Operation
Liebert
®
GXT4
™
User Manual
46
4.4 Manual Bypass
To manually transfer the connected equipment to the internal bypass:
1. From the main menu select Control then press enter.
2. Select
TURN ON & OFF
and press Enter.
3. Select
TURN UPS BYPASS
and press Enter. The UPS will transfer the connected loads to the internal
bypass.
If the internal bypass is not available because of input power problems, pressing this button once will be
ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If
other indicators are illuminated, refer to
4.5 Shut Down the GXT4
To shut down the UPS from the LCD:
1. From the Main Menu select
CONTROL
, press Enter, then select
TURN ON & OFF
.
2. Press the Enter key.
3. Select
TURN UPS OFF
, then press Enter. Press either the Up or Down button to move the cursor to
confirm the turn off command and press Enter.
The UPS will sound an audible alarm; this is normal.
4. Power to the connected equipment is now Off.
The UPS display will still be illuminated because the batteries are still being charged. The UPS may now
be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds.
4.6 Disconnecting Input Power from the GXT4
1. After the UPS has been shut down as detailed in
, disconnect the input
cable from the wall socket.
2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates
that the power-off is complete.
3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery
cabinet.
After powering Off the UPS, the UPS ceases output and the load is powered Off.
4.7 Maintenance Bypass
Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in
Maintenance Bypass:
1. Place the UPS on internal bypass. This may be done by either of the following methods:
a. Refer to
b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires
loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.
2. Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires
loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......