E2 Version 3.01 and below Setup for RLDS (without Gateway)RLDS Setup on REFLECS, E2, Einstein, and Supervi
-
sory Controllers • 67
and Controllers
.
3. Under the
I/O Network
tab, set the number of
desired RLDS controllers under
IRLDS
.
4. Press the
key to return to the E2 home
screen and save changes.
5. Set the Gateway to 1. Each Gateway can
handle three RLDS controllers, so if four
RLDS controllers are on the network, two
Gateways are needed. The first Gateway will
be address 1 and the RLDS units are numbered
as 1,2,3. The second Gateway will be
addressed as 4, but the RLDS is set to 1
because all units on the Gateway are numbered
sequentially 1 to 3. The RLDS controllers are
always numbered 1 to 3 when connected to the
Gateway.
To see a summary of RLDS controllers on the
network:
1. Press
- Configured Applications
.
2. Select
185.
for
IR Leak Detection
.
3. The leak detectors are listed on the status
screen. Press the down arrow to highlight a unit
and
to go the setup screen to enter
channel, zone information, and more.
Figure 11-1
- Connected I/O Setup Screen
Figure 11-2
- Configured Applications
Figure 11-3
- RLDS Application Setup Screen
Summary of Contents for GW-810-3760
Page 1: ...Refrigerant Leak Detection System RLDS Installation and Operation Manual 026 1309 Rev 11 ...
Page 37: ...30 RLDS I O Manual 026 1309 Rev 11 Figure 4 22 Connecting the Gateway to the RS485 Network ...
Page 84: ...Appendix B System Menu Map B 79 Appendix B System Menu Map ...