1592033070 XR70CHC EN r1.0 2019.01.30 

                           XR70CHC 

3/6 

 

11.3.2

 

PROTECTED MENU 

1.

 

Select the parameter to modify 

5.

 

Press the 

SET

 key to display its current value 

6.

 

Use 

UP

 or 

DOWN

 to change its value 

7.

 

Press 

SET

 to store the new value and move to the following parameter 

 

To exit

: Press 

SET+

UP

 or wait for 15 sec without pressing any button. 

 

NOTE:  

1.

 

If there are no parameters into the User Level, after 3 sec 

the “nP” 

label will be displayed. Go to 

submenu Pr2 and follow the previous procedure. 

2.

 

The modified value will be stored even if the programming mode ends by timeout. 

3.

 

Modify the par. 

PSU

 (when into Protected Level) to change the current password 

11.3.3

 

MOVE PARAMETERS THROUGH LEVELS 

Each parameter present into the Protected Level can be moved into the User Level by pressing both 

SET+DOWN 

buttons. If a parameter is into the User Level, when visualized into the Protected Level it 

will have also the decimal point. 

11.4

 

KEYBOARD MANAGEMENT 

11.4.1

 

TEMPORARY LOCK 

1.

 

Keep both 

UP 

and 

DOWN 

buttons pressed for more than 3 sec. 

2.

 

The “

oFF

” label

 will be displayed and the keyboard will be locked. If any button is pressed more 

than 3 sec, 

the “

oFF

” message will be displayed.

 

11.4.2

 

TEMPORARY UNLOCK 

Keep both 

UP 

and 

DOWN 

buttons pressed together for more than 3 sec till the 

“on”

 

message will be 

displayed. 

11.4.3

 

ADVANCED LOCK FUNCTION 

It is possible to selectively lock the keyboard by using the following parameters: 

1.

 

brd

: select the kind of lock: 

a.

 

UnL

: all buttons unlocked 

b.

 

SEL

: buttons 

UP

DOWN

 and 

DEFROST

 are locked 

c.

 

ALL

: all keyboard is locked 

2.

 

tLC

: delay after power-on before activating the advanced lock function 

 

NOTE

: when advanced lock function is active, temporary lock and unlock functions are disabled. 

11.5

 

THE ON/OFF FUNCTION 

 

 

If 

onF = oFF

, the instrument will be switched off by pushing the 

ON/OFF

 button. The 

OFF

 

message  will  appear  on  the  display.  In  this  configuration  the  regulation  is 

disabled. To switch the instrument on, push again the 

ON/OFF

 button. 

 
WARNING: any load connected to the normally closed contacts of the relays is always supplied 
from the main voltage, even if the instrument is in standby mode.

 

12

 

PARAMETERS 

MENU LIST 

rEG 

Regulation: it includes all parameters related to main temperature regulation 

Prb 

Probe setup: it includes all parameters related to probe configuration 

diS 

Display: it includes all parameters related to the user interface 

dEF 

Defrost: it includes all parameters to control any defrost operation 

FAn 

Ventilators: it includes all parameters to control the ventilators 

AUS 

Auxiliary: it includes all parameters for auxiliary regulators 

ALr 

Alarms: it includes all parameters to set up the alarm conditions 

oUt 

Outputs: it includes all parameters to set up the digital outputs 

inP 

Inputs: it includes all parameters to set up the digital inputs 

ES 

Energy Saving: it includes all parameters to define the energy saving mode 

Cnt 

Counters: to see the counters values 

rtC 

Real Time Clock: it includes all parameters to set up the internal clock 

bLE 

Bluetooth: it includes all parameters to set up the Bluetooth communication 

E2 

EEPROM: it includes all parameters to set up the datalogger 

oth 

Other: it includes all parameters to set up the serial communication and the keyboard  

viS 

Visualization: it includes the read only parameters (probe values and FW info) 

REGULATION - rEG 

SEt 

Regulation Set Point: 

range from LS to US 

LS 

Minimum Set Point:

 (-100.0°C to SET; -148°F to SET) sets the minimum value for the  set 

point. 

US 

Maximum Set Point:

 (SET to 200.0°C; SET to 392°F) set the maximum value for set point. 

HY 

Differential in normal mode:

 (0.1 to 25.0°C; 1 to 45°F) differential for set point. Compressor 

Cut-IN is 

T > SET + HY

. Compressor Cut-OUT is 

T<=SET

HYE 

Differential  in  energy  saving  mode:

  (0.1  to  25.0°C;  1  to  45°F)  differential  for  set  point. 

Compressor Cut-IN is 

T > SET + HES + HYE

. Compressor Cut-OUT is 

T<= SET + HES

odS 

Outputs  delay  activation  after  power  on:

 (0  to  255  min)  this  function  is  enabled  after  the 

power-on of the instrument and delays output activations. 

AC 

Anti-short cycle delay:

 (0 to 50 min) minimum interval between a compressor stop and the 

following restart. 

rtr 

Percentage for regulation: 

100=P1 only; 0=P2 only

 

CCt 

Maximum duration for pull down:

 (0.0 to 23h50min, res. 10min) after elapsing this interval of 

time the super cooling function is immediately stopped 

CCS 

Differential for pull down:

 (-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the 

regulation  SETPOINT  is  moved  to 

SET+CCS 

(in  normal  mode)  or  to 

SET+HES+CCS

  (in 

energy saving mode)

 

oHt 

Overheating  before  activating  the  pull-down  function  (when  in  normal  mode): 

(1.0  to 

12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function. 

oHE 

Overheating before activating the pull-down function (when in energy saving mode): 

(1.0 

to  12.0°C;  1  to  21°F)  this  is  the  upper  threshold  limit  used  to  activate  the  super  cooling 
function. 

Con 

Compressor ON time with faulty probe:

 (0 to 255 min) time during which the compressor is 

active in case of faulty thermostat probe. With 

CY=0

 compressor is always OFF. 

CoF 

Compressor OFF time with faulty probe:

 (0 to 255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With 

Cn=0

 compressor is always active. 

PROBE SETUP - Prb 

PbC 

Probe selection:

 ntC; PtC; Pt1000 

ot 

Probe P1 calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the 

first probe. 

P2P 

Evaporator probe presence:

 

n

 = not present; 

Y

 = the defrost stops by temperature. 

oE 

Evaporator  probe  calibration:

  -12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust  any  possible 

offset of the third probe. 

P3P 

Third probe presence:

 

n

 = not present; 

Y

 = the defrost stops by temperature. 

o3 

Third probe calibration:

 -12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of 

the third probe. 

P4P 

Fourth probe presence:

 

n

 = not present; 

Y

 = the condenser temperature alarm is managed. 

o4 

Fourth probe calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of 

the condenser probe. 

DISPLAY - diS 

iCo 

Enabling icon visualisation:

 (n; Y) the icons can be hidden during normal functioning

 

CF 

Temperature measurement unit: 

(°C; °F) 

°C 

= Celsius; 

°F

 = Fahrenheit. 

rES 

Resolution (only for °C):

 (dE; in) 

dE

 = decimal; 

in

 = integer. 

Lod 

Probe displayed: 

(

P1; P2; P3; P4; SEt; dtr; USr

Px

=probe “x”; 

SEt

=set point; 

dtr

=do not 

use it; 

USr

=do not use it. 

dLY 

Temperature  visualization  delay:

  (0.0  to  20min00sec,  res.  10  sec)  when  the  temperature 

increases, the display is updated of 1°C or 1°F after this time. 

dtr 

Visualization percentage = F(P1;P2): 

(0 to 100)

 

with 

dtr=1

 the display will show this value 

VALUE=0.01*P1+0.99*P2 

DEFROST - dEF 

EdF 

Defrost mode:

 

in

=fixed intervals; 

rtC

=following real time clock 

 

tdF 

Defrost type: EL

=electrical heaters; 

in

=hot gas; 

ALt

=uses only for compressor stop defrost. 

dFP 

Probe  selection  for  defrost  control:

 

nP

=no  probe; 

P1

=thermostat  probe; 

P2

=evaporator 

probe; 

P3

=third probe (do not use it); 

P4

=Probe on Hot Key plug. 

dtE 

Defrost termination temperature for defrost control:

 (-55 to 50°C; -67 to 122°F) it sets the 

temperature measured by the evaporator probe (

dFP

), which causes the end of defrost.

 

idF 

Interval  between  two  consecutive  defrost  cycles:

  (0  to  255  hours)  determines  the  time 

interval between the beginnings of two defrosting cycles. 

MdF 

Maximum length for defrost:

 (0 to 255 min; 0 means no defrost) when 

P2P=n

 (no evaporator 

probe presence) it sets the defrost duration, when 

P2P=Y

 (defrost end based on  evaporator 

temperature) it sets the maximum length for defrost. 

dSd 

Start defrost delay: 

(0 to 255 min) delay in defrost activation.

 

StC 

Compressor stop time before starting any defrost: 

(0 to 900 sec) interval with compressor 

stopped before activating hot gas cycle 

dFd 

Display during defrost:

 (rt; it; SP; dF) 

rt

 = real temperature; 

it

 = start defrost temperature;  

SP

 = SET-POINT; 

dF

 

= label “

dF

”.

 

dAd 

Max delay for updating display after any defrost: 

(0 to 255 min) delay before updating the 

temperature on the display after finishing any defrost. 

Fdt 

Draining time: 

(0 to 255 min) 

 

Hon 

Drain heater enabled after draining time (Fdt):

 (0 to 255 min) the relative output will stay on 

after draining time. 

dPo 

First defrost after start-up: 

(n; Y) to enable defrost at power on.

 

Pd1 

Differential during any pre-defrost phase: 

(-12.0 to 12.0°C; -21 to 21°F) the regulation Set 

Point is changed to a temporary different value before any defrost 

Pd2 

Pre-defrost time: 

(0 to 120 min) interval with temporary Set Point before any defrost. 

dAF 

Defrost delay after freezing: 

(0.0 to 24h00min, res. 10 min) delay before activating a defrost. 

od1 

Automatic  defrost  (at  the  beginning  of  any  energy  saving  mode): 

(n;  Y) 

n

=function 

disabled; 

Y

=function enabled 

SYn 

Tipe of synchronized defrost:

 (nu; rnd) nu=not used; rnd=random defrost 

ndE 

Number  of  devices  connected  to  the  virtual  network  for  random  defrost  (valid  if 
Syd=rnd):

 (1 to 20) used to define how many devices will use the Random Defrost Function 

FAN - FAn 

FAP 

Probe  selection  for  evaporator  fan  management:  nP

=no  probe; 

P1

=thermostat  probe; 

P2

=evaporator probe; 

P3

=do not use it; 

P4

=Probe on Hot Key plug.

 

FSt

 

Evaporator  fan  stop  temperature: 

(-55  to  50°C;  -67  to  122°F)  setting  of  temperature, 

detected by evaporator probe. Over this value of temperature fans are always OFF. 

NOTE: it 

works only for the evaporator fan, NOT for the condenser fan.

 

HYF 

Differential for evaporator fan:

 (0.1 to 25.5°C; 1 to 45°F) differential for evaporator ventilator 

regulator 

FnC

 

Evaporator fan mode operation: 

(Cn; on; CY; oY)  

 

Cn 

= runs with the compressor, duty-cycle when  compressor is OFF (see 

FoF

,

  Fon

FF1 

and 

Fo1 

parameters) and OFF during defrost  

 

on 

= continuous mode, OFF during defrost 

 

CY 

= runs with the compressor, duty-cycle when  compressor is OFF (see 

FoF

,

  Fon

FF1 

and 

Fo1 

parameters) and ON during defrost 

 

oY 

= continuous mode, ON during defrost 

Fnd 

Fan delay after defrost: 

(0 to 255 min) delay before fan activation after any defrosts. 

FCt 

Differential of temperature for forced activation of fans 

Fon

 

Fan on time when the compressor is off: 

(0 to 255 min) used when energy saving status is 

not active. 

FoF

 

Fan off time when the compressor is off: 

(0 to 255 min) used when energy saving status is 

not active. 

Fo1

 

Fan on time with compressor off in Energy Saving mode: 

(0 to 255 min) used when energy 

saving status is active. 

FF1

 

Fan off time with compressor off in Energy Saving mode: 

(0 to 255 min) used when energy 

saving status is active. 

FAC 

Probe selection for  condenser fan management:  nP

=no probe; 

P1

=probe Pb1; 

P2

=probe 

Pb2; 

P3

=probe Pb3; 

P4

=probe Pb4 on Hot Key plug.

 

St2

 

Condenser  fan  stop  temperature: 

(-55  to  50°C;  -67  to  122°F)  setting  of  temperature, 

detected by evaporator probe. Over this value of temperature fans are always OFF. 

HY2 

Differential for condenser fan:

 (0.1 to 25.5°C; 1 to 45°F) differential for evaporator ventilator 

regulator 

FCC

 

Condenser fan mode operation: 

(Cn; on; CY; oY)  

 

Cn 

= runs with the compressor and OFF during defrost  

 

on 

= continuous mode, OFF during defrost 

 

CY 

= runs with the compressor and ON during defrost 

 

oY 

= continuous mode, ON during defrost 

Summary of Contents for Dixell XR70CHC

Page 1: ...NERGY SAVING ALGORITHM The energy saving status will be always saved in the internal memory to resume previous operation if a power failure occurs It needs the presence of a door switch to work for example i1F dor 4 2 1 PARAMETER INVOLVED i1F or i2F set as door input to monitor the appliance usage StE interval to change from normal to energy saving mode EtS interval to change from energy saving to...

Page 2: ...ions related to par UPC and UP2 if available DOWN In programming mode it browses the parameter codes or decreases the displayed value Other functions related to the par dnC and dn2 if available ONOFF Keep it pressed for 3 sec to switch on and off the device KEYS COMBINATION To lock or unlock the keyboard To enter in programming mode To return to room temperature display ICON MODE MEANING On Compre...

Page 3: ...t any possible offset of the first probe P2P Evaporator probe presence n not present Y the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of the third probe P3P Third probe presence n not present Y the defrost stops by temperature o3 Third probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust any possible offset of...

Page 4: ...do not use it did Digital inputs 1 alarm delay 0 to 255 it is the delay between the detection of an external event and the activation of the relative function i2P Digital input 2 polarity if d i 2 present oP CL oP activated by closing the contact CL activated by opening the contact i2F Digital input 2 configuration nu dor dEF AUS ES EAL bAL PAL FAn HdF onF LiG CC EMt nu not used dor door switch fu...

Page 5: ...ed to control the light output CHANGE CONFIGURATION ixF CC It is used to change the controller configuration MOTION SENSOR DETECTOR ixF EMt To use the X MOD motion sensor Please note that motion sensor can be connected only to the HOTKEY port so it needs digital input 2 properly configurated 14 INSTALLATION AND MOUNTING Instrument XR70CHC shall be mounted on vertical panel in a 29x71 mm hole and f...

Page 6: ...ized repairs changes or modifications could result in permanent damage to the equipment and void your warranty and your authority to operate this device under Part 15 of the FCC Rules NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful int...

Reviews: