Group F8: Display Parameters
Para.
Name
LCD Display
Setting Range
Unit
Factory
Setting
Modif.
F8.03
Parameter displayed at
STOP state
STOP DISPLAY
(flashes,
▲
and
▼
key are valid
in frequency
displaying status;
the status will be
saved at power
off)
Binary settings:
0:No display; 1:Display
Unit’s place of LED:
Bit0: Reference frequency(Hz)
Bit1: External counting value(no unit)
Bit2: Spinning speed(R/MIN)
Bit3: Reference speed(R/MIN)
Ten’s place of LED:
Bit0: Line speed(M/S)
Bit1: Reference line speed(M/S)
Bit2: VCI(V)
Bit3: CCI(V)
Hundred’s place of LED:
Bit0: Analog close loop feedback(%)
Bit1:Analog close loop setup(%)
Bit2: Actual length
Bit3: Reference length
Thousand’s place of LED:
Bit0: Terminal status(no unit)
Bit1: Bus voltage
Note: The reference frequency will be displayed in
default if all the Bits are 0
1 1FF
○
F8.04
Coefficient of displayed
speed
SPEED
FACTOR
0.1~999.9%
Spinning speed = actual spinning speed*F8.04(PG)
Spinning speed=
120*operating Frequency/FH.00*F8.04(non PG)
Reference speed =
close loop reference speed*F8.04(PG)
Reference speed=
120*reference frequency/FH.00*F8.04(non PG))
Note: No influence to actual speed
0.1% 100.0%
○
F8.05
Coefficient of displayed line
speed
LINE SPEED
FACTOR
0.1~999.9%
Line speed = running frequency*F8.05(non PG))
Line speed = spinning speed*F8.05(PG)
Reference line speed = reference frequency*F8.05(non
PG))
Reference line speed=reference speed*F8.05(PG)
Note: No influence to actual speed
0.1% 1.0%
○
F8.06
Coefficient of displayed
analog close loop
parameter/ feedback
CLOSELOOP
DISPLAY
FACTOR
0.1~999.9%
Note: Analog close loop reference/feedback displaying
range:0~999.9
0.1% 100.0%
○