1592033070 XR70CHC EN r1.0 2019.01.30 

                           XR70CHC 

6/6 

 

19

 

ALARM SIGNALLING 

Label  Cause 

Outputs 

“oFF”

  Keyboard locked 

Outputs unchanged 

“on”

  Keyboard unlocked 

Outputs unchanged 

P1

  Room probe failure 

Compressor output according to 

Con

 e 

CoF

  

P2

  Evaporator probe failure 

Defrost end is timed 

“P3”

  Third probe failure 

Depends on the alarms 

“P4”

  Fourth probe failure 

Linked temperature alarm is not managed 

HA

  Maximum temperature alarm 

Outputs unchanged 

LA

  Minimum temperature alarm 

Outputs unchanged 

“H2”

 

Maximum temperature for second 
temperature alarm 

Outputs unchanged 

“L2”

 

Minimum temperature for second 
temperature alarm 

Outputs unchanged 

“dA”

  Door open more than 

dxd

 time 

Compressor and fans restarts  

“EA”

  External alarm 

Outputs unchanged 

“CA”

  Serious external alarm 

Outputs disabled 

“EE”

  EEPROM alarm 

Outputs unchanged 

19.1

 

ALARM RECOVERY 

Probe alarms 

P1

P2

P3

 

and “

P4

 start some seconds after the fault in the related probe; they 

automatically stop some seconds after the probe restarts normal operation. Check connections before 

replacing the probe. Temperature alarms “

HA

LA

H2

” and “

L2

” 

automatically stop as soon as the 

temperature returns to normal values. 

It is possible to reset the “

EE

” alarm by pressing any button.

 

The alarms “EA”, “CA” and “dA” 

will automatically stop as soon as the digital input is disabled. 

The internal buzzer can be muted by pressing any key if parameter 

tbA=Y

20

 

TECHNICAL DATA 

Housing: 

self-extinguishing ABS

 

Case: 

frontal 32x74 mm; depth 60mm 

Mounting: 

panel mounting in a 71x29mm panel cut-out 

Body Protection: 

IP20 

Frontal protection: 

IP65 

Terminal blocks: 

Screw terminal block 

 2.5 mm

2

 wiring 

Power supply: 

(according to the model) 230Vac 

10%, 50/60Hz; 110Vac 

10%, 50/60Hz

 

Power absorption: 

3.5VA max

 

Display

: 3-digit LED, H=14.2 mm 

Inputs

: up to 4 NTC, PTC or PT1000 probes

 

Digital input: 

 up to 2 voltage free contacts 

Relay outputs:  Compressor 

SPST 16(5)A, 250VAC;  

oA2: 

SPDT 8(2)A, 250VAC;  

oA3: 

SPST 8(3)A, 250VAC;  

oA4:

 SPST 5(2)A, 250VAC 

Data storing

: EEPROM 

Kind of action: 

1B  

Pollution degree: 

2  

Software class: 

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0 to 60°C (32 to 140°F) 

Storage temperature: 

-25 to 60°C (-13 to 140°F) 

Relative humidity:

 20 to 85% (no condensing) 

Measuring and regulation range:  

NTC 

-40 to 110°C (-40 to 230°F) 

PTC

 -55 to 150°C (-67 to 302°F) 

PT1000

 -100 to 200°C (-148 to 392°F) 

Resolution: 

0.1°C or 1°C (selectable) 

Accuracy (ambient temp. 25°C)

:   

NTC or PTC:

 ±0.1°C ±1 digit 

PT1000:

 ±0.1°C ±1 digit for probes Pb1, Pb2 and Pb3; ±1.0°C ±1 digit for probe Pb4 

Real time clock:

 data maintenance up to 6 months with lithium battery 

HOT-KEY inputs:

 MAX voltage allowed is 3.3VDC. DO NOT CONNECT ANY EXTERNAL POWER 

SUPPLY. 

20.1

 

STANDARDS 

 

The complete Declaration of Conformity can be found at:  

 

https://dxapp.cloud/ 

20.1.1

 

THE XR70CHC IS COMPLIANT WITH THE FOLLOWING STANDARDS  

ETSI EN 300 328 V2.1.1 (2016-11) 
ETSI EN 301 489-17 V3.1.1 (2016-11) 
IEC EN 60730-2-9: 2008 (Third Edition) and Am.1:2011 in conjunction with IEC 60730-1:2010 (Fourth Edition)  
UL  60730-1  Fourth  Edition  and  CAN/CSA-E60730-1:02  Third  Edition  along  with  its  Amendment  1  dated 
February 2007, the Standards for Automatic electrical controls for household and similar use 

 Part 1: General 

requirements. 
 
It therefore meets the essential requirements of the following Directives: 

Radio equipment Directive 2014/53/EU 
Electromagnetic compatibility 2004/108/EC 
Low Voltage equipment 2006/95/EC 

20.1.2

 

THE XR70CHC IS COMPLIANT WITH THE FOLLOWING STANDARDS 

FCC 15.247 

20.1.3

 

THE XR70CHC IS COMPLIANT TO PART 15 OF THE FCC RULE 

Operation is subject to the following two conditions:  
(1) this device may not cause harmful interference, and  
(2)  this  device  must  accept  any  interference  received,  including  interference  that  may  cause  undesired 

operation.”

 

 
Unauthorized repairs, changes or modifications could result in permanent damage to the equipment and void 
your warranty and your authority to operate this device under Part 15 of the FCC Rules. 

 

NOTE:  This  equipment  has  been  tested  and  found  to  comply  with  the  limits  for  a  Class  A  digital  device, 
pursuant  to  part  15  of  the  FCC  Rules.  These  limits  are  designed  to  provide  reasonable  protection against 
harmful interference when the equipment is operated in a commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction 
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential 
area is likely to cause harmful interference in which case the user will be required to correct the interference at 
his own expense. 

20.1.4

 

THE XR70CHC IS COMPLIANT TO RSS 102 

This device complies with Industry Canada RSS-210. Operation is subject to the following two conditions: (1) 
this  device  may  not  cause  interference,  and  (2)  this  device  must  accept  any  interference,  including 
interference that may cause undesired operation of the device. 

 

20.1.5

 

CET XR70CHC INSTRUMENT REPOND AUX NORMES RSS 102 

Le  présent  appareil  est  conforme  aux  CNR  d’Industrie  Canada  applicables  aux  appareils 

radio  RSS-210. 

L’exploitation est autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas produire de brouillage, et 
(2)  l’utilisateur  de  l’appareil  doit  accepter  tout  brouillage  radioélectrique  subi,  même  si  le  brouillage  est 
susceptible d’en

 compromettre le fonctionnement. 

21

 

WIRINGS 

21.1

 

XR70CHC, 16+8+8+5A  

 

 

Power Supply:

  

110 or 230 Vac @50 or 60Hz 

22

 

BLUETOOTH COMMUNICATION 

 

The controller implements a Bluetooth 4.2 communication module. This gives 
the possibility to communicate with external devices (for example with a mobile 
APP  able  to  recognize  and  decode  the  device).  All  controllers  use  a  unique 
MAC-ADDRESS, which is used both for identification and communication. The 
communication range is about 5 m (worst case, indoor coverage in presence of 
obstacles).  Over  this  distance  it  is  possible  to  suffer  interruptions  in  the 
communication or  quality  degradation  of  the  communication.  A 6-digit  pairing 
secure  code  can  be  required  for  connection.  Please  follow  the  Emerson 
Connected APP instruction for more information. 

22.1

 

FIRST INSTALLATION 

After installation, it will be possible to manage the controller by using the Emerson Connected APP. Il will be 
required to: 

-

 

Install the Emerson Connected APP on your mobile device (smartphone or tablet) 

-

 

Create a new user account before using the APP 

The owner is the only account that can: 

-

 

Manage the controller via Bluetooth 

-

 

Extend rights of access to a specific appliance also to other users 

 
A Cloud portal will be used for: 

-

 

Extend rights of access to a specific appliance also to other users 

-

 

Select the permission level for any new user 

 
The link for opening the Cloud webpage is on the left side menu of the mobile APP (slide right the screen of 
the APP when on the Device List 

page and follow the “Cloud management” link. Please note that the login and 

password for the Cloud webpage are the same of the mobile APP. 

22.2

 

RESET TO FACTORY DEFAULT 

In case a factory reset is required, please follow these operations: 

-

 

Access to the Cloud webpage and select the appliance you want to reset (search for name 
and/or MAC-ADDRESS) 

-

 

Click on the “DELETE” link, the appliance will be removed from the list of owned appliances

 

-

 

Go to the device controller (with the same MAC-ADDRESS) 

-

 

Enter the programming mode 

-

 

Go to the “

b

LE” menu

 

-

 

Select the par. 

rPS

 (reset device ownership) 

-

 

Select “Y” and confirm with SET button

 

-

 

Select the par. 

rLi

 (reset device whitelist) 

-

 

Select “Y” and confirm with SET button

 

-

 

Exit from the programming menu 

-

 

Logout and login from the mobile APP 

After this, the controller will be reset to factory default configuration and it will be ready for a new association. 
 

Summary of Contents for Dixell XR70CHC

Page 1: ...NERGY SAVING ALGORITHM The energy saving status will be always saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to...

Page 2: ...ions related to par UPC and UP2 if available DOWN In programming mode it browses the parameter codes or decreases the displayed value Other functions related to the par dnC and dn2 if available ONOFF Keep it pressed for 3 sec to switch on and off the device KEYS COMBINATION To lock or unlock the keyboard To enter in programming mode To return to room temperature display ICON MODE MEANING On Compre...

Page 3: ...t any possible offset of the first probe P2P Evaporator probe presence n not present Y the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of the third probe P3P Third probe presence n not present Y the defrost stops by temperature o3 Third probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of...

Page 4: ...do not use it did Digital inputs 1 alarm delay 0 to 255 it is the delay between the detection of an external event and the activation of the relative function i2P Digital input 2 polarity if d i 2 present oP CL oP activated by closing the contact CL activated by opening the contact i2F Digital input 2 configuration nu dor dEF AUS ES EAL bAL PAL FAn HdF onF LiG CC EMt nu not used dor door switch fu...

Page 5: ...ed to control the light output CHANGE CONFIGURATION ixF CC It is used to change the controller configuration MOTION SENSOR DETECTOR ixF EMt To use the X MOD motion sensor Please note that motion sensor can be connected only to the HOTKEY port so it needs digital input 2 properly configurated 14 INSTALLATION AND MOUNTING Instrument XR70CHC shall be mounted on vertical panel in a 29x71 mm hole and f...

Page 6: ...ized repairs changes or modifications could result in permanent damage to the equipment and void your warranty and your authority to operate this device under Part 15 of the FCC Rules NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful int...

Reviews: