3
8 Series
pressure deflagrations. Enardo utilizes a patented
(US Patent No. 5415233) element assembly that
dampens the high velocities and pressures associated
with deflagration and detonations while quenching the
flame front.
Designed with flanged connections, this arrestor allows
removal of the flame cell element for easy cleaning
and replacement without removing the arrestor
body from the pipe connection. Standard housing
construction is carbon steel or stainless steel. The
element is available in Stainless steel. Special material
and protective coating are available on request.
Principle of Operation
The high-pressure deflagration flame arrestor is
an enhanced version of the standard deflagration
flame arrestor, designed to stop flames in the low,
medium, and high pressure deflagration states. Flame
arrestor allows gas to pass though it but stops flame
in order to prevent a larger fire of explosion. Arrestor
prevents flame by absorbing and dissipating the heat
from flame as it attempts to travel through the spiral
wound crimped ribbon flame cells. These cells allow
maximum flow with maximum protection. See Figure 3.
Table 1.
8 Series High Pressure Deflagration Flame Arrestor Available Construction
Figure 3.
Flame Arrestor Operation
FLAME STABILIZED ON
ARRESTOR ELEMENT
PIPING
EXPOSED SIDE
FLAME ARRESTOR ELEMENT ABSORBS
AND QUENCHES FLAME FRONT
PROTECTED SIDE
MODEL
FLANGE SIZE
HOUSING SIZE
In.
mm
In.
mm
80802
2
50
8
200
80803
3
75
8
200
80804
4
100
8
200
81206
6
150
12
300
81608
8
200
16
400
82010
10
250
20
500
82412
12
300
24
600
82814
14
350
28
700
83016
16
400
30
750
83018
18
450
34
850
83620
20
500
36
900
84824
24
600
48
1200