Programming Setup and UI Navigation for RLDS - Display Screens • 37
1. Press the
ENTER
key to adjust the setting.
2. Use the LEFT/RIGHT cursor keys to move
across the entry field and the UP/DOWN
cursor keys to modify the individual numbers.
3. Press
ENTER
to accept the new entry or
ESC
to revert to the previous setting.
6.17. Password
This field is used to define a system password. The
default setting is
000
, which provides no password
protection.
1. Press the
ENTER
key to adjust the password.
2. Use the LEFT/RIGHT cursor keys to move
across the entry field and the UP/DOWN
cursor keys to modify the individual
alphanumeric characters.
3. Press
ENTER
to accept the new password or
ESC
to revert to the previous setting.
6.18. Additional Service
Features
The Service Mode option is located on the System
Setup Screen in the bottom right corner. When
activated, the Service Mode will disable the RLDS
unit for a specified length of time. The default is 5
minutes. This time interval can be changed as
Access the service mode options from the initial
Data
Display Screen
. Press the
SERVICE MODE
ENTRY
option twice within 3 seconds. To exit the
Service Mode
, again press the
SERVICE MODE
ENTRY
option twice within 3 seconds.
Several features can be viewed on the
System Setup
Screen 3
when the monitor is placed in service mode.
While in service mode, the user can identify the
model number, set digipot values and sensor
temperature, and acquire the temperature coefficient.
6.19.Service Timeout
Displayed in Service Mode. Sets the length of time
the Service Mode is in effect. Stops the monitor for up
to 300 minutes (5 hrs) to allow for servicing the unit.
1. Press the
ENTER
key to adjust the setting.
2. Use the LEFT/RIGHT cursor keys to move
across the entry field and the UP/DOWN
cursor keys to modify the individual numbers.
3. Press
ENTER
to accept the new entry or ESC
to revert to the previous setting.
6.20.DEG Digipot
The DIGIPOT function allows a manual and more
precise adjustment of the digital potentiometer, which
controls the voltage of the IR Detector. The DIGIPOT
is auto-tuned at every power up.
1. Press the
ENTER
key to adjust the setting.
Once the option is selected the screen will also
display the voltage.
2. Use the UP/DOWN cursor key to modify the
Digipot value.
IMPORTANT: Note that while in the Service
Mode no measurements are made, nor are any
alarms activated.
Figure 6-6
- System Setup Screen 3 - Service Mode