background image

 

 

1592027600 XW90LT RTC GB r1.1 10.02.2012.doc 

XW90LT 

3/6 

CoF 

Compressor  OFF  time  with  faulty  probe:  (0  to  255min)  time  during  which  the 
compressor  is  OFF  in  case  of  faulty  thermostat  probe.  With  CoF=0  compressor  is 
always active. 

DISPLAY 

CF 

Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.  
WARNING: When the measurement unit is changed the SET point and the values of 
the parameters HYLSUSotALU and ALL have to be checked and modified (if 
necessary). 

rES 

Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display. 

Lod 

Instrument display: (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by 
the  instrument.  P1  =  Thermostat  probe;  P2  =  Evaporator  probe;  P3  =  Third  probe 
(only  for model with this option enabled); P4 = Fourth probe, SET = set point; dtr = 
percentage of visualization. 

rEd 

X-REP  display  (optional):  (P1;  P2,  P3,  P4,  SET,  dtr)  it  selects  which  probe  is 
displayed  by  X-  REP.  P1  =  Thermostat  probe;  P2  =  Evaporator  probe;  P3  =  Third 
probe (only for model with this option enabled); P4 = Fourth probe, SET = set point;  
dtr = percentage of visualization. 

dLY 

Display  delay:  (0  to  20min00s;  res.  10s)  when  the  temperature  increases,  the 
display is updated of 1°C or 1°F after this time. 

dtr 

Percentage of the second and first probe for visualization when Lod=dtr: (0 to 
99;  100=P1,  0=P2)  if  Lod=dtr  it  allows  to  set  the  visualization  according  to  the 
percentage of the first and second probe, as for the following formula (dtr(P1-P2)/100 
+ P2). 

DEFROST 

EdF 

Defrost mode (only for controller with RTC): 

-

 

rtC:  Real  Time  Clock  mode.  Defrost  time  follows  Ld1÷Ld6  parameters  on 
workdays and Sd1÷Sd6 on holidays. 

-

 

in: interval mode. The defrost starts when the time idf is expired. 

tdF 

Defrost type: (EL; in) EL = electrical heater; in = hot gas. 

dFP 

Probe selection for defrost termination: (nP; P1; P2; P3; P4) nP = no probe;  
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug. 

dtE 

Defrost  termination  temperature:  (-55  to  50°C;  -67  to  122°F)  (enabled only when 
EdF=Pb) sets the temperature measured by the evaporator probe, which causes the 
end of defrost. 

idF 

Interval  between  defrost  cycles:  (0  to  120hours)  determines  the  interval  of  time 
between two defrost cycles. 

MdF 

(Maximum)  length  for  defrost:  (0  to 255min) when P2P=n, (not evaporator probe: 
timed  defrost)  it  sets  the  defrost  duration.  When  P2P=Y  (defrost  end  based  on 
temperature) it sets the maximum length for defrost. 

dSd 

Start defrost delay: (0 to 99min) this is useful when different defrost start times are 
necessary to avoid overloading the plant.  

dFd 

Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;  
it = temperature at defrost start; SEt = set point; dEF = “dEF” label. 

dAd 

MAX display delay after defrost: (0 to 255min) sets the maximum time between the 
end of defrost and the restarting of the real room temperature display. 

Fdt 

Drip  time:  (0  to  120min)  time  interval  between  reaching  defrost  termination 
temperature  and  the  restoring of the control’s normal operation. This time allows the 
evaporator to eliminate water drops that might have formed due to defrost. 

dPo 

First defrost after start-up: (n; Y) n = after the idF time, Y = immediately. 

dAF 

Defrost  delay  after  continuous  cycle:  (0.0  to  24h00min,  res.  10min)  time  interval 
between the end of the fast freezing cycle and the following defrost related to it. 

FANS 

FnC 

Fans  operating  mode:  (C-n;  o-n;  C-Y;  o-Y)  C-n  =  runs  with  the  compressor,  OFF 
during  defrost;  o-n  =  continuous  mode,  OFF  during  defrost;  C-Y  =  runs  with  the 
compressor, ON during defrost; o-Y = continuous mode, ON during defrost. 

Fnd 

Fans delay after defrost: (0 to 255min) interval between end of defrost and evaporator 
fans start. 

FCt 

Temperature  differential  to  avoid  fan  short  cycles:  (0  to  59°C;  0  to  90°F)  (N.B.: 
FCt=0 means function disabled) if the difference of temperature between the evaporator 
and the room probes is higher than FCt value, the fans will be switched on. 

FSt 

Fans stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature, detected 
by evaporator probe, above which fans are always OFF. 

Fon 

Fan  ON  time:  (0  to  15min)  with  Fnc=C_n  or  C_Y,  (fan  activated  in  parallel  with 
compressor) it sets the evaporator fan ON cycling time when the compressor is off. With 
Fon=0  and  FoF≠0  the  fan  are  always  off,  with Fon=0 and FoF=0 the fan are always 
off. 

FoF 

Fan OFF time: (0 to 15min)  
With FnC=C_n or C_Y, (fan activated in parallel with compressor) it sets the evaporator 
fan off cycling time when the compressor is off.  
With  Fon=0  and  FoF≠0  the  fan  are  always  off,  with  Fon=0  and  FoF=0  the  fan  are 
always off. 

FAP 

Probe selection for fan management: (nP; P1; P2; P3; P4) nP = no probe;  
P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on 
Hot Key plug. 

AUXILIARY THERMOSTAT CONFIGURATION  – OAx = AUS 

ACH 

Kind of regulation for auxiliary relay: (Ht; CL) Ht = heating; CL = cooling. 

SAA 

Set  Point  for  auxiliary  relay:  (-55.0  to  150.0°C;  -67  to  302°F)  it  defines  the  room 
temperature set point to switch auxiliary relay. 

SHY 

Differential for auxiliary output: (0.1 to 25.5°C; 1 to 45°F) intervention differential for 
auxiliary output set point. 

 

ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut out is SAA

 

ACH=Ht, AUX Cut in is [SAA–SHY]; AUX Cut out is SAA

ArP 

Probe selection for auxiliary: (nP; P1; P2; P3; P4) nP = no probe, the auxiliary relay 
is  switched  only  by  the  digital  input;  P1  =  Probe  1  (Thermostat  probe);  P2  =  Probe 2 
(evaporator probe); P3 = Probe 3 (display probe); P4 = Probe 4. 

Sdd 

Auxiliary  relay  off  during  defrost:  (n;  Y)  n  =  the  auxiliary  relay  operates  during 
defrost. Y = the auxiliary relay is switched off during defrost. 

ALARMS 

ALP 

Probe  selection  for  alarm:  (nP;  P1;  P2;  P3;  P4)  nP  =  no  probe,  the  temperature 
alarms  are  disabled;  P1  =  Probe  1  (Thermostat  probe);  P2  =  Probe  2  (evaporator 
probe);  
P3 = Probe 3 (display probe); P4 = Fourth probe. 

ALC 

Temperature  alarms  configuration:  (Ab;  rE)  Ab  =  absolute  temperature,  alarm 
temperature is given by the ALL or ALU values.  rE = temperature alarms are referred 
to  the  set  point.  Temperature  alarm  is  enabled  when  the  temperature  exceeds  the 
[SET+ALU] or [SET-ALL] values. 

ALU 

MAXIMUM temperature alarm:  

 

If ALC=Ab: [ALL to 150.0°C or ALL to 302°F] 

 

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the ALd delay time. 

ALL 

Minimum temperature alarm:  

 

If ALC=Ab: [-55°C to ALU; -67 to ALU] 

 

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the ALd delay time. 

AFH 

Differential  for  temperature  alarm  recovery:  (0.1  to  25.5°C;  1  to 45°F) intervention 
differential for recovery of temperature alarm. 

ALd 

Temperature  alarm  delay:  (0  to  255  min)  time  interval  between  the  detection  of  an 
alarm condition and alarm signalling. 

dAo 

Exclusion  of  temperature  alarm  at  start-up:  (0.0  to  24h00min,  res.  10min)  time 
interval between the detection of the temperature alarm condition after instrument power 
on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 

AP2 

Probe selection for temperature alarm of condenser: (nP; P1; P2; P3; P4)  
nP = no probe; P1 = thermostat probe; P2 = evaporator probe; P3 = configurable probe; 
P4 = Probe on Hot Key plug. 

AL2 

Low  temperature  alarm  of  condenser:  (-55  to  150°C;  -67  to  302°F)  when  this 
temperature is reached the LA2 alarm is signalled, possibly after the Ad2 delay. 

Au2 

High  temperature  alarm  of  condenser:  (-55  to  150°C;  -67  to  302°F)  when  this 
temperature is reached the HA2 alarm is signalled, possibly after the Ad2 delay. 

AH2 

Differential for temperature condenser alarm recovery: 0.1 to 25.5°C; 1 to 45°F 

Ad2 

Condenser  temperature  alarm  delay:  (0  to  255  min)  time  interval  between  the 
detection of the condenser alarm condition and alarm signalling. 

dA2 

Condenser temperature alarm exclusion at start up: 0.0 to 24h00min, res. 10min. 

bLL 

Compressor  off  with  low temperature alarm of condenser: (n; Y) n = compressor 
keeps on working; Y = compressor is switched off till the alarm is present, in any case 
regulation restarts after AC time at minimum. 

AC2 

Compressor off with high temperature alarm of condenser: (n; Y) n = compressor 
keeps on working; Y = compressor is switched off till the alarm is present, in any case 
regulation restarts after AC time at minimum. 

AUXILIARY RELAYS 

tbA 

Alarm relay silencing (with oAx =ALr): (n; Y) n = silencing disabled: alarm relay stays 
on  till  alarm  condition  lasts.  Y  =  silencing  enabled:  alarm  relay  is  switched  OFF  by 
pressing a key during an alarm. 

oA3 

Third relay configuration (1-3): (dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES) dEF 
= defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; onF = 
always on with instrument on; db = neutral zone; dEF2 = do not select it; HES = night 
blind. 

oA4 

Fourth relay configuration (22-23): (dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES) 
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; 
onF = always on with instrument on; db = neutral zone; dEF2 = do not select it; HES = 
night blind. 

oA5 

Fifth  relay  configuration  (20-21):  (dEF;  FAn;  ALr;  LiG;  AUS;  onF;  db;  dEF2;  HES) 
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; 
onF = always on with instrument on; db = neutral zone; dEF2 = do not select it; HES = 
night blind. 

AoP 

Alarm relay polarity: (CL; oP) it set if the alarm relay is open or closed when an alarm 
occurs. CL = terminals closed during an alarm; oP = terminals open during an alarm. 

DIGITAL INPUTS 

i1P 

First digital input polarity: (oP; CL) oP = the digital input is activated by opening the 
contact; CL = the digital input is activated by closing the contact. 

i1F 

First  digital  input  configuration:  (EAL;  bAL;  PAL;  dor;  dEF;  ES;  AUS;  Htr;  FAn; 
HdF; onF; Sbt) EAL = external alarm: “EA” message is displayed; bAL = serious alarm 
CA” message is displayed; PAL = pressure switch alarm, “CA” message is displayed; 
dor  =  door  switch  function;  dEF  =  activation  of  a  defrost  cycle;  ES  =  energy  saving; 
AUS = auxiliary relay activation with oA2=AUSHtr = type of inverting action (cooling or 
heating); FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the 
controller off; Sbt = to activate Sabbath mode. 

i2P 

Second digital input polarity: (oP; CL) oP = the digital input is activated by opening 
the contact; CL = the digital input is activated by closing the contact. 

i2F 

Second digital input configuration: (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn; 
HdF; onF; Sbt) EAL = external alarm: “EA” message is displayed; bAL = serious alarm 
CA” message is displayed; PAL = pressure switch alarm, “CA” message is displayed; 
dor  =  door  switch  function;  dEF  =  activation  of  a  defrost  cycle;  ES  =  energy  saving; 
AUS = auxiliary relay activation with oA2=AUSHtr = type of inverting action (cooling or 
heating); FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the 
controller off; Sbt = to activate Sabbath mode. 

did 

Digital input 1 alarm delay:  (0 to 255 min) delay between the detection of the external 
alarm condition and its signalling. 
When  i1F=  PAL,  it  is  the  interval  of  time  to  calculate  the  number  of  pressure  switch 
activation. 

doA 

Door open alarm delay: 0 to 255 min. 

nPS 

Number of pressure switch activation: (0 to 15) Number of activation, during the did 
or d2d interval, before signalling an alarm event (i1F, i2F=PAL).  
If  the  nPS  activation  during  did  or  d2d  time  is  reached,  switch  off  and  on  the 
instrument to restart normal regulation. 

odC 

Compressor status when open door: (no; FAn; CPr;F_C;)  no = normal;  
FAn = normal; CPr = compressor OFF, F_C = compressor OFF. 

Summary of Contents for dixell XW90LT

Page 1: ...me clock system depending on the hours set in the parameters Ld1 Ld6 during workdays and in Sd1 Sd6 during holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTRO...

Page 2: ...elect the required parameter 4 Press the SET key to display its value 5 Use UP or DOWN keys to change its value 6 Press SET to store the new value and move to the following parameter To exit press SET UP keys or wait for 15 sec without pressing any key NOTE1 if no parameters are present in Pr1 after 3 sec the noP message will be displayed Keep the keys pushed till the Pr2 message is displayed NOTE...

Page 3: ... off during defrost ALARMS ALP Probe selection for alarm nP P1 P2 P3 P4 nP no probe the temperature alarms are disabled P1 Probe 1 Thermostat probe P2 Probe 2 evaporator probe P3 Probe 3 display probe P4 Fourth probe ALC Temperature alarms configuration Ab rE Ab absolute temperature alarm temperature is given by the ALL or ALU values rE temperature alarms are referred to the set point Temperature ...

Page 4: ... defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 9 6 SWITCH THE AUXILIARY RELAY i1F or i2F AUS With oAx AUS the digital input will change the status of the auxiliary relay 9 7 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F or ...

Page 5: ... Hy Differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr1 LS Minimum set point 55 C to SET 67 F to SET 50 0 Pr2 US Maximum set point SET to 150 C SET to 302 F 110 Pr2 ot Thermostat probe calibration 12 to 12 C 21 to 21 F 0 0 Pr1 P2P Evaporator probe presence n not present Y present Y Pr1 oE Evaporator probe calibration 12 to 12 C 21 to 21 F 0 0 Pr2 P3P Third probe presence n not present Y present n Pr2 o3 ...

Page 6: ...59 rtc dAY Current day Sun to SAt rtc Hd1 First weekly holiday Sun to SAt nu nu rtc Hd2 Second weekly holiday Sun to SAt nu nu rtc ILE Energy Saving cycle start during workdays 0 0 to 23h50min 0 rtc dLE Energy Saving cycle length during workdays 0 0 to 24h00min 0 rtc ISE Energy Saving cycle start on holidays 0 0 to 23h50min 0 rtc dSE Energy Saving cycle length on holidays 0 0 to 24h00min 0 rtc Ld1...

Reviews: