1592040000 XR70T EN v1.1 2019.07.09
XR70T
32/40
12.6 AUXILIARY OUTPUT (oAx = AUS)
The auxiliary output can be managed by digital inputs (
oAx=AUS
,
i1F
or i2F=AUS
): the output is switched
on and off following the relative digital input status.
12.6.1 AUXILIARY REGULATOR
The auxiliary regulator can be used to manage the auxiliary output. Here are the involved parameters:
•
ACH:
type of regulation for the auxiliary relay:
Ht
= heating;
CL
=
cooling
•
SAA:
set point for auxiliary relay
•
SHY:
auxiliary relay differential
•
ArP:
probe for auxiliary relay
•
Sdd:
auxiliary output off during defrost
12.6.2 TIMED ACTIVATION
The following parameters can be used to define fixed activation and deactivation intervals.
•
btA:
base time for auxiliary output activation and deactivation intervals
•
Ato:
auxiliary activation interval
•
AtF:
auxiliary deactivation interval
12.6.3 GENERAL NOTES
if
oAx=AUS
and
ArP=nP
(no probe for auxiliary digital output) the AUX output can be managed:
•
by digital input if
i1F=AUS
or
i2F=AUS
•
by auxiliary button (if set as
AUS
)
•
by serial command (Modbus protocol)
•
by fixed interval of time if
Ato>0
and
AtF>0
(if
Ato=0
or
AtF=0
the auxiliary output is disabled)
12.7 DEAD BAND REGULATION (oAx = db)
With
oAx=db
the output can be used to control, for example, a heater element. It is used to implement a
dead band regulation. If so:
•
oAx=db
cut in is
SET-HY
•
oA1=db
cut out is
SET
12.8 ON/OFF OUTPUT (oAx = onF)
When
oAx=onF
, the output is activated when the controller is switched on and deactivated when the
controller is switched off.
12.9 ENERGY SAVING OUTPUT (oAx = HES)
When
oAx=HES
, the output is activated when the energy saving mode is active and vice-versa.
12.10 CONDENSER FAN OUTPUT (oAx = Cnd)
With
oAx=Cnd
the relay operates as a condenser fan output.
12.11 SECOND COMPRESSOR OUTPUT (oAx = CP2)
With
oAx=CP2
the relay operates as a second regulation output. This function is available only for special
models and normally must be not selected.
12.12 SECOND DEFROST OUTPUT (oAx = dF2)
With
oAx=dF2
the relay operates as second defrost output. This function is available only for special models
and normally must be not selected.
12.13 HEATER OUTPUT (oAx = HEt)
With
oAx=HEt
the relay operates as a heater output. In this case, it will be used during and after any defrost
cycle. The par.
Hon
defines the time the relative output will stay active after the end of a defrost operation.
12.14 INVERTER OUTPUT (oAx = inV)
Function not available for this model.