Probe 4 configuration
P4c
Probe 4 setting (22-23):
nP =
not used:
nt10 =
NTC 10 K 38 - 42
nt86 =
NTC 86 K 38 - 42
ntcH =
NTC 10 K extended range (150°C)
O4
Probe 4 calibration
the range depends on the dEU parameter:
dEU = °C: -12.0 - 12.0;
dEU = °F: -200 - 200;
Probe selection for fan
FPb Probe selection for condenser fan
nP =
not used:
P1 =
Probe 1
P2 =
Probe 2
P3 =
Probe 3
17.3 Other input configuration
iF01 Digital input 1 configuration (10 - 13)
nu = Not used:
the digital input is disabled.
oA1 =
Safety digital input for load 1, term. 15 - 17;
(Factory setting);
oA2 =
Safety digital input for load 2,
term. 16 - 17
oA3 =
Safety digital input for load 3,
term. 17 - 18
oA4 =
Safety digital input for load 4, term. 17 - 20
oA6 =
Safety digital input for load 6, term. 21 - 22
inF =
Safety digital input of inverter for fan, used when none relay is configured as inverter
for fans
LP1 =
Low pressure switch
LP2 =
low pressure switch, circuit2
HP =
High pressure switch
ES =
Energy saving;
oFF =
instrument shut down;
LL =
liquid level alarm
SIL =
to enable the silence function
EAL =
generic external alarm, it doesn’t affect the regulation
Co1 =
running proof function for load 1, term. 15 - 17
Co2 =
running proof function for load 2,
term. 16 - 17
Co3 =
running proof function for load 3,
term. 17 - 18
Co4 =
running proof function for load 4, term. 17 - 20
Co6 =
running proof function for load 6, term. 21 - 22
NOTE
: Also the following values
oA5, Co5,
are present. These values
must not
be used.
iF02 Digital input 2 configuration (10 - 14) –
For the values see iF01; Factory setting oA2.
iF03 Digital input 3 configuration (10 - 11) –
For the value see iF01; Factory setting oA3.
iF04 Digital input 4 configuration (10 - 12) –
For the value see iF01; Factory setting oA4.
iF05 Digital input 5 configuration (9 - 10) –
For the value see iF01; Factory setting LP1.
iF06 Digital input 6 configuration (25 - 26) –
For the value see iF01; Factory setting HP.
iF07 Digital input 7 configuration (27 - 28) –
For the value see iF01; Factory setting LL.
NOTE: Digital input 7 is enabled only when P4C = NP, otherwise it operates as
temprature probe
iP01 Digital input 1 polarity (10 - 13):
oP:
the digital input is activated by opening the contact.
CL:
the digital input is activated by closing the contact.