OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX
42/54
19.4 Hot gas injection valve
Controller can manage a hot gas injection valve to increase suction superheat. See above figure.
Parameters
A
relay
must be set as hot gas valve:
oA2
or
oA3
or
oA4
or
oA5
or
oA6
= HGi, and
an
auxiliary probe
among P3 (term. 3 - 4) or P4 (term. 27 - 28) has to be set as superheat
temperature probe
ASH9 = P3 or P4
.
Then the following parameters:
ASH7 Superheat value to enable hot gas injecting valve (
0.1 - 15.0 °C/ 1 – 30 °F)
ASH8 Differential for ASH7 (
0.1 - 30.0 °C/ 1 – 60 °F)
Regulation:
The regulation respects the following schema:
Superheat < ASH7 - ASH8
HGi on
Superheat > ASH7
HGi off
ASH7 < Superheat < ASH7 - ASH8
The state is maintained.
Special conditions
a. With
ASH9 = nP
: none probe set as SH probe and one relays set as HGi (valve for hot gas
injection) the configuration error is displayed “
no Probe For SH
”, and the relay set as HGi is
never activated.
b. If the probe used to calculate the SH is in error the related probe fault alarm is generated (P3
or P4) and the HGi relay is not activated.
ALARM LIST
Usually alarm conditions are signaled by means of:
1. Activation of alarm output 0 – 12 V
2. Buzzer activation
3. Message on proper display
4. Log of alarm: code and duration.
The table at paragraph 20.3
20.1 Types of alarms and signaling managed
A12: Configuration alarm
The following configuration parameters are checked after each modification.:
OA2 - OA6
Outputs 2 - 6 configuration
P2P
Second probe presence
AOP
Probe for analog output
When these parameters are set in wrong way an alarm message is generated:
the label
A12
is shown on the upper display, while the lower display the following messages are
shown: