 1600 March 2022 Installation Manual 11 ...

Page 12: ...Planning Installation Manual March 2022 00825 0100 1600 12 Micro Motion 1600 Ethernet Transmitters ...

Page 13: ...pe refer to standard EN 60079 14 or national standards If national standards are not in effect adhere to the following guidelines for grounding Use copper wire 14 AWG 2 08 mm2 or larger wire size Keep all ground leads as short as possible less than 1 Ω impedance Connect ground leads directly to earth or follow plant standards Procedure 1 Ground the Coriolis sensor according to the instructions in ...

Page 14: ...e power wiring compartment The external ground screw is located on the outside of the transmitter housing below the transmitter tag Figure 3 2 External ground screw Mounting and sensor wiring Installation Manual March 2022 00825 0100 1600 14 Micro Motion 1600 Ethernet Transmitters ...

Page 15: ...positions but a stop exists that will not allow a full 360 rotation 3 Gently lower the transmitter onto the base confirming that the transmitter is in a locked position 4 Replace the clamp in its original position and tighten the cap screw Torque to 29 in lbf 3 28 N m to 31 in lbf 3 50 N m 3 4 Rotate the transmitter display Configure the software to rotate the transmitter display 0 90 180 or 270 Y...

Page 16: ...Mounting and sensor wiring Installation Manual March 2022 00825 0100 1600 16 Micro Motion 1600 Ethernet Transmitters ...

Page 17: ...Discrete Output 1 ProLink III and the integrated web server can always be connected to Channel A 4 2 Wire the I O channel The Channel 1600 I O can be configured as mA Output Frequency Output Discrete Output 4 2 1 Access the wiring channels Procedure Remove the wiring access cover to reveal the I O wiring terminal block connectors Installation Manual Wiring the channels 00825 0100 1600 March 2022 I...

Page 18: ...nal and pins Figure 4 1 Internally powered mA Output wiring A D C B A mA Output B Channel B C 820 Ω maximum loop resistance Note This resistor is normally built into the signal device d This resistor is not used for HART communications D Signal device Figure 4 2 Externally powered mA Output wiring A E D C B A mA Output B Channel B C 5 30 VDC maximum D See Figure 4 3 E Signal device Wiring the chan...

Page 19: ...onhazardous installations Prerequisites WARNING Meter installation and wiring should be performed only by suitably trained personnel using the appropriate government and corporate safety standards Procedure Wire to the appropriate output terminal and pins Figure 4 4 Internally powered FO wiring A D C B A Frequency Output B Channel B C See Figure 4 5 D Counter Installation Manual Wiring the channel...

Page 20: ...5 30 VDC maximum D 500 mA current maximum E Counter 4 2 4 Wire the Discrete Output Wire the Discrete Output in nonhazardous installations Prerequisites WARNING Meter installation and wiring should be performed only by suitably trained personnel using the appropriate government and corporate safety standards Procedure Wire to the appropriate output terminal and pins Wiring the channels Installation...

Page 21: ... D Counter Figure 4 8 Internally powered DO output amplitude versus load resistance 24 VDC Nom open circuit 0 2 4 6 8 10 12 14 16 18 20 22 24 0 750 1500 2250 3000 A B A Output amplitude V B Load resistor Ω Installation Manual Wiring the channels 00825 0100 1600 March 2022 Installation Manual 21 ...

Page 22: ...ain an A coded M12 terminated cable Procedure 1 Attach the M12 terminated cable to the configuration I O connector on the 1600 transmitter 2 Attach the other cable end using the pinouts described in the following table Figure 4 10 M12 terminated cables to the configuration I O Table 4 1 Cable end I O pinouts Pin identification Wire color Outputs on terminal Signal name Pin 1 Brown Pin3 VDC Wiring ...

Page 23: ...have an overall screen to cover all cores Where permissible connect the overall screen to earth at the host end 360 bonded 4 3 1 Wire an Ethernet network using the RJ45 ports Prerequisites When using a pre terminated RJ45 cable ensure there is no protective boot on the connector as a protective boot will not fit through the conduit Alternatively you can use the RJ45 connector using a shielded fiel...

Page 24: ...M12 terminated cables to the Ethernet I O 2 Attach the other cable end using the pinouts described in the following table Table 4 2 M12 Ethernet I O pinouts Pin identification Wire color Outputs on RJ45 Signal name Pin 1 Orange White Pin1 TDP1 RDP2 Pin 2 Green White Pin 3 RDP1 TDP2 Pin 3 Orange Pin 2 TDN1 RDN2 Pin 4 Green Pin 6 RDN1 RDN2 Wiring the channels Installation Manual March 2022 00825 010...

Page 25: ... the Low Voltage Directive 2014 35 EU European installations verify that the transmitter is located in close proximity to a switch Figure 5 1 Location of power supply wiring terminals and equipment ground Procedure 1 Remove the housing cover and the display where applicable 2 Connect the power supply wires For DC power connect to terminals VDC and VDC 3 Tighten the two screws of the power connecto...

Page 26: ...ce Classification 3 in the IEEE 802 3af and 802 3at standards If the installation uses Cat5e or Cat6 Ethernet cables the transmitter supports both Mode A and Mode B power delivery If the installation uses D code M12 cables the transmitter only supports Mode A power delivery WARNING If the transmitter is in a hazardous area do not remove the housing cover while the transmitter is powered up Failure...

Page 27: ...icable and the housing cover 5 3 Wire the power supply using an M12 terminated cable optional Use this procedure if you are using an M12 terminated cable to wire the power supply Prerequisites Obtain an A coded M12 terminated cable Procedure 1 Attach the M12 terminated cable to the power connector on the 1600 transmitter Installation Manual Power supply wiring 00825 0100 1600 March 2022 Installati...

Page 28: ...annel B 2 Attach the other cable end using the pinouts described in Table 5 2 Note For M12 power supply pinouts only pins 1 and 3 are used Table 5 2 M12 power supply pinouts Pin identification Wire color Outputs on terminal Signal name Pin 1 Brown Pin3 VDC Pin 2 White Pin 1 Channel B Pin 3 Blue Pin 4 VDC Pin 4 Black Pin 2 Channel B Power supply wiring Installation Manual March 2022 00825 0100 1600...

Page 29: ...printer The printer IP address prints after a few minutes 4 Temporarily change the Ethernet address for the PC so that the Ethernet is on the same subnet as the printer Default IP address 192 168 192 168 a From Windows 10 right click the Start button and select Network Connections b Right click the Ethernet connection and select Properties Select Yes on any user account pop up windows c Select Int...

Page 30: ...indows you used in Step 4 7 Configure the 1600 Ethernet transmitter for the printer a Remove the Ethernet cable from the PC and connect it to the 1600 Ethernet transmitter b If you have not already done so configure the transmitter IP address subnet mask and default gateway Display Menu Configuration Ethernet Settings Network Settings ProLink III Device Tools Configuration Network Settings For ins...

Page 31: ...n TM T88VI printer using the printer s default IP address Procedure 1 Connect one end of an Ethernet cable and power supply to the printer 2 Connect the other end of the Ethernet cable to the PC 3 Power on the printer It can take 1 2 minutes for the printer to finish configuring network settings When complete the following ticket prints IP Address 192 168 192 168 SubnetMask 255 255 255 0 Gateway 0...

Page 32: ... From the display From ProLink III Go to Menu Configuration Printer Printer Type Go to Device Tools Configuration Printer and Tickets b Verify that the IP address is 192 168 192 168 6 3 Reset the interface settings Use this procedure if you forgot the IP address of your printer and need to reset the default 192 168 192 168 Procedure 1 Turn off the printer and close the roll paper cover 2 If the co...

Page 33: ...tart a print while another transmitter is printing Configuration items and audit log tickets can take more than 15 minutes to print and use up paper If during this time another transmitter starts a print the new print may either be rejected causing a functional check alert printer offline or the print will be inserted in the middle of the configuration audit log print The functional check alert is...

Page 34: ...Set up the printer Installation Manual March 2022 00825 0100 1600 34 Micro Motion 1600 Ethernet Transmitters ...

Page 35: ...eriod Alert 009 is active The diagnostic routines should complete in approximately 30 seconds The status LED will turn green and begin to flash when the startup diagnostics are complete If the status LED exhibits different behavior an alert is active Postrequisites Although the sensor is ready to receive process fluid shortly after power up the electronics can take up to 10 minutes to reach therma...

Page 36: ...Power up the transmitter Installation Manual March 2022 00825 0100 1600 36 Micro Motion 1600 Ethernet Transmitters ...

Page 37: ...ter display This tool guides you through basic configuration of the transmitter The guided setup allows you to upload configuration files set the transmitter display options configure channels and review sensor calibration data Installation Manual Guided setup 00825 0100 1600 March 2022 Installation Manual 37 ...

Page 38: ...Guided setup Installation Manual March 2022 00825 0100 1600 38 Micro Motion 1600 Ethernet Transmitters ...

Page 39: ... status LEDs indicate the current state of the transmitter STATUS and the current state of the Ethernet network NET From the display the symbol on the right side is the transmitter status LED The symbol NET on the left side is the network status LED The 1600 status LED supports NE107 mode For configuration information see the Micro Motion 1600 with Ethernet Transmitters Configuration and Use Manua...

Page 40: ...ent value of the display variables and their measurement units The LCD panel also provides access to the display menus and alert information From the display menus you can View the current configuration and make configuration changes Perform procedures such as loop testing and zero verification Run batches The alert information allows you to see which alerts are active acknowledge the alerts indiv...

Page 41: ... indicate the associated membrane switch If the menu or the topic is too large for a single display screen the and symbols at the bottom and top of the LCD panel are used to indicate that you must scroll down or up to see more information Figure 9 2 Navigation arrows 4 If you make a menu choice that leads back to the main menu or changes to certain procedures such as zero calibration If display se...

Page 42: ...r the display password 5 If you make a menu choice that requires entering a numeric value or character string the display provides a screen similar to the following Components of the transmitter display Installation Manual March 2022 00825 0100 1600 42 Micro Motion 1600 Ethernet Transmitters ...

Page 43: ...characters are set Activate and hold to save the value 6 To exit the display menu system use either of the following methods Wait until the menu times out and returns to the display variables Exit each menu separately working your way back to the top of the menu system Installation Manual Components of the transmitter display 00825 0100 1600 March 2022 Installation Manual 43 ...

Page 44: ...Components of the transmitter display Installation Manual March 2022 00825 0100 1600 44 Micro Motion 1600 Ethernet Transmitters ...

Page 45: ... converter to connect to the service port terminals USB to USB Type C WARNING If the transmitter is in a hazardous area do not remove the housing cover while the transmitter is powered up Failure to follow these instructions can cause an explosion resulting in injury or death Installation Manual Available service port connection 00825 0100 1600 March 2022 Installation Manual 45 ...

Page 46: ...Available service port connection Installation Manual March 2022 00825 0100 1600 46 Micro Motion 1600 Ethernet Transmitters ...

Page 47: ... Procedure 1 Wire the negative terminal on Channel B from the 1600 Ethernet transmitter to A14 2 Wire the positive terminal on Channel B from the 1600 Ethernet transmitter to either C14 C16 or C18 Figure A 1 Wiring for 1600 Ethernet Channel B DO to 3100 relays F3 C A IEC 127 2 J3 DISC OUT 3 T5A 250V C A F1 C A IEC 127 2 J1 J4 DS1 T5A 250V K3 K2 K1 A B C DISC OUT 2 IEC 127 2 F2 T5A 250V J2 DS2 DISC...

Page 48: ...o Motion Inc All rights reserved The Emerson logo is a trademark and service mark of Emerson Electric Co Micro Motion ELITE ProLink MVD and MVD Direct Connect marks are marks of one of the Emerson Automation Solutions family of companies All other marks are property of their respective owners ...