background image

 

 

 

1592040000 XR70T EN v1.1 2019.07.09 

XR70T 

29/40 

rtC 

Ld5 

5th defrost starting time 

00:00 

Pr2 

hh:m

0.0 to 23h50min(143); nu(144) 

rtC 

Ld6 

6th defrost starting time 

00:00 

Pr2 

hh:m

0.0 to 23h50min(143); nu(144) 

E2 

MAP 

Current configuration 

Pr1 

 

C-1(0); C-2(1) 

E2 

LdM 

Restore default factory setting 

Pr2 

 

n(0); Y(1) 

E2 

rHA 

Reset Haccp values  

Pr2 

 

n(0); Y(1) 

CoM 

Adr 

Serial address 

Pr2 

 

1 to 247 

CoM 

bAU 

Baudrate 

9.6 

Pr2 

 

9.6(0); 19.2(1);  

38.4(2); 57.6(3); 

CoM 

PAr 

Parity control 

no 

Pr2 

 

no(0); odd(1); EvE(2) 

Ui 

SCS 

User interface timeout  

60 

Pr2 

sec 

1 to 255 sec 

Ui 

bS 

Sound Level 

Pr2 

 

0 to 5 

Ui 

PSU 

Password for protected level Pr2 

 

Pr2 

 

0 to 999 

inF 

dP1 

Probe P1 value visualization 

 

Pr1 

 

read only 

inF 

dP2 

Probe P2 value visualization 

 

Pr1 

 

read only 

inF 

dP3 

Probe P3 value visualization 

 

Pr1 

 

read only 

inF 

dP4 

Probe P4 value visualization 

 

Pr1 

 

read only 

inF 

rSE 

Real regulation Set Point (SET + ES + 

SETd) 

 

Pr1 

 

read only 

inF 

FdY 

Firmware release date: day 

 

Pr1 

 

read only 

inF 

FMn 

Firmware release date: month 

 

Pr1 

 

read only 

inF 

FYr 

Firmware release date: year 

 

Pr1 

 

read only 

inF 

rEL 

Firmware release 

 

Pr1 

 

read only 

inF 

SUb 

Firmware sub release 

 

Pr1 

 

read only 

inF 

Ptb 

Parameter map version 

 

Pr1 

 

read only 

6. 

REGULATION 

The regulation is based on the temperature measured 
by the thermostat probe (P1) with a positive differential 
respect to the set point: if the temperature  increases 
and  reaches  the  set  point  plus  differential,  the 
compressor will start. The compressor will stop when 
the temperature reaches the set point value again. In 
case of fault because of the thermostat probe, the start 
and  stop  of  the  compressor  are  timed  through 
parameters 

CoF

 and 

Con

 

7. 

ENERGY SAVING 

The standard SET-POINT (

SET

) is used to maintain the temperature at a certain value when the energy 

saving status (ES) is not active. On the other hand, when the ES status is active a different SET-POINT 
(

SET_ES

), higher than the standard one, will be used. The parameter 

HES

 defines the energy setpoint 

according to the following formula: 

SET_ES = SET + HES

 

There are also two different differential values for 

SET

 and 

SET_ES

, which are used for compressor cut-in 

and cut-out: when ES status is active, the 

HYE

 parameter will be used instead of the 

HY

 parameter. 

7.1 

BASIC ENERGY SAVING ALGORITHM 

The energy saving status will be always saved in the internal memory to resume previous operation if a 
power failure occurs. The presence of a door switch to work properly (for example: 

i1F=dor

) is required. 

Summary of Contents for Dixell XR70T

Page 1: ...XR70T Full Touch V 1 0 ...

Page 2: ......

Page 3: ...1 14 Serial Communication port configuration parameters CoM 18 5 1 15 User Interface configuration parameters Ui 18 5 1 16 Information read only parameters inF 18 5 2 PARAMETER CONFIGURATION 1 19 5 3 PARAMETER CONFIGURATION 2 24 6 REGULATION 29 7 ENERGY SAVING 29 7 1 BASIC ENERGY SAVING ALGORITHM 29 7 1 1 PARAMETERS INVOLVED 30 8 PULL DOWN FUNCTION 30 9 DEFROST OPERATIONS 30 9 1 TIMED OR TEMPERATU...

Page 4: ...TPUT IXF LIG 33 13 12 CHANGE CONFIGURATION IXF CC 33 13 13 MOTION SENSOR DETECTOR IXF EMT 33 14 ALARM SIGNALLING 34 14 1 ALARM RECOVERY 34 15 SERIAL COMMUNICATION 34 16 INSTALLATION AND MOUNTING 34 17 WIRING DIAGRAM 35 18 TECHNICAL SPECIFICATIONS 36 19 APPENDIX 37 19 1 TOOLS 37 19 1 1 XH REP 37 19 1 2 X MOD 37 19 1 3 WIZMATE 37 19 1 4 HOTKEY 37 19 1 5 USB TO RS485 CONVERTER 37 19 2 EXAMPLE OF MENU...

Page 5: ...d by the End User the device must not be opened consider the maximum current that can be applied to each relay make sure that the wires of the probes of the loads and the electical power supply cables are sufficiently separated from each other without crossing or intertwining In case of applications in industrial environments it may be useful to use the main filters as well as the inductive loads ...

Page 6: ...he device from the rest of the electrical devices connected inside the electrical panel The secondary of the transformer must never be connected to the earth Dixell Srl reserves the right to change the components of its products even without notice ensuring the same and unchanged functionality 2 PRODUCT DISPOSAL WEEE In compliance with the Directive 2002 96 EC of the European Parliament and of the...

Page 7: ...CT dixell service emerson com 4 USER INTERFACE XR70T has a capacitive user interface with Full Touch technology The whole display area is used to interact with the device Specific gestures are used to enable or disable functions browse through screens and operational modes and modify the configuration of the device 4 1 SCREENS SCREEN DESCRIPTION Home this screen shows temperature value measurement...

Page 8: ...FF When in the Loads Info screen compressor output OFF FLASH Anti short cycle delay is running ON When in the Loads Info screen compressor output ON FAN OFF When in the Loads Info screen evaporator fan output OFF FLASH Activation delay is running ON When in the Loads Info screen evaporator fan output ON DEFROST OFF Function not available FLASH When in the Virtual Keyboard screen defrost ON ON When...

Page 9: ...EL 2 icons toggle when the visualized value is editable ON First level parameter groups of the parameter menu is visualized PROG LEVEL 2 OFF FLASH PROG LEVEL 2 and PROG LEVEL 1 icons toggle when the visualized value is editable ON Second level parameter labels of the parameter menu is visualized RADIO ON OFF Not used FLASH Not used ON Not used PROGRAMMING MODE OFF Programming mode disabled FLASH O...

Page 10: ...wse through HOME Virtual Keyboard and Info View When in programming mode use horizontal swipe to browse through parameter menu V SWIPE Drag a finger across the screen from top to bottom or from bottom to top overlapping only one of the digits Modify use vertical swipe from top to bottom or bottom to top to change a parameter value 4 4 HOME BROWSING Use H SWIPE to move through the screens The logic...

Page 11: ...c 4 The copying procedure will start and the PRG icon will blink during the copy operations 5 At the end of the copying procedure a message will notify the user that the operation has been competed successfully a End all parameters have been copied b Err some error occours during copying operations 4 9 HOTKEY DOWNLOAD When in Power off or in Stand by mode it is possible to activate the HotKey Down...

Page 12: ...guration parameters FAn Evaporator and condenser fan configuration parameters AUS Auxiliary regulator parameters ALr Alarm configuration parameters oUt Digital and analogue output configuration parameters inP Digital input configuration parameters ES Energy saving configuration parameters Cnt Counters read only values rtC Real Time Clock configuration parameters E2 Memory storage management CoM Se...

Page 13: ...er cooling phase the regulation SETPOINT is moved to SET CCS in normal mode or to SET HES CCS in energy saving mode oHt Threshold for automatic activation of Pull Down in normal mode SET HY oHt 1 0 to 12 0 C 1 to 21 F this is the upper limit used to activate the super cooling function oHE Threshold for automatic activation of Pull Down in energy saving mode SET HES HYE oHE 1 0 to 12 0 C 1 to 21 F ...

Page 14: ...fter finishing a defrost phase Hon Drain heater enabled after draining time par Fdt 0 to 255 min the relative output will stay on after draining time dPo Defrost cycle enebled at stat up n Y enables defrost at power on od1 Automatic defrost at the beginning of any energy saving mode n Y n function disabled Y function enabled 5 1 5 Evaporator and condenser fan configuration parameters FAn FAP Probe...

Page 15: ...Cut out is SAA ArP Probe selection for auxiliary regulator nP P1 P2 P3 P4 nP no probe the auxiliary relay is switched only by the digital input Px probe x Note P4 Probe on Hot Key plug Sdd Auxiliary regulator disabled during any defrost cycle n Y n the auxiliary relay operates during defrost Y the auxiliary relay is switched off during defrost btA Base time for parameters Ato and AtF SEC Min SEC b...

Page 16: ...zer nor any digital output set as an alarm Y yes it is possible to deactivate both the buzzer and the digital output set as an alarm 5 1 8 Digital and analogue output configuration parameters out oAx x 2 3 4 Relay output oAx configuration nu CP1 dEF FAn ALr LiG AUS db onF HES Cnd nu not used CP1 compressor dEF defrost FAn ventilators ALr alarm LiG light AUS auxiliary relay onF always ON with instr...

Page 17: ... 54 to 54 F sets the increasing value of the set point during the Energy Saving cycle LdE Energy saving controls the lights lights OFF when energy saving is active n Y lights off when energy saving mode is active StE Period to switch from normal mode to energy saving mode 0 0 to 24h00min res 10 min if the door stay closed for StE time the energy saving mode will be activated NOTE this will require...

Page 18: ...onday defrost dd3 Tuesday defrost dd4 Wednesday defrost dd5 Thursday defrost dd6 Friday defrost dd7 Sunday defrost Ldx Defrost starting time 00h00min to 23h50min these parameters set the beginning of the programmable defrost cycles during any ddx day Example when Ld2 12 4 the second defrost starts at 12 40 am during working days 5 1 13 Memory storage management E2 MAP Current configuration C 1 C 2...

Page 19: ...o 12 0 C 21 6 F to 21 6 F rEG oHt Threshold for automatic activation of Pull Down in normal mode SET HY oHt 10 0 Pr2 C 0 0 C to 25 0 C 0 0 F to 45 0 F rEG oHE Threshold for automatic activation of Pull Down in energy saving mode SET HES HYE oHE 10 0 Pr2 C 0 0 C to 25 0 C 0 0 F to 45 0 F rEG Con Compressor ON time with faulty probe 10 Pr1 min 0 to 255 min rEG CoF Compressor OFF time with faulty pro...

Page 20: ...ting mode C_n Pr2 C n 0 O n 1 C Y 2 O Y 3 FAn Fnd Evaporator fan delay after defrost cycle 1 Pr2 min 0 to 255 min FAn FCt Differential temperature for cyclic activation of evaporator fans o disabled 0 Pr2 C 0 C to 50 C 0 F to 90 F FAn FSU Evaporator fan operating mode Std Pr2 Std 0 FoF 1 Fon 2 FAn Ft Evaporator fan controlled during defrost no Pr2 n 0 Y 1 FAn Fon Evaporator fan ON time in normal m...

Page 21: ... ALr AP2 Probe selection for second temperature alarm P2 Pr2 nP 0 P1 1 P2 2 P3 3 P4 4 ALr AU1 Pre alarm threshold for second temperature alarm absolute value 150 0 Pr2 C 100 0 C to 150 0 C 148 0 F to 302 0 F ALr AH1 Second high temperature pre alarm differential 2 0 Pr2 C 0 1 C to 25 0 C 0 1 F to 45 0 F ALr Ad1 Second high temperature pre alarm delay 255 Pr2 min 0 to 255 min ALr AL2 Second low tem...

Page 22: ...de temperature differential 0 Pr1 C 30 C to 30 C 54 F to 54 F ES LdE Energy saving controls the lights lights OFF when energy saving is active no Pr1 n 0 Y 1 ES StE Period to switch from normal mode to energy saving mode 00 00 Pr1 hh mm 0 to 23h50min nu ES EtS Period to switch from energy saving mode to normal mode 00 00 Pr1 hh mm 0 to 23h50min nu ES dS Door opening time to switch from EtS to StE ...

Page 23: ...ing cycle starting time on working days 00 00 Pr2 hh mm 0 0 to 23h50min rtC dLE Energy saving cycle duration on working days 00 00 Pr2 hh mm 0 0 to 24h00min rtC iSE Energy saving cycle starting time on weekends 00 00 Pr2 hh mm 0 0 to 23h50min rtC dSE Energy saving cycle duration on weekends 00 00 Pr2 hh mm 0 0 to 24h00min rtC dd1 Sunday defrost no Pr2 n 0 Y 1 rtC dd2 Monday defrost no Pr2 n 0 Y 1 ...

Page 24: ...ET to 302 0 F rEG HY Compressor regulation differential in normal mode 6 0 Pr1 F 0 1 C to 25 0 C 0 1 F to 45 0 F rEG HYE Compressor regulation differential in energy saving mode 6 0 Pr1 F 0 1 C to 25 0 C 0 1 F to 45 0 F rEG odS Output activation delay at start up 0 Pr1 min 0 to 255 min rEG AC Anti short cycle delay 0 Pr1 min 0 to 50 min rEG rtr Regulation percentage F P1 P2 100 P1 0 P2 100 Pr2 0 t...

Page 25: ...F 3 Coo 4 dEF dAd Temperature display delay after any defrost cycle 0 Pr2 min 0 to 255 min dEF Fdt Draining time 1 Pr2 min 0 to 255 min dEF Hon Drain heater enabled after draining time par Fdt 2 Pr2 min 0 to 255 min dEF dPo Defrost cycle enebled at stat up no Pr2 n 0 Y 1 dEF od1 Automatic defrost at the beginning of any energy saving mode no Pr2 n 0 Y 1 FAn FAP Probe selection for evaporator fan P...

Page 26: ...E 0 Ab 1 ALr ALU High temperature alarm 302 0 Pr1 F C 0 0 to 50 0 or ALL to 150 0 F 0 0 to 90 0 or ALL to 302 0 ALr ALL Low temperature alarm 100 0 Pr1 F C 0 0 to 50 0 or 100 0 to ALU F 0 0 to 90 0 or 148 0 to ALU ALr AFH Temperature alarm differential 4 0 Pr1 F 0 1 C to 25 0 C 0 1 F to 45 0 F ALr ALd Temperature alarm delay 0 Pr1 min 0 to 255 min ALr dot Temperature alarm delay with door open 00 ...

Page 27: ...e depends on par ibt 0 Pr1 sec 0 to 255 min sec inP nPS Number of external pressure switch alarms before stopping the regulation 0 Pr2 0 to 15 inP odC Compressor and fan status after door opening no Pr2 no 0 FAn 1 CPr 2 F C 3 inP rrd Regulation restart after door alarm no Pr2 n 0 Y 1 ES ErA Energy saving algorithm nu Pr2 nu 0 bAS 1 ES HES Energy saving mode temperature differential 0 Pr1 F 30 C to...

Page 28: ...output oA4 units of Pr1 hours read only rtC Hur Hours Pr1 read only rtC Min Minutes Pr1 read only rtC dAY Day of the week Pr1 read only rtC dYM Day of the month Pr1 read only rtC Mon Month Pr1 read only rtC YAr Year Pr1 read only rtC Hd1 First day of weekend nu Pr2 Sun 0 to SAt 6 nu 7 rtC Hd2 Second day of weekend nu Pr2 Sun 0 to SAt 6 nu 7 rtC iLE Energy saving cycle starting time on working days...

Page 29: ... read only inF Ptb Parameter map version Pr1 read only 6 REGULATION The regulation is based on the temperature measured by the thermostat probe P1 with a positive differential respect to the set point if the temperature increases and reaches the set point plus differential the compressor will start The compressor will stop when the temperature reaches the set point value again In case of fault bec...

Page 30: ...fter power on if T SET CCS When the regulation probe temperature T is o T SET HY oHt value in normal mode o T SET HES HYE oHE value in energy saving mode In these cases a different set point value SET CCS will be used As soon as the room temperature reaches the SET CCS value the compressor will stop and the normal regulation will restart NOTE Pull Down function is disabled when CCS 0 or CCt 0 The ...

Page 31: ...rol probe St2 to select the deactivation setpoint HY2 differential FCC to define the working mode o C n in parallel with compressor output and stopped during any defrost When compressor is OFF they will start a duty cycle mode see FoF Fon FF1 and Fo1 parameters o O n always on stopped during any defrost o C Y in parallel with compressor output and always on during any defrost When compressor is OF...

Page 32: ...0 or AtF 0 the auxiliary output is disabled 12 7 DEAD BAND REGULATION oAx db With oAx db the output can be used to control for example a heater element It is used to implement a dead band regulation If so oAx db cut in is SET HY oA1 db cut out is SET 12 8 ON OFF OUTPUT oAx onF When oAx onF the output is activated when the controller is switched on and deactivated when the controller is switched of...

Page 33: ...put if present and configured will be enabled disabled following the status of the relative digital input 13 4 ENERGY SAVING ixF ES The energy saving mode will be enabled disabled following the status of the relative digital input 13 5 EXTERNAL WARNING ALARM ixF EAL It is used to detect an external alarm It does not lock the regulation 13 6 EXTERNAL LOCK ALARM ixF bAL It is used to detect any crit...

Page 34: ...ations Always check the connections probe device terminals before replacing the probe Temperature alarms HA LA H2 and L2 are automatically reset as soon as the temperature is within the normal working range It is possible to reset the EE alarm by pressing any button The alarms EA CA and dA are automatically reset as soon as the relative digital input is disabled The internal buzzer can be muted by...

Page 35: ...1592040000 XR70T EN v1 1 2019 07 09 XR70T 35 40 17 WIRING DIAGRAM Power Supply 110VAC 230VAC or 100 240VAC 50 60Hz oA1 always set as main compresso output CP1 ...

Page 36: ...0T150 C resolution 0 1 C or 1 C selectable PTC 50T150 C resolution 0 1 C or 1 C selectable Accuracy 1 compared to the full scale Inputs Up to 4 NTC PTC or PT1000 configurable Up to 2 voltage free contacts Relay Outputs Nominal UL IEC oA1 SPST 16A 250VAC 10FLA 60LRA 30k cycles Pilot Duty B300 6k cycles 10 4 A 250 Vac 50 60 Hz 100K cycles oA2 SPDT 8A 250VAC hp 240 Vac 30k cycles Pilot Duty B300 30k ...

Page 37: ...version must be used The X_MOD usage will disable the serial communication 19 1 3 WIZMATE WIZMATE software used in combination with the XJ485USB allows to manage the configuration of the controller 19 1 4 HOTKEY The HOT KEY is used for a quick and easy upload from device to HOT KEY or download from HOT KEY to device of the parameter map The 64K version must be used code DK00000300 19 1 5 USB TO RS...

Page 38: ... 09 XR70T 38 40 H SWIPE to browse 19 2 EXAMPLE OF MENU NAVIGATION AND PARAMETER MODIFICATION and icons are blinking TAP and HOLD PRESS PRG TAP and HOLD PRG TAP and HOLD PRG to save and exit and exit V SWIPE to modify TAP and HOLD PRG ...

Page 39: ...1592040000 XR70T EN v1 1 2019 07 09 XR70T 39 40 ...

Page 40: ...1592040000 XR70T EN v1 1 2019 07 09 XR70T 40 40 ...

Reviews: