1592033070 XR70CHC EN r1.0 2019.01.30
XR70CHC
6/6
19
ALARM SIGNALLING
Label Cause
Outputs
“oFF”
Keyboard locked
Outputs unchanged
“on”
Keyboard unlocked
Outputs unchanged
“
P1
”
Room probe failure
Compressor output according to
Con
e
CoF
“
P2
”
Evaporator probe failure
Defrost end is timed
“P3”
Third probe failure
Depends on the alarms
“P4”
Fourth probe failure
Linked temperature alarm is not managed
“
HA
”
Maximum temperature alarm
Outputs unchanged
“
LA
”
Minimum temperature alarm
Outputs unchanged
“H2”
Maximum temperature for second
temperature alarm
Outputs unchanged
“L2”
Minimum temperature for second
temperature alarm
Outputs unchanged
“dA”
Door open more than
dxd
time
Compressor and fans restarts
“EA”
External alarm
Outputs unchanged
“CA”
Serious external alarm
Outputs disabled
“EE”
EEPROM alarm
Outputs unchanged
19.1
ALARM RECOVERY
Probe alarms
“
P1
”
,
“
P2
”
,
“
P3
”
and “
P4
”
start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections before
replacing the probe. Temperature alarms “
HA
”
,
“
LA
”
,
“
H2
” and “
L2
”
automatically stop as soon as the
temperature returns to normal values.
It is possible to reset the “
EE
” alarm by pressing any button.
The alarms “EA”, “CA” and “dA”
will automatically stop as soon as the digital input is disabled.
The internal buzzer can be muted by pressing any key if parameter
tbA=Y
.
20
TECHNICAL DATA
Housing:
self-extinguishing ABS
Case:
frontal 32x74 mm; depth 60mm
Mounting:
panel mounting in a 71x29mm panel cut-out
Body Protection:
IP20
Frontal protection:
IP65
Terminal blocks:
Screw terminal block
2.5 mm
2
wiring
Power supply:
(according to the model) 230Vac
10%, 50/60Hz; 110Vac
10%, 50/60Hz
Power absorption:
3.5VA max
Display
: 3-digit LED, H=14.2 mm
Inputs
: up to 4 NTC, PTC or PT1000 probes
Digital input:
up to 2 voltage free contacts
Relay outputs: Compressor
SPST 16(5)A, 250VAC;
oA2:
SPDT 8(2)A, 250VAC;
oA3:
SPST 8(3)A, 250VAC;
oA4:
SPST 5(2)A, 250VAC
Data storing
: EEPROM
Kind of action:
1B
Pollution degree:
2
Software class:
A
Rated impulsive voltage
: 2500V;
Overvoltage Category
: II
Operating temperature:
0 to 60°C (32 to 140°F)
Storage temperature:
-25 to 60°C (-13 to 140°F)
Relative humidity:
20 to 85% (no condensing)
Measuring and regulation range:
NTC
-40 to 110°C (-40 to 230°F)
PTC
-55 to 150°C (-67 to 302°F)
PT1000
-100 to 200°C (-148 to 392°F)
Resolution:
0.1°C or 1°C (selectable)
Accuracy (ambient temp. 25°C)
:
NTC or PTC:
±0.1°C ±1 digit
PT1000:
±0.1°C ±1 digit for probes Pb1, Pb2 and Pb3; ±1.0°C ±1 digit for probe Pb4
Real time clock:
data maintenance up to 6 months with lithium battery
HOT-KEY inputs:
MAX voltage allowed is 3.3VDC. DO NOT CONNECT ANY EXTERNAL POWER
SUPPLY.
20.1
STANDARDS
The complete Declaration of Conformity can be found at:
https://dxapp.cloud/
20.1.1
THE XR70CHC IS COMPLIANT WITH THE FOLLOWING STANDARDS
ETSI EN 300 328 V2.1.1 (2016-11)
ETSI EN 301 489-17 V3.1.1 (2016-11)
IEC EN 60730-2-9: 2008 (Third Edition) and Am.1:2011 in conjunction with IEC 60730-1:2010 (Fourth Edition)
UL 60730-1 Fourth Edition and CAN/CSA-E60730-1:02 Third Edition along with its Amendment 1 dated
February 2007, the Standards for Automatic electrical controls for household and similar use
–
Part 1: General
requirements.
It therefore meets the essential requirements of the following Directives:
Radio equipment Directive 2014/53/EU
Electromagnetic compatibility 2004/108/EC
Low Voltage equipment 2006/95/EC
20.1.2
THE XR70CHC IS COMPLIANT WITH THE FOLLOWING STANDARDS
FCC 15.247
20.1.3
THE XR70CHC IS COMPLIANT TO PART 15 OF THE FCC RULE
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired
operation.”
Unauthorized repairs, changes or modifications could result in permanent damage to the equipment and void
your warranty and your authority to operate this device under Part 15 of the FCC Rules.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be required to correct the interference at
his own expense.
20.1.4
THE XR70CHC IS COMPLIANT TO RSS 102
This device complies with Industry Canada RSS-210. Operation is subject to the following two conditions: (1)
this device may not cause interference, and (2) this device must accept any interference, including
interference that may cause undesired operation of the device.
20.1.5
CET XR70CHC INSTRUMENT REPOND AUX NORMES RSS 102
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils
radio RSS-210.
L’exploitation est autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas produire de brouillage, et
(2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est
susceptible d’en
compromettre le fonctionnement.
21
WIRINGS
21.1
XR70CHC, 16+8+8+5A
Power Supply:
110 or 230 Vac @50 or 60Hz
22
BLUETOOTH COMMUNICATION
The controller implements a Bluetooth 4.2 communication module. This gives
the possibility to communicate with external devices (for example with a mobile
APP able to recognize and decode the device). All controllers use a unique
MAC-ADDRESS, which is used both for identification and communication. The
communication range is about 5 m (worst case, indoor coverage in presence of
obstacles). Over this distance it is possible to suffer interruptions in the
communication or quality degradation of the communication. A 6-digit pairing
secure code can be required for connection. Please follow the Emerson
Connected APP instruction for more information.
22.1
FIRST INSTALLATION
After installation, it will be possible to manage the controller by using the Emerson Connected APP. Il will be
required to:
-
Install the Emerson Connected APP on your mobile device (smartphone or tablet)
-
Create a new user account before using the APP
The owner is the only account that can:
-
Manage the controller via Bluetooth
-
Extend rights of access to a specific appliance also to other users
A Cloud portal will be used for:
-
Extend rights of access to a specific appliance also to other users
-
Select the permission level for any new user
The link for opening the Cloud webpage is on the left side menu of the mobile APP (slide right the screen of
the APP when on the Device List
page and follow the “Cloud management” link. Please note that the login and
password for the Cloud webpage are the same of the mobile APP.
22.2
RESET TO FACTORY DEFAULT
In case a factory reset is required, please follow these operations:
-
Access to the Cloud webpage and select the appliance you want to reset (search for name
and/or MAC-ADDRESS)
-
Click on the “DELETE” link, the appliance will be removed from the list of owned appliances
-
Go to the device controller (with the same MAC-ADDRESS)
-
Enter the programming mode
-
Go to the “
b
LE” menu
-
Select the par.
rPS
(reset device ownership)
-
Select “Y” and confirm with SET button
-
Select the par.
rLi
(reset device whitelist)
-
Select “Y” and confirm with SET button
-
Exit from the programming menu
-
Logout and login from the mobile APP
After this, the controller will be reset to factory default configuration and it will be ready for a new association.