Instruction Manual
D104239X012
Multiport Flow Selector
January 2019
48
Modbus
Foundation Fieldbus
Configuration and Calibration Registers MAO (Channel 19) MAI (Channel 20)
Register
Parameter
Parameter
211
Port 0 calibration
IN_1
OUT_1
212
Port 1 calibration
IN_2
OUT_2
213
Port 2 calibration
IN_3
OUT_3
214
Port 3 calibration
IN_4
OUT_4
215
Port 4 calibration
IN_5
OUT_5
216
Port 5 calibration
IN_6
OUT_6
217
Port 6 calibration
IN_7
OUT_7
218
Port 7 calibration
IN_8
OUT_8
Note
Input and Output parameters are the number of hardware registers that are connected to the I/O block. They define the
transducers to be used going to or from the physical world.
WARNING
Extreme caution must be used when writing port calibration values to registers 211 through 218. Only values read from
these registers shall be written to them. The purpose of these registers is to allow the network host to store the port
calibration values and then write them back to the actuator in case of replacement of the CPU module.
Note: The network host may write a Port Position Setpoint to Channel 3 (SP/OUT) as a 12-bit unsigned integer analog
value corresponding to 0% to 8% where the percentage relates to the port number 0 to 8. The analog value is
calculated as absolute value of Port Number / 100 * 4095. Example: Analog value for Port 6 = 6/100*4095=245.7 =
245. The actuator will accept the percentage analog value within a tolerance as shown below:
Port 0 =
0
If CA is configured as 1 for Home Port = 8,
Port 1 = 39 – 42
the MPA will accept either 0 or 327 for setpoint
Port 2 = 79 – 82
of Home Port. The acceptable range for Port 8
Port 3 = 120 – 123
is 325 to 329. (see page 21 for CA configuration)
Port 4 = 162 – 165
Port 5 = 203 – 206
Port 6 = 244 – 247
Port 7 = 284 – 288