1592027600 XW90LT RTC GB r1.1 10.02.2012.doc
XW90LT
6/6
Label Name
Range
°C/°F
Level
oA3 Third relay configuration
ALr = alarm; dEF = do not select
it; Lig =Light; AUS =AUX;
onF=always on; Fan= do not
select it; db = neutral zone; cP2
= second compressor; dF2 = do
not select it; HES = night blind
Lig
Pr2
oA4 Fourth relay configuration
ALr = alarm; dEF = do not select
it; Lig =Light; AUS =AUX;
onF=always on; Fan= do not
select it; db = neutral zone; cP2
= second compressor; dF2 = do
not select it; HES = night blind
AUS
Pr2
oA5 Fifth relay configuration
ALr = alarm; dEF = do not select
it; Lig =Light; AUS =AUX;
onF=always on; Fan= do not
select it; db = neutral zone; cP2
= second compressor; dF2 = do
not select it; HES = night blind
ALr
Pr2
AoP Alarm relay polarity (oAx=ALr)
oP; cL
cL
Pr2
i1P Digital input polarity
oP=opening; CL=closing
cL
Pr1
i1F Digital input 1 configuration
EAL, bAL, PAL, dor; dEF; Htr,
AUS
dor
Pr1
did Digital input alarm delay
0 to 255 min
15
Pr1
i2P Digital input polarity
oP=opening; CL=closing
cL
Pr2
i2F Digital input configuration
EAL, bAL, PAL, dor; dEF; Htr,
AUS
EAL
Pr2
d2d Digital input alarm delay
0 to 255 min
5
Pr2
Nps Number of activation of pressure switch
0 to 15
15
Pr2
odc
Compress and fan status when open
door
no; Fan; CPr; F_C
F-c
Pr2
rrd Regulation restart with door open alarm
n(0); Y(1)
y
Pr2
HES Differential for Energy Saving
[-30 to 30°C]
[-54 to 54°F]
0
Pr2
Hur* Current hour
0 to 23
-
rtc
Min* Current minute
0 to 59
-
rtc
dAY* Current day
Sun to SAt
-
rtc
Hd1* First weekly holiday
Sun to SAt; nu
nu
rtc
Hd2* Second weekly holiday
Sun to SAt; nu
nu
rtc
ILE*
Energy Saving cycle start during
workdays
0.0 to 23h50min
0
rtc
dLE*
Energy Saving cycle length during
workdays
0.0 to 24h00min
0
rtc
ISE* Energy Saving cycle start on holidays
0.0 to 23h50min
0
rtc
dSE* Energy Saving cycle length on holidays
0.0 to 24h00min
0
rtc
Ld1* 1
st
workdays defrost start
0.0 to 23h50min; nu
6.0
rtc
Ld2* 2
nd
workdays defrost start
0.0 to 23h50min; nu
13.0
rtc
Ld3* 3
rd
workdays defrost start
0.0 to 23h50min; nu
21.0
rtc
Ld4* 4
th
workdays defrost start
0.0 to 23h50min; nu
0.0
rtc
Ld5* 5
th
workdays defrost start
0.0 to 23h50min; nu
0.0
rtc
Ld6* 6
th
workdays defrost start
0.0 to 23h50min; nu
0.0
rtc
Sd1* 1
st
holiday defrost start
0.0 to 23h50min; nu
6.0
rtc
Sd2* 2
nd
holiday defrost start
0.0 to 23h50min; nu
13.0
rtc
Sd3* 3
rd
holiday defrost start
0.0 to 23h50min; nu
21.0
rtc
Sd4* 4
th
holiday defrost start
0.0 to 23h50min; nu
0.0
rtc
Sd5* 5
th
holiday defrost start
0.0 to 23h50min; nu
0.0
rtc
Sd6* 6
th
holiday defrost start
0.0 to 23h50min; nu
0.0
rtc
LoC Keyboard lock timer
nu; 10 to 255 sec
60
Pr2
Adr Serial address
1 to 247
1
Pr2
PbC Kind of probe
PtC; ntC
ntc
Pr2
onF on/off key enabling
nu, oFF; ES
oFF
Pr2
dP1 Room probe display
Read Only
-
Pr2
dP2 Evaporator probe display
Read Only
-
Pr2
dP3 Third probe display
Read Only
-
Pr2
dP4 Fourth probe display
Read Only
-
Pr2
rSE Real set
actual set
-
Pr2
rEL Software release
Read Only
6.9
Pr2
Ptb Map code
Read Only
Pr2
* Only for model with real time clock
2
Only for XW90LT with X-REP output