FIRST INSTALLATION
At first installation, it’s necessary the following:
1. Select the kind of gas. 2. Set the range of the pressure probes.
In the following paragraph a short cut for the above operations.
Chapters 11
will show in detail these operations.
7.1 How to set the kind of gas
The controller has memorized the relation between temperature and pressure for some gases.
The pre-set gas is: R448A. (FtyP = 448)
If another gas is used, act as in the following:
1. Enter the Programming mode by pressing the
Set
and
DOWN
key for 3 seconds.
2. Select the “
Pr2
” parameter. Then enter the password
3 2 1 0
.
3. Select the
FtyP, kind of gas,
parameter.
4. Press the “
SET
” key: the value of the parameter will start blinking.
5. Use “
UP
” or “
DOWN
” to change the gas among the following:
r22 =
R22
134 =
R134
404 =
R404A
407A
= R407A
407C =
R407C
407F=
R407F
410
= R410
507 =
R507
CO2
= CO
2
r32
= R32
290
= R290
448
= R448A
449
= R449A
450
= R450A
452
= R452
513
= R513
1234
= R1234ze
6. Press “
SET
” to store the new value and move to the following parameter.
EXIT:
Press
SET + UP
or wait 30s without pressing a key.
NOTE
: The set value is stored even when the procedure is excited by waiting the time-out to
expire.
7.2 How to set the range of the pressure probes
If an instrument with the following part number is used: EC2-XC645CX – xxxxF, it is pre-set to
work with pressure probe with the following range:
Probe 1: -0.5 -11.0 bar (relative pressure);
Probe 2: 0 - 30.0 bar (relative pressure)
If the probes you’re using have a different range act as in the following:
To set the pressure range of the
Probe 1 (suction probe)
use the parameter:
PA04:
Adjustment of read out corresponding to 4 mA (0.5 V)
PA20
:
Adjustment of read out corresponding to 20 mA (4.5 V)
To set the pressure range of the
Probe 2 (condenser probe)
use the parameter:
FA04:
Adjustment of read out corresponding to 4 mA (0.5 V)
FA20
:
Adjustment of read out corresponding to 20 mA (4.5 V)
Practically these parameters have to be set with the start and end scale of the probe range.
How to do:
1. Enter the Programming mode by pressing the
Set
and
DOWN
key for 3 seconds.
2. Select the “
Pr2
” parameter. Then enter the password 3 2 1 0.
3. Select the
PA04, adjustment of read out corresponding to 4 mA (0.5 V),
parameter.
4. Press the “
SET
” key: the value of the parameter will start blinking.
5. Set the lower value of the probe range.
6. Push the
SET
key to confirm the value. The
PA20: adjustment of read out corresponding
to 20 mA (4.5 V)
parameter will be displayed.
7. Set the higher value of the range.
8. Push the
SET
key to confirm the value. Next parameter will be displayed.
Do the same things for the Probe 2,
FA04, FA20
parameters
.