1592040000 XR70T EN v1.1 2019.07.09
XR70T
24/40
CoM
bAU
Baudrate
9.6
Pr2
9.6(0); 19.2(1);
38.4(2); 57.6(3);
CoM
PAr
Parity control
no
Pr2
no(0); odd(1); EvE(2)
Ui
SCS
User interface timeout
60
Pr2
sec
1 to 255 sec
Ui
bS
Sound Level
3
Pr2
0 to 5
Ui
PSU
Password for protected level Pr2
Pr2
0 to 999
inF
dP1
Probe P1 value visualization
Pr1
read only
inF
dP2
Probe P2 value visualization
Pr1
read only
inF
dP3
Probe P3 value visualization
Pr1
read only
inF
dP4
Probe P4 value visualization
Pr1
read only
inF
rSE
Real regulation Set Point (SET + ES +
SETd)
Pr1
read only
inF
FdY
Firmware release date: day
Pr1
read only
inF
FMn
Firmware release date: month
Pr1
read only
inF
FYr
Firmware release date: year
Pr1
read only
inF
rEL
Firmware release
Pr1
read only
inF
SUb
Firmware sub release
Pr1
read only
inF
Ptb
Parameter map version
Pr1
read only
5.3
PARAMETER CONFIGURATION 2
Grou
p
Paramete
r
Description
Value
Protec
ted
U.O.
M.
Range
rEG
SEt
Set Point
38.0
Pr1
°F
LS to US
rEG
LS
Minimum Set point
-148.0
Pr1
°F
[-100.0°C to SET]
[-148.0°F to SET]
rEG
US
Maximum Set point
302.0
Pr1
°F
[SET to 150.0°C]
[SET to 302.0°F]
rEG
HY
Compressor regulation differential in
normal mode
6.0
Pr1
°F
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
HYE
Compressor regulation differential in
energy saving mode
6.0
Pr1
°F
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
odS
Output activation delay at start-up
0
Pr1
min
0 to 255 min
rEG
AC
Anti-short cycle delay
0
Pr1
min
0 to 50 min
rEG
rtr
Regulation percentage=F(P1; P2)
(100=P1; 0=P2)
100
Pr2
0 to 100
rEG
CCt
Maximum duration for Pull Down
00:00
Pr2
hh:m
m
0 to 23h50min
rEG
CCS
Pull Down phase differential (SET+CCS
or SET+HES+CCS)
0.0
Pr2
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
rEG
oHt
Threshold for automatic activation of
Pull Down in normal mode
(SET+HY+oHt)
20.0
Pr2
°F
[0.0°C to 25.0°C]
[0.0°F to 45.0°F]
rEG
oHE
Threshold for automatic activation of
Pull Down in energy saving mode
(SET+HES+HYE+oHE)
20.0
Pr2
°F
[0.0°C to 25.0°C]
[0.0°F to 45.0°F]
rEG
Con
Compressor ON time with faulty probe
10
Pr1
min
0 to 255 min
rEG
CoF
Compressor OFF time with faulty probe
15
Pr1
min
0 to 255 min
Prb
ot
Probe P1 calibration
0
Pr1
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
Prb
P2P
Probe P2 presence
Y
Pr1
n(0); Y(1)
Prb
oE
Probe P2 calibration
0
Pr1
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
Prb
P3P
Probe P3 presence
no
Pr1
n(0); Y(1)
Prb
o3
Probe P3 calibration
0
Pr1
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]