7.4.1 Network Setup
This option on the Startup menu enables you to define the TCP/IP
Ethernet, Gateway, and Modbus network addresses.
Note
:
Define the necessary network settings
before
you initiate any
network communications. You can
only
view or modify these settings
physically through the Startup menu. (You cannot use the Config600
software to define communications.) The S600 keeps these settings in
a separate area of the SRAM database and retains them after you
download a configuration file to the S600.
Ethernet LAN
Before you establish an Ethernet LAN connection (for host
communications, local operator communications, or web server
access), you must verify or define the TCP/IP address.
To define the Ethernet LAN network address:
1.
Select
NETWORK SETUP
from the Startup menu.
2.
Select either
NETWORK I/F 1
(for the standard Ethernet port) or
NETWORK I/F 2
(for the Dual Ethernet port).
Note
:
The options for TCP/IP address and Subnet mask are valid
for I/F 1 and I/F 2. The Gateway address is available only on I/F 1.
If the second network card (P190) is installed, I/F 1 and I/F 2
must
each use
separate
subnets.
3.
Select
TCP/IP ADDRESS
.
4.
Enter a valid TCP/IP address and press
Enter
.
Note
:
If the displayed TCP/IP address is correct, press
CLEAR
to
return to the menu.
5.
Select
GATEWAY ADDRESS
.
6.
Enter a valid Gateway address and press
Enter
.
Note
:
If the displayed Gateway address is correct, press
CLEAR
to
return to the menu.
7.
Select
SUBNET MASK
.
8.
Enter a valid Subnet mask and press
Enter
.
Note
:
If the displayed Subnet mask is correct, press
CLEAR
to
return to the menu.
9.
Perform a restart to update the system settings.
7-4 Startup
Revised
Jan-07