2 Chapter 1 Product Description
RDU-SIC G2 Card User Manual
Network port
The RDU-SIC G2 card provides one network port which adopts 10/100M Base-T self-adaptable Ethernet port. Its
position is shown in Figure 1-1. See Table 1-2 for default configuration of the network port.
Table 1-2 Default configuration parameters of the network port
Parameter
Network card
IP address
Subnet mask
Default gateway
Default parameter
192.168.0.252
255.255.255.0
192.168.0.1
COM port
The RDU-SIC G2 card supplies three independent COM ports. Their positions are shown in Figure 1-1.
The port adopts RS-485 communication mode; the gold finger adopts RS-485/232C (adaptive) communication mode.
See Table 1-3 for the communication parameters.
Table 1-3 Communication parameters of COM port
Parameter
Baud rate
Bit
Parity
Stop bit
Value
1200bps, 2400bps,
4800bps, 9600bps,
19200bps (optional)
5 ~ 8 bits
Even/Odd/None/Mark/Space
1 ~ 2 bits
Note: The combination mode of 5-bit word size and 2-bit stop bit is not supported
1.2 Main Functions
The main functions of RDU-SIC G2 card are listed in Table 1-4.
Table 1-4 Main functions of RDU-SIC G2
Main function
Description
Device monitoring
Realizing camera viewing in data center; getting and handling the data of different intelligent devices and
controlling them through Web interface
Safe shutdown
Shutdown
schedule
Configure the maintenance policy of the UPS, and can periodically reboot or close the
supervised UPS
Sever shutdown
Used together with the NetworkShutdown software. When the UPS has certain critical
alarm, the system will notify the server shutdown to avoid the sever going down
Alarm
Management
Current alarm
Displaying alarm in real time, and confirming the current alarm
History alarm
Querying the history alarm
Alarm notification
1. Can be customized according to user requirements, that is, alarm notification
content can be customized;
2. You can choose the communication mode to receive alarm information of different
level from different equipment;
3. The communication mode includes Email, SMS and phone;
4. Email supports SSL function;
5. Supplying alarm test function to test whether or not users have received the alarm
notification information;
6. Sending the system running status periodically according to user configuration
Data & History
Device information
Querying the main data of equipment
History data
Querying the history data
History log
Querying the log data
Clear history
Clearing the history data and log data
Device Options
Device
management
1. Can add, modify and delete equipment actively, and support adding four pieces of
intelligent equipment at most;
2. Can install and uninstall equipment type and support connecting third party
equipment
Note: The default installed equipment cannot be deleted and modified
Signal setting
Modifying equipment name and alarm level online
Batch
configuration
Updating and downloading configuration files and system files