background image

Installation Drawings

90

Figure 71 Control wire list, external interconnections, Multi-Module System, Module 3/SCC, Cable 

Groups #20 & #21

96

-797

619-5

4A

Re

v.

 04

Summary of Contents for Liebert Series 610

Page 1: ...AC Power For Business Critical Continuity Liebert Series 610 UPS Installation Manual 500 750kVA 60Hz Three Phase Multi Module ...

Page 2: ...information available Part numbers _________________________________________________________________ Serial numbers ________________________________________________________________ Rating _______________________________________________________________________ Date purchased _______________________________________________________________ Date installed ______________________________________________...

Page 3: ...Open Rack Batteries 12 6 0 CONFIGURING YOUR NEUTRAL AND GROUND CONNECTIONS 13 6 1 Preferred Grounding Configuration Wye Connected Service 14 6 2 Alternate Grounding Configuration Wye Connected Service 15 6 3 Preferred Grounding Configuration With Isolated Bypass 16 6 4 Alternate Grounding Configuration Non Isolated 17 6 5 Grounding Configuration Corner Grounded Delta or Impedance Grounded Wye 18 6...

Page 4: ...e drawing 625 750kVA Multi Module UPS 12 pulse rectifier 41 Figure 23 Terminal details 625 750kVA Multi Module UPS 12 pulse rectifier 42 Figure 24 Outline drawing 500kVA Multi Module UPS 12 pulse rectifier with bottom entry wireway 43 Figure 25 Terminal details 500kVA Multi Module UPS 12 pulse rectifier with bottom entry wireway 44 Figure 26 Outline drawing 625 750kVA Multi Module UPS 6 pulse rect...

Page 5: ...ol Cabinet Part 3 of 3 Cable Group 8 81 Figure 63 Control wire list external interconnections Multi Module System remote status panel option Cable Group 4 82 Figure 64 Control wire list external interconnections Multi Module System SCC with momentary duty static switch customer alarm interface option Cable Group 9 83 Figure 65 Control wire list external interconnections Multi Module System alarm s...

Page 6: ...terminals factory supplied 28 Table 3 Torque specifications 28 Table 4 Field supplied lugs 29 Table 5 Table 310 16 National Electrical Code Reprint 30 Table 6 Site planning data 600V input 100 Table 7 Site planning data 480V input 101 Table 8 System Control Cabinet data SCCT 102 ...

Page 7: ... DC as well as AC voltages Check for voltage with both AC and DC voltmeters prior to making contact WARNING Under typical operation and with all UPS doors closed only normal safety precautions are necessary The area around the UPS system should be kept free of puddles of water excess moisture and debris Special safety precautions are required for procedures involving handling installation and main...

Page 8: ... generates uses and radiates radio frequency energy and if not installed and used in accordance with this instruction manual may cause harmful interference to radio communications Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense NOTE Liebert Corporation neither recommends nor knowingly sells this product for use with life sup...

Page 9: ...104 F 40 C without derating The batteries should not exceed 77 F 25 C At elevations above 4000 ft 1219m temperature derating may be required for full power output consult your Liebert sales representative or call 1 800 LIEBERT 7 Even though your Liebert UPS unit is at least 92 94 efficient the heat output is substantial For more specific information see Appendix A Be sure environmental conditionin...

Page 10: ...ti Module 500 to 750kVA UPS Figure 2 UPS Multi Module Unit block diagram NOTE The instantaneous trip setting of the breaker feeding the SCC bypass input should be high enough to accommodate short duration overloads The bypass static switch inside the SCC can draw up to 10 times the system s rated current for up to three cycles UPS MODULE ...

Page 11: ...or operated system breakers The SCCT is painted the same color as the Liebert UPS but does not match the sheet metal style of the UPS For SCCT dimensions refer to Table 8 2 SCCI has the system control logic circuit breakers and static bypass switch integrated into a switchboard cabinet manufactured by others 3 SCCC is an integrated configuration like the SCCI with the static bypass switch rated fo...

Page 12: ...atch up of sections as identified by labels and drawings WARNING Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel The UPS module weight ranges from 5710 to 12 005 lbs 2590 to 5445kg Battery cabinets weigh from 3060 to 5300 lbs 1388 to 2404kg Locate center of gravity symbols before handling cabinet Test lift and balance the cabinet before transportin...

Page 13: ...s and remove cabinet panels to check for shipping damage to internal components 4 Check for loose connections or unsecured components in the cabinet s 5 Check for installation of circuit breaker line safety shields There should be no exposed circuit breaker terminals when the cabinet doors are opened 6 Check for any unsafe condition that may be a potential safety hazard 7 UPS modules are shipped w...

Page 14: ...pment to fully open all doors without restriction See drawings and local codes SCCT requires front and rear or one side access for installation and maintenance b Verify that there is adequate area in front of circuit breakers to perform maintenance Check installation drawings for location of breakers Check with local codes c Verify that there is adequate clearance above all cabinets to allow exhau...

Page 15: ... tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnecting battery terminals Determine if battery is inadvertently grounded If inadvertently grounded remove source of ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock will b...

Page 16: ...as poser d outils ou d objets métalliques sur les batteries Déconnecter la source de chargement avant de connecter ou de déconnecter les bornes de batterie Vérifier que la batterie n a pas été mise à la masse par inadvertance Si elle est mise à la masse éliminer la source de masse Tout contact avec des composants de batterie mise à la masse peut entraîner un choc électrique Éliminer le risque de c...

Page 17: ...iently next to each UPS module The front access only design eliminates side and rear service clearance requirements 5 Reinstallation If at any time it becomes necessary to move the battery cabinet to another location contact Liebert Global Services to inspect the internal battery hold down straps 6 Environment Locate the battery cabinet in a clean dry environment Recommended temperature range for ...

Page 18: ...es with manufacturer s specification Installations using vented lead acid batteries MUST have adequate ventilation to remove explosive gases per local and national codes 3 Low voltage control wiring must be kept separate from power wiring and run in separate conduits 4 Ensure that battery racks are properly grounded according to code requirements in your area If you have any questions concerning b...

Page 19: ...stems with 208 208 VAC What is the connected load Does the critical load consist of one or more Power Distribution Units PDUs Do the PDUs have isolation transformers Proper grounding should be based on NEC Section 250 but safe and proper equipment operation requires further enhancements The following pages detail Liebert s recommendations for grounding various system configurations to ensure optim...

Page 20: ...ity sized neu tral is recommended between the UPS module and the SCC for best system performance The SCC neutral is solidly connected to the building service neutral which is bonded to the grounding conduc tor at the service entrance equipment The isolation transformers in the PDUs are considered a separately derived source Therefore the PDU neutral should be bonded to the PDU grounding conductor ...

Page 21: ...current must flow In the previous configuration the current flows through the neutral conductor In this configuration the current flows through the ground path possibly tripping ground fault interrupters GFIs and distorting the bypass waveform reference Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping Figure 5 Alternate grounding configuration wye connected se...

Page 22: ...he grounding conductor can theoretically be done at either the SCC or the Bypass Transformer However we recommend bonding at the Bypass Transformer because the UPS module will sometimes be powered down for maintenance and its output transformer will be out of the circuit The neutral should be bonded to ground and a local grounding electrode should be installed at the Bypass Transformer per NEC 250...

Page 23: ...ed source The UPS module output neutral and the load neutral are solidly connected to the building service neutral which is bonded to the grounding conductor at the service entrance equipment Figure 7 Alternate grounding configuration non isolated This arrangement may be used for systems with 208 VAC input and output However it does not pro vide any isolation or common mode noise attenuation for s...

Page 24: ...output neutral to achieve this When the building service is delta connected however the installer must take special steps to ensure reliable UPS functioning If the building service is corner grounded delta or impedance grounded wye the UPS requires the Series 610 Isolated Neutral Kit as do each of the UPS modules This kit uses control isolation trans formers to create a reference point For this ap...

Page 25: ...e Grounding Config uration Wye Connected Service except for the wye input The UPS input and bypass must be fed from the same source The load must be strictly 3 wire And the GFI time delay should be set to at least 0 2 seconds to prevent tripping during transfer or retransfer operations CAUTION Failure to properly set the ground fault interrupters could cause loss of power to the critical load ...

Page 26: ...ery systems are not possible with battery cabinet systems Whether the battery system is open rack or cabinet the metal rack parts or cabinet must be grounded to the UPS module ground bus Figure 10 illustrates how a simple one cabinet system would be grounded For systems with multi ple cabinets the same configuration would apply However for simplicity the installer can connect all the battery cabin...

Page 27: ...g cables or making any electrical connections NOTE The instantaneous trip setting of the bypass feeder breaker should be high enough to accommodate short duration overloads The bypass static switch inside the SCC can draw up to 10 times the system s rated current for up to three cycles in the event of a downstream fault NOTE Use 75 C copper wire Select wire size based on the ampacities in Table 5 ...

Page 28: ...ly derived system at the supply transformer or motor generator set in accordance with the instructions in 6 0 Configuring Your Neutral and Ground Connections c The attachment plug receptacles in the vicinity of the unit or system are all to be of a grounding type and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment 4 Observe clockwise ...

Page 29: ...ad SBB SBS MBB System Controls I R 2 UPS CB1 CB2 I R 1 UPS CB1 System Controls I R 3 UPS CB1 CB I I I 2 RIB RIB CB2 SKRU RIB BFB MIB Output SBB SBS MBB SCCT can accomodate up to 6 UPS modules To Critical Load Battery MBD SCCT Battery MBD Battery MBD BIB UOB UOB These configurations are for illustrative purposes only They represent only a sample of the possible configurations Refer to the submittal...

Page 30: ...ance bypass switchgear Cable groups 20 and 21 carry signals for general housekeeping modules to SCC Other cable groups will be required for other optional equipment If your system has any installed options special wire lists will be included in your Submittal Drawing Package Contact your Liebert Sales Representative for assistance if the submittal drawings have been lost or misplaced Figures 55 th...

Page 31: ...nnected for safety during shipment Do not complete these connections A Liebert Global Services representative will complete these connections as part of start up An improperly installed unit can result in injury to personnel or damage to equipment CAUTION Be sure polarity is correct when wiring the battery cabinet to the connected equipment positive to positive negative to negative If polarity is ...

Page 32: ...ordance with all applicable national and local electrical codes Improper wiring may cause damage to the UPS or injury to personnel CAUTION All shielded cables non shielded cables non shielded control wires non shielded battery breaker control wires and non shielded remote control wires must be housed in individual separate steel conduits Placing multiple cables in the same conduit with other contr...

Page 33: ... be run in individual separate steel conduit 13 Emergency Power Off control wiring to SCC must be run in separate steel conduit 14 Optional communications wiring to SCC for terminals site monitoring or modem must be run in separate steel conduit 15 Any additional special wiring required at your site Refer to Figures 58 through 74 or your submittal drawings CAUTION UPS bypass and system output neut...

Page 34: ... Rectifier input is top entry directly to lugs on top of input circuit breaker 625 750kVA standard models with standard input Busbars for AC output Neutral and Ground are provided on the right side of module with top or bottom cable entry Rectifier input is top entry directly to lugs on top of input circuit breaker DC input is top entry to busbars 750kVA 675 kW and other modules with optional inpu...

Page 35: ... 5 4 0 AWG 3 8 1 20 M973 12 714255 86 6 Color Keyed Aluminum Copper 1 AWG 3 8 0 75 60124 7 1 0 AWG 3 8 0 88 60130 8 2 0 AWG 3 8 0 97 60136 9 3 0 AWG 3 8 1 06 60142 10 Color Keyed Copper Cable Long Barrel 1 AWG 5 16 0 67 54947BE 11 1 0 AWG 3 8 0 75 54909BE 12 2 0 AWG 3 8 0 81 54910BE 13 3 0 AWG 1 2 0 94 54965BE 14 4 0 AWG 1 2 1 03 54970BE 15 250 MCM 1 2 1 09 54913BE 16 Narrow Tongue Copper Cable 35...

Page 36: ...0 535 555 585 285 310 320 330 355 340 375 385 395 425 385 420 435 450 480 600 700 750 800 900 1000 1250 1500 1750 2000 455 495 520 545 560 545 590 625 650 665 615 665 705 735 750 375 405 435 455 470 445 485 520 545 560 500 545 585 615 630 1000 1250 1500 1750 2000 CORRECTION FACTORS Ambient Temp C For ambient temperatures other than 30 C 86 F multiply the allowable ampacities shown above by the app...

Page 37: ...Installation Drawings 31 10 0 INSTALLATION DRAWINGS Figure 12 One line diagram two module parallel system with two breaker maintenance bypass 97 797600 169 Rev 03 ...

Page 38: ...Installation Drawings 32 Figure 13 One line diagram four module parallel system with three breaker maintenance bypass 97 797600 176 Rev 03 ...

Page 39: ...Installation Drawings 33 Figure 14 Outline drawing 500kVA Multi Module UPS 6 pulse rectifier 480V input 480 277V output 88 797658 84 Rev 10 ...

Page 40: ...Installation Drawings 34 Figure 15 Terminal details 500kVA Multi Module UPS 6 pulse rectifier 480V input 480 277V output 88 797658 94 Rev 08 ...

Page 41: ...Installation Drawings 35 Figure 16 Outline drawing 500kVA Multi Module UPS 6 pulse rectifier 600V input 600 346V output 88 797657 26 Rev 03 ...

Page 42: ...Installation Drawings 36 Figure 17 Terminal details 500kVA Multi Module UPS 6 pulse rectifier 600V input 600 346V output 88 797657 95 Rev 03 ...

Page 43: ...Installation Drawings 37 Figure 18 Outline drawing 500kVA Multi Module UPS 12 pulse rectifier 88 797657 25 Rev 06 ...

Page 44: ...Installation Drawings 38 Figure 19 Terminal details 500kVA Multi Module UPS 12 pulse rectifier 88 797657 92 Rev 08 ...

Page 45: ...Installation Drawings 39 Figure 20 Outline drawing 625 750kVA Multi Module UPS 6 pulse rectifier 88 797668 84 Rev 06 ...

Page 46: ...Installation Drawings 40 Figure 21 Terminal details 625 750kVA Multi Module UPS 6 pulse rectifier 88 797668 90 Rev 07 ...

Page 47: ...Installation Drawings 41 Figure 22 Outline drawing 625 750kVA Multi Module UPS 12 pulse rectifier 88 797665 29 Rev 07 ...

Page 48: ...Installation Drawings 42 Figure 23 Terminal details 625 750kVA Multi Module UPS 12 pulse rectifier 88 797665 90 Rev 09 ...

Page 49: ...Installation Drawings 43 Figure 24 Outline drawing 500kVA Multi Module UPS 12 pulse rectifier with bottom entry wireway 88 797656 66 Rev 05 ...

Page 50: ...Installation Drawings 44 Figure 25 Terminal details 500kVA Multi Module UPS 12 pulse rectifier with bottom entry wireway 88 797656 86 Rev 04 ...

Page 51: ...Installation Drawings 45 Figure 26 Outline drawing 625 750kVA Multi Module UPS 6 pulse rectifier with bottom entry wireway 88 797668 66 Rev 05 ...

Page 52: ...Installation Drawings 46 Figure 27 Terminal details 625 750kVA Multi Module UPS 6 pulse rectifier with bottom entry wireway 88 797668 86 Rev 06 ...

Page 53: ...Installation Drawings 47 Figure 28 Outline drawing 625 750kVA Multi Module UPS 12 pulse rectifier with bottom entry wireway 88 797664 68 Rev 05 ...

Page 54: ...Installation Drawings 48 Figure 29 Terminal details 625 750kVA Multi Module UPS 12 pulse rectifier with bottom entry wireway 88 797664 88 Rev 06 ...

Page 55: ...Installation Drawings 49 Figure 30 Terminal details 750kVA 675kW Multi Module UPS 12 pulse rectifier with bottom entry wireway 88 797677 65 Rev 04 ...

Page 56: ...Installation Drawings 50 Figure 31 Base mounting patterns 500kVA module 6 pulse rectifier 88 797613 16 Rev 06 ...

Page 57: ...Installation Drawings 51 Figure 32 Base mounting patterns 500kVA module 12 pulse rectifier 88 797613 22 Rev 04 ...

Page 58: ...Installation Drawings 52 Figure 33 Base mounting patterns 500kVA module 12 pulse rectifier with bottom entry wireway 88 797613 28 Rev 04 ...

Page 59: ...Installation Drawings 53 Figure 34 Base mounting patterns 625 750kVA module 6 pulse rectifier 88 797613 20 Rev 04 ...

Page 60: ...Installation Drawings 54 Figure 35 Base mounting patterns 625 750kVA module 6 pulse rectifier with bottom entry wireway 88 797613 29 Rev 04 ...

Page 61: ...Installation Drawings 55 Figure 36 Base mounting patterns 625 750kVA module 12 pulse rectifier 88 797613 19 Rev 04 ...

Page 62: ...Installation Drawings 56 Figure 37 Base mounting patterns 625 750kVA module 12 pulse rectifier with bottom entry wireway 88 797613 27 Rev 05 ...

Page 63: ...Installation Drawings 57 Figure 38 Shipping split detail 500kVA 12 pulse rectifier 88 797612 01 Rev 04 ...

Page 64: ...Installation Drawings 58 Figure 39 Shipping split detail 500kVA 12 pulse rectifier with bottom entry wireway 88 797612 08 Rev 04 ...

Page 65: ...Installation Drawings 59 Figure 40 Shipping split detail 625 750kVA 6 pulse rectifier 88 797612 04 Rev 04 ...

Page 66: ...Installation Drawings 60 Figure 41 Shipping split detail 625 750kVA 6 pulse rectifier with bottom entry wireway 88 797612 09 Rev 05 ...

Page 67: ...Installation Drawings 61 Figure 42 Shipping split detail 625 750kVA 12 pulse rectifier 88 797612 03 Rev 05 ...

Page 68: ...Installation Drawings 62 Figure 43 Shipping split detail 625 750kVA 12 pulse rectifier with bottom entry wireway 88 797612 07 Rev 05 ...

Page 69: ...Installation Drawings 63 Figure 44 Battery power pack system 88 797616 03 Rev 08 ...

Page 70: ...Installation Drawings 64 Figure 45 Battery power pack Size A 88 797616 01 Rev 10 ...

Page 71: ...Installation Drawings 65 Figure 46 Line up detail 300 500kVA Single or Multi Module System with battery cabinets 88 797607 63 Rev 04 ...

Page 72: ...Installation Drawings 66 Figure 47 Outline drawing System Control Cabinet SCCT 200 1200A 88 797614 01 Rev 08 ...

Page 73: ...Installation Drawings 67 Figure 48 Base mounting patterns System Control Cabinet SCCT 200 1200A 88 797613 71 Rev 08 ...

Page 74: ...Installation Drawings 68 Figure 49 Outline drawing System Control Cabinet SCCT 1600 2000A 88 797614 02 Rev 07 ...

Page 75: ...Installation Drawings 69 Figure 50 Base mounting patterns System Control Cabinet SCCT 1600 2000A 88 797613 78 Rev 07 ...

Page 76: ...Installation Drawings 70 Figure 51 Outline drawing System Control Cabinet SCCT 2500 3000A 88 797614 03 Rev 08 ...

Page 77: ...Installation Drawings 71 Figure 52 Base mounting patterns System Control Cabinet SCCT 2500 3000A 88 797613 73 Rev 06 ...

Page 78: ...Installation Drawings 72 Figure 53 Outline drawing System Control Cabinet SCCT 4000A 88 797614 04 Rev 08 ...

Page 79: ...Installation Drawings 73 Figure 54 Base mounting patterns System Control Cabinet SCCT 4000A 88 797613 72 Rev 07 ...

Page 80: ...Installation Drawings 74 Figure 55 Control connection location diagram Multi Module System 300 500kVA 96 797619 58A Rev 03 ...

Page 81: ...Installation Drawings 75 Figure 56 Control connection location diagram Multi Module System 625 750kVA 96 797619 66A Rev 03 ...

Page 82: ...Installation Drawings 76 Figure 57 Control connection location diagram SCCT 96 797619 88A Rev 04 ...

Page 83: ...Installation Drawings 77 Figure 58 Control wiring external interconnect diagram Multi Module System 96 797619 51A Rev 03 ...

Page 84: ...Installation Drawings 78 Figure 59 Control wire list external interconnections standard wiring Multi Module System UPS module Cable Group 1 96 797619 60 Rev 06 ...

Page 85: ...Installation Drawings 79 Figure 60 Control wire list external interconnections standard wiring Multi Module System System Control Cabinet Part 1 of 3 Cable Groups 2 3 96 797619 19A Rev 03 ...

Page 86: ...Installation Drawings 80 Figure 61 Control wire list external interconnections standard wiring Multi Module System System Control Cabinet Part 2 of 3 Cable Groups 5 6 96 797619 20 Rev 06 ...

Page 87: ...Installation Drawings 81 Figure 62 Control wire list external interconnections standard wiring Multi Module System System Control Cabinet Part 3 of 3 Cable Group 8 96 797619 21 Rev 06 ...

Page 88: ...Installation Drawings 82 Figure 63 Control wire list external interconnections Multi Module System remote status panel option Cable Group 4 96 797619 130 Rev 03 ...

Page 89: ...Installation Drawings 83 Figure 64 Control wire list external interconnections Multi Module System SCC with momentary duty static switch customer alarm interface option Cable Group 9 96 797619 28 Rev 06 ...

Page 90: ...Installation Drawings 84 Figure 65 Control wire list external interconnections Multi Module System alarm status contacts option Cable Group 14 96 797619 128 Rev 04 ...

Page 91: ...Installation Drawings 85 Figure 66 Control wire list external interconnections Multi Module System battery temperature sensor option Cable Group 15 96 797619 62 Rev 06 ...

Page 92: ...Installation Drawings 86 Figure 67 Control wire list external interconnections Multi Module System maintenance bypass interlock option Cable Group 7 96 797619 90 Rev 04 ...

Page 93: ...Installation Drawings 87 Figure 68 Control wire list external interconnections Multi Module System SNMP interface option Cable Group 26 96 797619 91 Rev 02 ...

Page 94: ...Installation Drawings 88 Figure 69 Control wire list external interconnections Multi Module System Module 1 SCC Cable Groups 20 21 96 797619 52A Rev 04 ...

Page 95: ...Installation Drawings 89 Figure 70 Control wire list external interconnections Multi Module System Module 2 SCC Cable Groups 20 21 96 797619 53A Rev 04 ...

Page 96: ...Installation Drawings 90 Figure 71 Control wire list external interconnections Multi Module System Module 3 SCC Cable Groups 20 21 96 797619 54A Rev 04 ...

Page 97: ...Installation Drawings 91 Figure 72 Control wire list external interconnections Multi Module System Module 4 SCC Cable Groups 20 21 96 797619 55A Rev 04 ...

Page 98: ...Installation Drawings 92 Figure 73 Control wire list external interconnections Multi Module System Module 5 SCC Cable Groups 20 21 96 797619 56A Rev 04 ...

Page 99: ...Installation Drawings 93 Figure 74 Control wire list external interconnections Multi Module System Module 6 SCC Cable Groups 20 21 96 797619 57A Rev 04 ...

Page 100: ...Installation Drawings 94 Figure 75 Outline drawing single breaker module battery disconnect 300 450 600 800 1000 1200A 88 797616 09 Rev 08 ...

Page 101: ...Installation Drawings 95 Figure 76 Outline drawing single breaker module battery disconnect 1400AT 1600AT 2000AT 2500AT 600VDC circuit breaker 88 797616 13 Rev 05 ...

Page 102: ...Installation Drawings 96 Figure 77 Outline drawing dual breaker module battery disconnect 600 800 1000 1200A 88 797616 07 Rev 08 ...

Page 103: ...Installation Drawings 97 Figure 78 Outline drawing remote status panel surface mount 88 791617 01 Rev 05 ...

Page 104: ...Installation Drawings 98 ...

Page 105: ...easured at the module at maximum discharge current 7 Grounding conductors to be sized per NEC 250 122 Neutral conductors to be sized for full capacity per NEC 310 15 b 4 for systems with 4 wire loads and half capacity for systems with 3 wire loads 7 continued NOTE A neutral conductor is required from each Multi Module Unit output to the System Control Cabinet and from each SCC to the Power Tie cab...

Page 106: ...214 112 050 32 8 6330 2871 325 1587 500 450 600 NO YES 551 688 481 601 1200 1214 133 550 39 1 96x39x78 2438x991x1981 9030 4096 347 1694 500 450 600 YES YES 510 638 481 601 1200 1214 139 010 40 7 9230 4187 355 1733 625 500 600 NO NO 602 753 601 752 1400 1349 108 950 31 9 108x39x78 2743x991x1981 7805 3540 300 1465 625 500 600 YES NO 559 699 601 752 1400 1349 118 650 34 7 8025 3640 309 1509 625 500 6...

Page 107: ...3 250 30 2 5930 2690 304 1484 500 450 480 NO YES 688 861 601 752 1200 1214 124 550 36 5 96x39x78 2438x991x1981 9030 4096 347 1694 500 450 480 YES YES 638 798 601 752 1200 1214 129 950 38 1 9230 4187 355 1733 625 500 480 NO NO 749 936 752 940 1400 1349 99 300 29 1 108x39x78 2743x991x1981 7405 3359 285 1391 625 500 480 YES NO 694 867 752 940 1400 1349 105 050 30 8 7625 3459 293 1431 625 500 480 NO Y...

Page 108: ...load current Table 8 shows dimensions and weights for SCCT cabinets Table 8 System Control Cabinet data SCCT Type Amps Overall dimensions WxDxH in mm Weight lb kg SCCT 560 1200 37x37x78 940x940x1981 1000 454 SCCT 1600 62x48x78 1575x1219x1981 1525 692 SCCT 2000 62x48x78 1575x1219x1981 2850 1293 SCCT 2500 3000 62x60x78 1575x1524x1981 3100 1406 SCCT 4000 138x60x78 3505x1524x1981 5850 2653 ...

Page 109: ...Site Planning Data Series 610 500 750kVA Multi Module Systems 103 NOTES ...

Page 110: ...Site Planning Data Series 610 500 750kVA Multi Module Systems 104 ...

Page 111: ......

Page 112: ...ebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 monitoring emersonnetworkpower com Outside the US 614 841 6755 Single Phase UPS 800 222 5877 upstech emersonnetworkpower com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech emersonnetworkpower com En...

Reviews: