1592040000 XR70T EN v1.1 2019.07.09
XR70T
31/40
•
HYF
: differential
•
FnC
: to define the working mode:
o
C-n:
in parallel with compressor output and stopped during any defrost. When compressor is OFF,
they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
O-n:
always on, stopped during any defrost
o
C-Y:
in parallel with compressor output and always on during any defrost. When compressor is
OFF, they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
o-Y:
always on
•
Fnd:
activation delay after any defrost
10.1 EVAPORATOR FAN AND DIGITAL INPUT
When a digital input is configured as a door switch (
i1F or i2F=dor
) and this digital input is active, evaporator
fan and compressor status will depend on par.
odC
:
•
odC=no
: normal regulation
•
odC=FAn
: evaporator fan OFF
•
odC=CPr
: compressor OFF
•
odC=F-C
: compressor and evaporator fan OFF
When
rrd=Y
, the regulation restarts after
d1d
or
d2d
time.
11.
CONDENSER FAN
To enable the condenser fan management it is required to set a condenser probe (par.
FAC
). Here are the
involved parameters:
•
FAC
: to select the control probe
•
St2
: to select the deactivation setpoint
•
HY2
: differential
•
FCC
: to define the working mode:
o
C-n:
in parallel with compressor output and stopped during any defrost. When compressor is OFF,
they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
O-n:
always on, stopped during any defrost
o
C-Y:
in parallel with compressor output and always on during any defrost. When compressor is
OFF, they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
o-Y:
always on
12.
DIGITAL OUTPUTS
Depending on the model, one or more digital outputs (relays) can be configurated with one of the following
functionalities.
12.1 COMPRESSOR OUTPUT (oAx = CP1)
With
oAx=CP1
the relay operates as the main regulation output.
12.2 DEFROST OUTPUT (oAx = dEF)
With
oAx=dEF
the relay operates as a defrost output.
12.3 EVAPORATOR FAN OUTPUT (oAx = FAn)
With
oAx=FAn
the relay operates as an evaporator fan output.
12.4 ALARM OUTPUT (oAx = ALr)
With
oAx=ALr
the output operates as an alarm output. It is activated every time an alarm happens. Its status
depends on the
tbA
parameter: if
tbA=Y
, the output is deactivated by pressing any key.
If
tbA=n
, the alarm output stays on until the alarm condition recovers.
12.5 LIGHT OUTPUT (oAx = LiG)
With
oAx=LiG
the relay operates as a light output.