S600 Instruction Manual
Note
:
If the display has not changed after 30 seconds, power down
the S600, wait at least five seconds, and then re-apply power.
6.
Follow steps 1 through 3 in the
Unpowered Cold Start
description.
The S600 builds a new database using the configuration files held
in Flash memory. When this process completes, the S600 Main
menu displays.
7.4
Startup Menu
If the S600 completes its start-up initialization sequence but does not
automatically warm start, the S600 Startup menu displays (see Figure
7-1).
Note
:
After you modify any data in the startup menu, the S600 may
require a power cycle.
1* WARM START
2* COLD START
3* NETWORK SETUP
4. REFLASH FIRMWARE
8* FACTORY SETUP
Figure 7-1. Startup Menu
Startup menu options include: If the S600 completes its start-up
initialization sequence but does not automatically warm start, the S600
Startup menu displays (see Figure 7-1).
Option Description
Warm Start
Restarts a previously configured S600 at the
point prior to being powered down.
Cold Start
Builds a new metering database on the S600
using the configuration files stored in Flash
memory.
Network Setup
Configures the TCP/IP, Gateway, and
Modbus addresses (see Section 7.4.1,
Reflash Firmware
Reprograms the S600 operating system
firmware stored in Flash memory (see
Factory Setup
Clears SRAM and formats Flash memory and
changes additional settings.
Note
: Use this option
only
at the direction of
a factory representative.
Revised Jan-07
Startup
7-3