Chapter 3 Web Page Of RDU-SIC G2 27
RDU-SIC G2 Card User Manual
Click the
Network Setting
under the
System Options
menu, and then click the
Access Management
tab, the page
shown in Figure 3-46 pops up.
Figure 3-46 Access management
In the event of adding visitor, in the textbox of
IP Address of RDU Manager
, type the new IP address of the RDU
manager, and click the
Add Visitor
button to finish the configuration.
Note
1. Up to three RDU manager IP addresses can be added in the system.
2. In the event of adding visitor, if you select to use an agent, you also need to configure the agent server.
3. SNMP Configuration
Click the
Network Setting
under the
System Options
menu, and then click the
SNMP Configuration
tab, you can
configure SNMP agent. The RDU-SIC G2 system supports V2 and V3 versions of SNMP agent.
As shown in Figure 3-47, the specific setting method of SNMP V2 is as follows:
1) Set
NMS IP
(host IP address of SNMP agent data receiving end);
2) Set
Trap Level
:
‘Enable’ or ‘disable’;
3) Keep defaults for other items.
Figure 3-47 SNMP V2 setting
As shown in Figure 3-47, the specific setting method of SNMP V3 is as follows:
1) Set
NMS IP
(host IP address of SNMP agent data receiving end);
2) Set the
Trap Level
:
‘Enable’ or ‘disable’;
3) Set the
Name
;
Summary of Contents for Liebert Vertiv RDU-SIC G2
Page 2: ......