1592027600 XW90LT RTC GB r1.1 10.02.2012.doc 

XW90LT 

2/6 

KEY COMBINATIONS: 

  

 

 

To lock & unlock the keyboard. 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE  FUNCTION 

 

ON 

Compressor enabled 

Flashing  Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

Flashing  Drip time in progress 

 

ON 

Fans enabled 

Flashing  Fans delay after defrost in progress. 

 

ON 

An alarm is occurring 

 

ON 

Continuous cycle is running 

 

ON 

Energy saving enabled 

 

ON 

Light on 

 

ON 

Auxiliary relay on 

°C/°F 

ON 

Measurement unit 

Flashing  Programming phase 

5.

 

AUTOMATIC KEYBOARD LOCK 

To  avoid  accidental  modifications  of  the  controller  settings, the XW90LT keyboard will be locked 
automatically if no key will be touched for 60 seconds. 
The XW90LT will show “LoC” flashing for 
few seconds when it’s locking. The light key is operating even if the keyboard is locked. 

5.1

 

TO UNLOCK THE KEYBOARD 

1.

 

Touch any key. 

2.

 

The keys will be lighted. 

3.

 

Keep a key pushed for few seconds till the “on” message is displayed. 

6.

 

MAX & MIN TEMPERATURE MEMORIZATION 

6.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the DOWN key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the DOWN key again or by waiting 5 sec the normal display will be restored. 

6.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the UP key. 

2. 

 

The “Hi” message will be displayed followed by the maximum recorded temperature. 

3. 

 

By pressing the UP key again or by waiting 5 sec the normal display will be restored. 

6.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Keep  SET  key  pressed  more  than  3  sec,  while  the max or min temperature is displayed. (rSt 
message will be displayed). 

2.

 

To  confirm  the  operation  the  “rSt”  message  starts  blinking and the normal temperature will be 
displayed. 

7.

 

MAIN FUNCTIONS 

7.1

 

TO SET THE CURRENT TIME AND DAY (ONLY WITH RTC) 

When the instrument is switched on, it’s necessary to program the time and day. 

1.

 

Enter the Pr1 programming menu, by pushing the SET+ DOWN

 

keys for 3 sec. 

2.

 

The rtC parameter is displayed. Push the SET key to enter the real time clock menu. 

3.

 

The Hur (hour) parameter is displayed. 

4.

 

Push  the  SET  and  set  current  hour  by  the  UP  and  DOWN  keys,  then  push  SET  to 
confirm the value. 

5.

 

Repeat the same operations with Min (minutes) and dAy (day) parameters. 

To exit: Push both SET+UP keys or wait for 15 sec without pushing any keys. 

7.2

 

HOW TO SEE THE SET POINT 

 

1.

 

Push and immediately release the SET key: the display will show the 
Set point value. 

2.

 

Push and immediately release the SET key or wait for 5 sec to display 
the probe value again. 

7.3

 

HOW TO CHANGE THE SETPOINT 

1.

 

Push the SET key more than 2 sec to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED will start blinking. 

3.

 

To change the Set value, push both UP and DOWN arrows within 10 sec. 

4.

 

To store the new set point value, push the SET key again or wait for 10 sec. 

7.4

 

HOW TO START A MANUAL DEFROST 

 

Push the DEF key more than 2 sec and to start a manual defrost. 

7.5

 

HOW TO CHANGE A PARAMETER VALUE 

To change any parameter, operate as follows:  
1.

 

Enter the Programming mode by pressing both SET+DOWN keys for 3 sec (the “°C” or “°F” LED 

will start blinking). 

2.

 

Select the required parameter and then press the SET key to display its value. 

3.

 

Use UP or DOWN keys to change its value. 

4.

 

Press SET to store the new value and move to the following parameter. 

To exit: press both SET+UP keys or wait for 15 sec without pressing any key. 
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

7.6

 

THE HIDDEN MENU 

The hidden menu shows all the parameters of the instrument. 

7.6.1  HOW TO ENTER THE HIDDEN MENU (Pr2) 

1.

 

Enter the Programming mode by pressing the SET+DOWN keys for 3 sec (the “°C” or “°F” LED 

will start blinking). 

2.

 

Released  the  keys  and  then push again the SET+DOWN keys more than 7 sec. The “Pr2” label 
will be displayed immediately followed by the HY parameter. 
NOW THE HIDDEN MENU IS DISPLAYED. 

3.

 

Select the required parameter. 

4.

 

Press the SET key to display its value 

5.

 

Use UP or DOWN keys to change its value. 

6.

 

Press SET to store the new value and move to the following parameter. 

To exit: press SET+UP keys or wait for 15 sec without pressing any key. 
NOTE1: if no parameters are present in Pr1, after 3 sec the “noP” message will be displayed. Keep 
the keys pushed till the Pr2 message is displayed.  
NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

7.6.2  MOVE A PARAMETER FROM Pr2 TO Pr1 AND VICEVERSA. 

Each parameter present in the Pr2 (HIDDEN MENU) can be moved to the Pr1 (user level) by pressing 
both SET+DOWN keys.  
When in Pr2 (hidden menu) if a parameter is visible in Pr1, then the decimal point will be on. 

7.7

 

MANUALLY LOCK AND UNLOCK THE KEYBOARD 

  

+

 

HOW TO LOCK THE KEYBOARD 

1.  

Keep both UP+DOWN keys pressed more than 3 sec. 

2.  

The “PoF” message will be displayed and the keyboard is locked. At 
this point it is only possible the viewing of the set point or the MAX o 
Min temperature stored and to switch ON and OFF the light, the 
auxiliary output and the instrument. 

 
HOW TO UNLOCK THE KEYBOARD 
Keep bothj UP+DOWN keys pressed more than 3 sec. 

7.8

 

THE CONTINUOUS CYCLE 

When  defrost  is  not  active,  a continuous cycle can be activated by keeping the UP key pressed for 
about 3 sec. The compressor operates to maintain the CCS set point for the time set through the CCt 
parameter.  The  cycle  can  be  terminated  before  the  end  of  the  set  time  by  keeping  the  UP  key 
pressed 3 sec. 

7.9

 

THE ON/OFF FUNCTION 

 

With onF=oFF, after pushing the ON/OFF key the instrument is switched off. The 
“OFF” message will be displayed. In this configuration the regulation is disabled.  
To switch the instrument on, push again the ON/OFF key. 

 
WARNING:  Loads  connected  to  the  normally  closed  contacts  of  the  relays  are  always 
supplied and under voltage, even if the instrument is in stand by mode.  

8.

 

PARAMETERS 

rtC 

Real  time  clock  menu  (only  for  controller  with  RTC):  to  set  the  time,  date  and 
defrost start time. 

REGULATION 

HY 

Differential:  (0.1  to  25.5°C;  1  to  45°F)  intervention  differential  for  set  point. 
Compressor Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the 
temperature reaches the set point. 

LS 

Minimum set point: (-55°C to SET; -67°F to SET) sets the minimum value for the set 
point. 

US 

Maximum  set  point:  (SET  to  150°C;  SET  to  302°F)  set  the  maximum  value for set 
point. 

ot 

Thermostat probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 
offset of the thermostat probe. 

P2P 

Evaporator probe presence: (n; Y) n = not present, the defrost stops by time;  
Y = present, the defrost stops by temperature. 

oE 

Evaporator probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 
offset of the evaporator probe. 

P3P 

Third  probe  presence  (P3):  (n;  Y)  n  =  not  present,  the  terminals  18-20  operate  as 
digital input; Y = present, the terminals 18-20 operate as third probe. 

o3 

Third probe calibration (P3): (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 
offset of the third probe. 

P4P 

Fourth probe presence: (n; Y) n = Not present; Y = present. 

o4 

Fourth  probe  calibration:  (-12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust  possible 
offset of the fourth probe. 

odS 

Outputs  activation  delay  at  start  up: (0  to  255min)  this  function  is  enabled  at  the 
initial start up of the instrument and inhibits any output activation for the period of time 
set in the parameter.  

AC 

Anti-short  cycle  delay:  (0  to  50min)  minimum  interval between the compressor stop 
and the following restart. 

rtr 

Percentage of the second and first probe for regulation: (0 to 100; 100=P1, 0=P2) 
it allows to set the regulation according to the percentage of the first and second probe, 
as for the following formula (rtr(P1-P2)/100 + P2). 

CCt 

Compressor ON time during continuous cycle: (0.0 to 24h00min, res. 10min) allows 
to  set  the  length  of  the  continuous  cycle.  Compressor  stays  on  without  interruption 
during CCt time. This is useful, for instance, when the room is filled with new products. 

CCS 

Set  point  for  continuous  cycle:  (-55  to  150°C;  -67  to  302°F)  it  sets  the  set  point 
used during the continuous cycle. 

Con 

Compressor  ON  time  with  faulty  probe:  (0  to  255min)  time  during  which  the 
compressor  is  active  in  case  of  faulty  thermostat  probe.  With  Con=0  compressor  is 
always OFF. 

Summary of Contents for dixell XW90LT

Page 1: ...me clock system depending on the hours set in the parameters Ld1 Ld6 during workdays and in Sd1 Sd6 during holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTRO...

Page 2: ...elect the required parameter 4 Press the SET key to display its value 5 Use UP or DOWN keys to change its value 6 Press SET to store the new value and move to the following parameter To exit press SET UP keys or wait for 15 sec without pressing any key NOTE1 if no parameters are present in Pr1 after 3 sec the noP message will be displayed Keep the keys pushed till the Pr2 message is displayed NOTE...

Page 3: ... off during defrost ALARMS ALP Probe selection for alarm nP P1 P2 P3 P4 nP no probe the temperature alarms are disabled P1 Probe 1 Thermostat probe P2 Probe 2 evaporator probe P3 Probe 3 display probe P4 Fourth probe ALC Temperature alarms configuration Ab rE Ab absolute temperature alarm temperature is given by the ALL or ALU values rE temperature alarms are referred to the set point Temperature ...

Page 4: ... defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 9 6 SWITCH THE AUXILIARY RELAY i1F or i2F AUS With oAx AUS the digital input will change the status of the auxiliary relay 9 7 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F or ...

Page 5: ... Hy Differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr1 LS Minimum set point 55 C to SET 67 F to SET 50 0 Pr2 US Maximum set point SET to 150 C SET to 302 F 110 Pr2 ot Thermostat probe calibration 12 to 12 C 21 to 21 F 0 0 Pr1 P2P Evaporator probe presence n not present Y present Y Pr1 oE Evaporator probe calibration 12 to 12 C 21 to 21 F 0 0 Pr2 P3P Third probe presence n not present Y present n Pr2 o3 ...

Page 6: ...59 rtc dAY Current day Sun to SAt rtc Hd1 First weekly holiday Sun to SAt nu nu rtc Hd2 Second weekly holiday Sun to SAt nu nu rtc ILE Energy Saving cycle start during workdays 0 0 to 23h50min 0 rtc dLE Energy Saving cycle length during workdays 0 0 to 24h00min 0 rtc ISE Energy Saving cycle start on holidays 0 0 to 23h50min 0 rtc dSE Energy Saving cycle length on holidays 0 0 to 24h00min 0 rtc Ld1...

Reviews: