background image

 

 

1592027600 XW90LT RTC GB r1.1 10.02.2012.doc 

XW90LT 

4/6 

rrd 

Outputs restart after door open alarm: (n; Y) n = outputs follow the odC parameter.  
Y = outputs restart with a door open alarm.  

HES 

Delta temperature during an Energy Saving cycle: (-30.0 to 30.0°C; -54 to 54°F) it 
sets the increasing value of the set point [SET+HES] during the Energy Saving cycle. 

CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC) 

Hur 

Current hour: 0 to 23h. 

Min 

Current minute: 0 to 59min. 

dAY 

Current day: Sun to SAt. 

Hd1 

First weekly holiday: (Sun to nu) set the first day of the week which follows the holiday 
times. 

Hd2 

Second weekly holiday: (Sun to nu) set the second day of the week which follows the 
holiday times. 

 
N.B.: Hd1, Hd2 
can be set also as “nu” value (Not Used).  

ENERGY SAVING TIMES (only for models with rtc) 

ILE 

Energy  Saving  cycle  start  during  workdays:  (0  to  23h50min)  during  the  Energy 
Saving  cycle  the  set  point  is  increased  by  the  value  in  HES  so  that  the  operation  set 
point is SET+HES. 

dLE 

Energy Saving cycle length during workdays: (0 to 24h00min) sets the duration of 
the Energy Saving cycle on workdays. 

ISE 

Energy Saving cycle start on holidays: 0 to 23h50min. 

dSE 

Energy Saving cycle length on holidays: 0 to 24h00min. 

TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC) 

Ld1÷Ld6 

Workday defrost start: (0 to 23h50min) these parameters set the beginning of the 6 
programmable  defrost  cycles  during  workdays.  Ex:  when  Ld2=12.4  the  second 
defrost starts at 12.40 during workdays. 

Sd1÷Sd6 

Holiday defrost start: (0 to 23h50min) these parameters set the beginning of the 6 
programmable  defrost  cycles  on  holidays.  Ex:  when  Sd2=3.4  the  second  defrost 
starts at 3.40 on holidays. 

 
N.B.: to disable a defrost cycle set it to “nu” (not used). 

OTHER 

LoC

 

Lock keyboard timer: nu(9) = keyboard never blocked, or 10 to 255 sec

 

Adr 

Serial  address:  (1  to  247)  identifies  the  instrument  address  when  connected  to  a 
ModBUS compatible monitoring system. 

PbC 

Type of probe: (PtC; ntC) it allows to set the kind of probe used by the instrument:  
PtC = PTC probe, ntC = NTC probe. 

onF 

On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it. 

dP1 

Thermostat probe display. 

dP2 

Evaporator probe display. 

dP3 

Third probe display. 

dP4 

Fourth probe display. 

rSE 

Real set point: it shows the set point used during the energy saving cycle or during the 
continuous cycle. 

rEL 

Software release for internal use. 

Ptb 

Parameter table code: readable only. 

9.

 

DIGITAL INPUTS  

The first digital input (terminals 13-14) is enabled if P3P=n
With P3P=n and i1F=i2F the second digital input will be disabled. 
The free voltage digital inputs are programmable by the i1F and i2F parameters. 

9.1

 

GENERIC ALARM (i1F or i2F = EAL) 

As soon as the digital input is activated the unit will wait for did time delay before signalling the “EAL” 
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-
activated. 

9.2

 

SERIOUS ALARM MODE (i1F or i2F = bAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  did  delay  before  signalling  the  “CA”  alarm 
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

9.3

 

PRESSURE SWITCH (i1F or i2F = PAL) 

If  during  the  interval  time  set  by  did  parameter,  the  pressure  switch  has  reached  the  number  of 
activation of the nPS parameter; the “CA” pressure alarm message will be displayed. The compressor 
and  the  regulation  are  stopped.  When the digital input is ON the compressor is always OFF. If the 
nPS activation in the did time is reached, switch off and on the instrument to restart normal 
regulation. 

9.4

 

DOOR SWITCH INPUT (i1F or i2F = dor) 

It signals the door status and the corresponding relay output status through the odC parameter: no: 
normal (any change); FAn: Fan OFF; CPr: Compressor OFF; F_C: Compressor and fan OFF. 
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, 
the  display  shows  the  message  “dA”  and  the  regulation  restarts  if  rtr=YES.  The  alarm  stops  as 
soon as the external digital input is disabled again. With the door open, the high and low temperature 
alarms are disabled. 

9.5

 

START DEFROST (i1F or i2F = dEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation 
will  restart  only  if  the  digital  input  is  disabled  otherwise  the  instrument will wait until the MdF safety 
time is expired. 

9.6

 

SWITCH THE AUXILIARY RELAY (i1F or i2F = AUS) 

With oAx=AUS the digital input will change the status of the auxiliary relay. 

9.7

 

INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F or i2F=Htr)  

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

9.8

 

ENERGY SAVING (i1F or i2F = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+HES 
(parameter) sum. This function is enabled until the digital input is activated. 

9.9

 

HOLIDAY DEFROST (i1F or i2F = HDF)  (ONLY FOR MODELS WITH RTC) 

This function enabled the holiday defrost setting. 

9.10

 

ON OFF FUNCTION (i1F or i2F = onF) 

To switch the controller on and off. 

9.11

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the i1P and i2P parameters. 

-

 

i1P or i2P =CL: the input is activated by closing the contact. 

-

 

i1P or i2P=OP: the input is activated by opening the contact. 

10.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The  TTL  serial  line,  available  through  the  HOT  KEY  connector,  allows  by  means  of  the  external 
TTL/RS485  converter,  XJ485-CX,  to  connect  the  instrument to a monitoring system ModBUS-RTU 
compatible such as the X-WEB500/3000/300. 

11.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the dedicated connector.  

 

To connect the X-REP to the 
instrument the following 
connectors must be used 
CAB/REP1(1m), CAB/REP2 
(2m), CAB/REP5 (5m), 

12.

 

INSTALLATION AND MOUNTING 

The  XW90LT  shall  be  mounted  on vertical panel, in a 150x31 mm hole, and fixed using the special 
brackets  supplied  with  the  controllers.  The  temperature  range  allowed  for  correct  operation  is  0  to 
60°C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases,  excessive  dirt  or  humidity.  The 
same recommendations apply to probes. Let the air circulate by the cooling holes. 

12.1

 

CUT OUT 

 

13.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 
2.5  mm

for  the  digital  and  analogue  inputs.  Relays  and  power  supply  have  a  Faston  connection 

(6.3mm).  Heat-resistant  cables  have  to  be  used.  Before  connecting  cables  make  sure  the  power 
supply complies with the instrument’s requirements. Separate the probe cables from the power supply 
cables, from the outputs and the power connections. Do not exceed the maximum current allowed on 
each relay, in case of heavier loads use a suitable external relay. 
 
N.B. Maximum current allowed for all the loads is 20A. 

13.1

 

PROBE CONNECTION 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room  temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

14.

 

HOW TO USE THE HOT KEY  

14.1

 

PROGRAM A HOT KEY FROM AN INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON,  insert  the  “HOT-KEY”  and  push  UP  button;  the  “uPL  message 
appears followed a by a flashing “End” label. 

3.

 

Push SET button and the “End” will stop flashing. 

4.

 

Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again. 

 
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again 
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation. 

14.2

 

PROGRAM AN INSTRUMENT BY USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a pre-programmed HOT-KEY into the 5-PIN receptacle and then turn the Controller 
ON. 

3.

 

The  parameter  list  of  the  “HOT-KEY”  will  be  automatically  downloaded  into  the  Controller 
memory. The “doL” message will blink followed a by a flashing “End” label. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “HOT-KEY”. 
 

NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then 
on if you want to restart the download again or remove the “HOT-KEY” to abort the operation. 

Summary of Contents for dixell XW90LT

Page 1: ...me clock system depending on the hours set in the parameters Ld1 Ld6 during workdays and in Sd1 Sd6 during holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTRO...

Page 2: ...elect the required parameter 4 Press the SET key to display its value 5 Use UP or DOWN keys to change its value 6 Press SET to store the new value and move to the following parameter To exit press SET UP keys or wait for 15 sec without pressing any key NOTE1 if no parameters are present in Pr1 after 3 sec the noP message will be displayed Keep the keys pushed till the Pr2 message is displayed NOTE...

Page 3: ... off during defrost ALARMS ALP Probe selection for alarm nP P1 P2 P3 P4 nP no probe the temperature alarms are disabled P1 Probe 1 Thermostat probe P2 Probe 2 evaporator probe P3 Probe 3 display probe P4 Fourth probe ALC Temperature alarms configuration Ab rE Ab absolute temperature alarm temperature is given by the ALL or ALU values rE temperature alarms are referred to the set point Temperature ...

Page 4: ... defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 9 6 SWITCH THE AUXILIARY RELAY i1F or i2F AUS With oAx AUS the digital input will change the status of the auxiliary relay 9 7 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F or ...

Page 5: ... Hy Differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr1 LS Minimum set point 55 C to SET 67 F to SET 50 0 Pr2 US Maximum set point SET to 150 C SET to 302 F 110 Pr2 ot Thermostat probe calibration 12 to 12 C 21 to 21 F 0 0 Pr1 P2P Evaporator probe presence n not present Y present Y Pr1 oE Evaporator probe calibration 12 to 12 C 21 to 21 F 0 0 Pr2 P3P Third probe presence n not present Y present n Pr2 o3 ...

Page 6: ...59 rtc dAY Current day Sun to SAt rtc Hd1 First weekly holiday Sun to SAt nu nu rtc Hd2 Second weekly holiday Sun to SAt nu nu rtc ILE Energy Saving cycle start during workdays 0 0 to 23h50min 0 rtc dLE Energy Saving cycle length during workdays 0 0 to 24h00min 0 rtc ISE Energy Saving cycle start on holidays 0 0 to 23h50min 0 rtc dSE Energy Saving cycle length on holidays 0 0 to 24h00min 0 rtc Ld1...