Installation
Liebert
®
GXT4
™
User Manual
22
2.6.2
Remove the Power Distribution Box
from 5000VA and 6000VA Models
1. Manually transfer the connected equipment to the internal bypass.
a. From the main menu select CONTROL, then press
Enter
.
b. Select TURN ON & OFF and press
Enter
.
c. Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the
internal bypass. (For help, refer to
.)
d. Loosen the captive screw over the maintenance bypass breaker (see
for the breaker’s
location).
e. Turn the maintenance bypass breaker On.
NOTICE
The load is unprotected from disturbances in the power supply while the UPS is on bypass.
2. Turn the output and input breakers Off.
3. Loosen other captive screws until the power distribution box releases.
4. Remove the power distribution box from the UPS and set it aside.
5. Loosen the screws over the plastic cover for the connector on the rear of the panel.
6. Slide the plastic cover over the connector and tighten the screws.
Figure 2-5 Power distribution box removal from 5000VA and 6000VA models
Maintenance Bypass Breaker
Extract these four
captive screws
Pigtails
removed for
clarity
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......