1592023130 XM670K_XM679K GB r4.2 26.06.2017.docx 

XM670K - XM679K  

          7/10 

 

SOA  Fixed value for analog output: 

(0 ÷ 100%) value for the output if 

trA=UAL

;

 

SdP 

Default value for Dew point

: (-55,0÷50,0°C; -67÷122°F) default value of dew point used when 

there is no supervising system (XWEB5000). Used only when 

trA=AC

ASr 

Dew-point offset (trA=AC) / Differential for modulating fan regulation (trA=rEG)

: (-25.5°C ÷ 

25.5°C) (-45°F ÷ 45°F); 

PbA 

Differential for anti-sweat heaters: 

(0.1°C ÷ 25.5°C) (1°F ÷ 45°F) 

AMi 

Minimum value for analog output: 

(0÷AMA)  

AMA  Maximum value for analog output: 

(Ami ÷ 100) 

AMt 

Anti-sweat  heaters  cycle  period (trA=AC)/  Time  with  fan  at  maximum  speed  (trA=rEG): 

(0÷255 s) when the fan starts, during this time the fan is at maximum speed;

 

ALARMS 
rAL 

Probe for temperature alarm:

 (nP - P1 - P2 - P3 - P4 - P5 

 tEr) it selects the probe used to 

signal alarm temperature

 

ALC 

Temperature alarm configuration: rE

 = High and Low alarms related to Set Point; 

Ab

 = High 

and low alarms related to the absolute temperature. 

ALU 

High temperature alarm setting:

 (ALC= rE, 0 

 

50°C or 90°F / ALC= Ab, ALL 

 150°C or 302°F) 

when this temperature is reached and after the 

ALd

 delay time the 

HA

 alarm is enabled. 

ALL 

Low temperature alarm setting: 

(ALC = rE , 0 

 50 °C or 90°F / ALC = Ab , - 55°C or - 67°F 

 

ALU) when this temperature is reached and after the 

ALd

 delay time, the 

LA

 alarm is enabled. 

AHy 

Differential for temperature alarm

: (0.1°C ÷ 25.5°C / 1°F ÷ 45°F) Intervention differential for 

recovery of temperature alarm; 

ALd 

Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition 

and the corresponding alarm signalling. 

dLU 

High temperature alarm (defrost probe):

 (ALC= rE, 0 

 

50°C or 90°F / ALC= Ab, ALL 

 150°C 

or  302°F)  when  this  temperature  is  reached  and  after  the 

ddA

  delay  time  the 

HAd

  alarm  is 

enabled. 

dLL 

Low temperature alarm (defrost probe): 

(ALC = rE , 0 

 50 °C or 90°F / ALC = Ab , - 55°C or 

- 67°F 

 ALU) when this temperature is reached and after the 

ALd

 delay time, the 

LAd

 alarm is 

enabled. 

dAH 

Differential for temperature alarm (defrost probe):

 (0.1°C ÷ 25.5°C / 1°F ÷ 45°F) Intervention 

differential for recovery of temperature alarm; 

ddA 

Temperature alarm delay (defrost probe): 

(0÷255 min) time interval between the detection of 

an alarm condition and the corresponding alarm signalling. 

FLU 

High temperature alarm (defrost probe):

 (ALC= rE, 0 

 

50°C or 90°F / ALC= Ab, ALL 

 150°C 

or  302°F)  when  this  temperature  is  reached  and  after  the 

FAd

  delay  time  the 

HAF

  alarm  is 

enabled. 

FLL 

Low temperature alarm (defrost probe):

 (ALC = rE , 0 

 50 °C or 90°F / ALC = Ab , - 55°C or 

- 67°F 

 ALU) when this temperature is reached and after the 

FAd

 delay time, the 

LAF

 alarm is 

enabled. 

FAH 

Differential for temperature alarm (defrost probe): 

(0.1°C ÷ 25.5°C / 1°F ÷ 45°F) Intervention 

differential for recovery of temperature alarm; 

FAd 

Temperature alarm delay (defrost probe): 

(0÷255 min) time interval between the detection of 

an alarm condition and the corresponding alarm signalling. 

dAO   Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection 

of the temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA   Alarm  delay  at  the  end of  defrost: 

(0

255  min)  Time  interval  between  the  detection  of  the 

temperature alarm condition at the end of defrost and the alarm signalling. 

dot 

Temperature alarm exclusion after door open:  

Sti 

Stop regulation interval (Only XM679K): (0.0÷24.0

 

hours: tens of minutes)

  after regulating 

continuously for 

Sti

 time, the valve closes for 

Std

 time in order to prevent  ice creation. 

Std 

Stop duration (Only XM679K): 

(0÷60 min.) it defines stop regulation time after 

Sti. 

 

nMS  Maximum number of regulation pauses 

(nu, 1÷255)

 

OPTIONAL OUTPUT (AnOUT) if present 

 

OA6 

Sixth  relay  configuration  (CPr-dEF-Fan-ALr-LiG-AUS-db-OnF):  CPr= 

relay  works  as  a 

compressor or solenoid valve relay; 

dEF=

 relay works as defrost relay; 

Fan=

 relay works as a 

Fan relay; 

ALr=

 activation with alarm conditions; 

LiG=

 light activation; 

AUS=

 auxiliary relay, it 

can be switched ON/OFF also by key; 

db=

 dead band regulation (

not compatible with CrE=y

); 

OnF=

 ON/OFF functioning; 

CoM  Type of functioning modulating output:  

 

For models with PWM / O.C. output 

 PM5= 

PWM 50Hz; 

PM6=

 PWM 60Hz; 

OA7=

 not set it;

 

 

For models with 4÷20mA / 0÷10V output 

 Cur= 

4÷20mA

 

current output; 

tEn=

 

0÷10V voltage output; 

 

AOP  Alarm relay polarity: cL= 

normally closed; 

oP=

 normally opened; 

iAU 

Auxiliary output is unrelated to ON/OFF device status: n= 

if the instrument is switched off 

also the auxiliary output is switched off; 

Y=

 the auxiliary output state is unrelated to the ON/OFF 

device status 

 

 

 

DIGITAL INPUTS 

 

i1P 

Digital input 1 polarity: 

(cL 

 oP)

 CL

: the digital input is activated by closing the contact;

 OP

the digital input is activated by opening the contact.

 

i1F 

Digital input 1 function: 

(EAL 

 bAL 

 PAL 

 dor 

 dEF 

 AUS 

 LiG 

 OnF 

 Htr 

 FHU 

 ES 

 Hdy) 

EAL= 

external alarm; 

bAL=

 serious external alarm; 

PAL= 

pressure switch activation; 

dor=

 

door open; 

dEF= 

defrost activation; 

AUS= 

auxiliary activation; 

LiG=

 light activation; 

OnF= 

switch 

on/off the instrument; 

Htr= 

change type of action ; 

FHU=

 not used; 

ES=

 activate energy saving; 

Hdy=

 activate holiday function; 

d1d  

Time interval/delay for digital input alarm: 

(0

255 min.) Time interval to calculate the number 

of the pressure switch  activation when  i1F=

PAL

. If  I1F=

EAL

 or 

bAL

 

(external  alarms),  “

d1d

” 

parameter  defines  the  time  delay  between  the  detection  and  the  successive  signalling  of  the 

alarm. If 

i1F=dor

 this is the delay to activate door open alarm 

i2P 

Digital input 2 polarity: 

(cL 

 oP) 

CL

 : the digital input is activated by closing the contact;

 OP

the digital input is activated by opening the contact.

 

i2F 

Digital input 2 function: 

(EAL 

 bAL 

 PAL 

 dor 

 dEF 

 AUS 

 LiG 

 OnF 

 Htr 

 FHU 

 ES 

 Hdy) 

EAL= 

external alarm; 

bAL=

 serious external alarm; 

PAL= 

pressure switch activation; 

dor=

 

door open; 

dEF= 

defrost activation; 

AUS= 

auxiliary activation; 

LiG=

 light activation; 

OnF= 

switch 

on/off the instrument; 

Htr= 

change type of action ; 

FHU=

 not used; 

ES=

 activate energy saving; 

Hdy=

 activate holiday function; 

d2d  

Time interval/delay for digital input alarm: 

(0

255 min.) Time interval to calculate the number 

of the pressure switch  activation when i2F=

PAL

. If  I2F=

EAL

 or 

bAL

 

(external  alarms),  “

d2d

” 

parameter  defines  the  time  delay  between  the  detection  and  the  successive  signalling  of  the 

alarm. If 

i2F=dor

 this is the delay to activate door open alarm 

i3P 

Digital input 3 polarity: 

(cL 

 oP) 

CL

 : the digital input is activated by closing the contact;

 OP

the digital input is activated by opening the contact.

 

i3F 

Digital input 3 function: 

(EAL 

 bAL 

 PAL 

 dor 

 dEF 

 AUS 

 LiG 

 OnF 

 Htr 

 FHU 

 ES 

 Hdy) 

EAL= 

external alarm; 

bAL=

 serious external alarm; 

PAL= 

pressure switch activation; 

dor=

 

door open; 

dEF= 

defrost activation; 

AUS= 

auxiliary activation; 

LiG=

 light activation; 

OnF= 

switch 

on/off the instrument; 

Htr= 

change type of action ; 

FHU=

 not used; 

ES=

 activate energy saving; 

Hdy=

 activate holiday function; 

d3d  

Time interval/delay for digital input alarm: 

(0

255 min.) Time interval to calculate the number 

of  the  pressure  switch  activation  when  i3F=

PAL

.  If  i3F=

EAL

  or 

bAL

 

(external  alarms),  “

d3d

” 

parameter  defines  the  time  delay  between  the  detection  and  the  successive  signalling  of  the 

alarm. If 

i3F=dor

 this is the delay to activate door open alarm 

nPS 

Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

d#d

” 

interval, before signalling the alarm event (I2F= PAL). 

If the nPS activation in the did time is 

reached, switch off and on the instrument to restart normal regulation.

 

odc 

Compressor  and  fan  status  when  open  door:

   

no

  =  normal; 

Fan

  =  Fan  OFF; 

CPr 

Compressor OFF; 

F_C

 = Compressor and fan OFF.  

rrd 

Outputs restart after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm;  

RTC SUBMENU (if present) 

 

CbP 

Clock Presence 

(n÷y): it permits to disable or enable the clock; 

Hur 

Current hour 

(0 ÷ 23 h) 

Min 

Current minute

 (0 ÷ 59min) 

dAY 

Current day

 (Sun ÷ SAt) 

Hd1 

First weekly holiday 

(Sun ÷ nu) Set the first day of the week which follows the holiday times. 

Hd2 

Second weekly holiday 

(Sun ÷ nu) Set the second day of the week which follows the holiday 

times. 

Hd3 

Third weekly holiday 

(Sun ÷ nu) Set the third day of the week which follows the holiday times. 

ILE 

Energy Saving cycle start during workdays

: (0 ÷ 23h 50 min.) During the Energy Saving cycle 

the set point is increased by the value in HES so that the operation set point is SET + HES.  

dLE 

Energy  Saving  cycle  length  during  workdays

:  (0  ÷  24h  00  min.)  Sets  the  duration  of  the 

Energy Saving cycle on workdays.  

ISE 

Energy Saving cycle start on holidays

. (0 ÷ 23h 50 min.) 

dSE 

Energy Saving cycle length on holidays

 (0 ÷ 24h 00 min.) 

HES 

Temperature  increase  during  the  Energy  Saving  cycle 

(-30÷30°C  /  -54÷54°F)  sets  the 

increasing value of the set point during the Energy Saving cycle.  

Ld1÷Ld6  Workday  defrost  start

  (0  ÷  23h  50  min.)  These  parameters  set  the  beginning  of  the  6 

programmable defrost cycles during workdays. Ex. When 

Ld2

 = 12.4 the second defrost starts at 

12.40 during workdays.  

Sd1÷Sd6  Holiday  defrost  start

  (0  ÷  23h  50  min.)  These  parameters  set  the  beginning  of  the  6 

programmable defrost cycles on holidays. Ex. When 

Sd2

 = 3.4 the second defrost starts at 3.40 

on holidays.  

 

ENERGY SAVING 

 

ESP 

Energy saving probe selection:

 (nP - P1 - P2 - P3 - P4 - P5 

 tEr).

 

HES 

Temperature  increase  during  the  Energy  Saving  cycle  :

  (-30÷30°C  /  -54÷54°F)  sets  the 

increasing value of the set point during the Energy Saving cycle. 

PEL 

Energy saving activation when light is switched off: 

(n÷Y) n= function disabled; Y= energy 

saving is actived when the light  is switched off and vice versa; 

 

LAN MANAGEMENT 

 

LMd 

Desfrost synchronisation: y

= the section send a command to start defrost to oher controllers, 

n

= the section don’t send a global defrost command

 

dEM  Type of end defrost: n= 

the of the LAN defrost are indipendent; 

y=

 the end of the defrost are 

synchronisated; 

LSP 

L.A.N. set-point  synchronisation

y

= the section set-point, when modified, is updated to the 

same value on all the other sections; 

n

= the set-point value is modified only in the local section 

LdS 

L.A.N. display  synchronisation

y

= the value displayed by the section is sent to all the other 

sections; 

n

= the set-point value is modified only in the local section 

LOF 

L.A.N. On/Off synchronisation

  this parameter states if the On/Off command of the section will 

act on all the other ones too: 

y

= the On/Off command is sent to all the other sections; 

n

= the 

On/Off command acts only in the local section 

LLi 

L.A.N. light  synchronisation

 this parameter states if the light  command of the section will act 

on  all the  other  ones too: 

y

= the light command is sent to all the  other sections; 

n

= the light 

command acts only in the local section 

LAU 

L.A.N. AUX output  synchronisation

 this parameter states if the AUX command of the section 

will act on all the other ones too: 

y

= the light command is sent to all the other sections; 

n

= the 

light command acts only in the local section 

LES 

L.A.N. energy saving  synchronisation

 this parameter states if the energy saving command of 

the section will act on all the other ones too: 

y

= the Energy Saving command is sent to all the 

other sections; 

n

= the Energy Saving command acts only in the local section 

LSd 

Remote probe display:

 this parameter states if the section has to display the local probe value 

or the value coming from another section: 

y

= the displayed value is the one coming from another 

section (which has parameter LdS = y); 

n

= the displayed value is the local probe one. 

LPP 

Remote pressure probe: n= 

the value of pressure probe is read from local probe; 

Y=

 the value 

of pressure probe is sent via LAN; 

StM 

Solenoid activation via LAN: n= 

not used; 

Y=

 a generic cooling requests from LAN activate  the 

solenoid valve connected to compressor relay; 

 

PROBE CONFIGURATION 

 

P1C 

Probe 1 configuration: 

(nP 

 Ptc 

 ntc 

 PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc=

 NTC; 

PtM=

 

Pt1000;

 

Ot 

Probe 1 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the thermostat 

probe. 

P2C 

Probe 2 configuration: 

(nP 

 Ptc 

 ntc 

 PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc = 

NTC; 

PtM=

 

Pt1000; 

OE   

Probe 2 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offsets of the evaporator 

probe. 

P3C 

Probe 3 configuration: (

nP 

 Ptc 

 ntc 

 PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc = 

NTC; 

PtM=

 

Pt1000;

 

o3 

Probe 3 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the probe 3. 

P4C 

Probe 4 configuration: (

nP 

 Ptc 

 ntc 

 PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc = 

NTC; 

PtM=

 

Pt1000; 

o4 

Probe 4 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the probe 4. 

P5C 

Probe 5 configuration: 

(nP 

 Ptc 

 ntc 

 PtM 

 420 

 5Vr) 

nP=

 not present; 

PtM=

 Pt1000; 

420=

 

4÷ 20mA; 

5Vr=

 0÷5V ratiometric; 

(Only XM679K)

 

o5 

Probe 5 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the probe 5. 

(Only XM679K)

 

P6C 

Probe 6 configuration: (

nP 

 Ptc 

 ntc 

 PtM) 

nP=

 not present; 

PtC=

 Ptc;  

ntc = 

NTC; 

PtM=

 

Pt1000; 

(Only XM679K)

 

o6 

Probe 6 calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the probe 6. 

(Only XM679K)

 

 

SERVICE 

 READ ONLY 

 

CLt 

Coling  time  percentage: 

it

 

shows  the  effective  cooling  time  calculated  by  XM600  during 

regulation;

 

tMd 

Time to next defrost: 

it

 

shows time before the next defrost if interval defrost is selected;

 

LSn 

L.A.N. section number 

 (1 ÷ 8)  Shows the number of sections available in the L.A.N. 

Lan 

L.A.N.  serial  address 

  (1  ÷  LSn)    Identifies  the  instrument  address  inside  local  network  of 

multiplexed cabinet controller. 

Adr  

RS485 serial address 

(1÷247)

Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

Summary of Contents for Dixell XM670K

Page 1: ...nstruments are equipped with the HOTKEY connector that permits to be programmed in a simple way Direct serial output RS485 ModBUS RTU compatible permits a simple XWEB interfacing RTC are available as options The HOTKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with D...

Page 2: ... to 10Vdc Use CABCJ15 to perform the connections It s located near the terminal 39 on a 2 pin connector It s possible to use the output to control anti sweat heaters through a chopped phase controller XRPW500 500watt or family XV D or XV K 6 QUICK REFERENCE GUIDE HOW TO RUN THE SELF ADAPTIVE REGULATION IN 4 STEPS 1 After wiring the XM679K set the proper gas via Fty parameter Pre set gas is R404A 2...

Page 3: ...c set point if the functions are enabled Exit Pressed together or wait the timeout of about 60 sec 10 MENU FOR MULTIMASTER FUNCTION SEC The function section SEC is enabled when icon is lit It allows entering in the remote programming mode from a keyboard not physically connected to the board through the LAN functionality Action Button or display Notes Enter menu Press UP arrow for about 3 sec the ...

Page 4: ...of regulation parameter SFd percentage and SFd time Forced opening of the valve after defrost parameter oPd percentage and Pdd time 12 4 MINIMUM STABLE SUPERHEAT SEARCH AMS YES ATU YES With the parameter ATU the minimum stable superheat search function is enabled With ATU yES controllers start searching the mimimum stable value for the SH the minimum admitted value in any case is LSH 2 C 4 F Pleas...

Page 5: ...ing to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low thermal exchange is detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtc the maximum duration of defrost is obtained ...

Page 6: ...pressure exceeds maximum operating pressure value instrument signals situation with MOP alarm related to PrM parameter LOP Lowest Operating Pressure threshold PA4 P20 bar psi kPA 10 if the suction pressure comes down to this value a low pressure alarm is signalled with LOP alarm related to PrM parameter dML delta MOP LOP 0 100 when a MOP alarm occurs valve will close of the dML percentage every cy...

Page 7: ...ion dor door open dEF defrost activation AUS auxiliary activation LiG light activation OnF switch on off the instrument Htr change type of action FHU not used ES activate energy saving Hdy activate holiday function d3d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i3F PAL If i3F EAL or bAL external alarms d3d para...

Page 8: ... for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 18 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KEY 1 When the XM unit is ON insert the Hot key and push UP key 2 The UPLOAD begins the uPL message is blinking 3 Remove the Hot Key At the end of the data transfer phase the instrument displays the foll...

Page 9: ...5 F Fod 0 Pr1 Fan activation time after defrost without compressor 0 255 min Fon 0 Pr1 Fan ON time 0 15 min FoF 0 Pr1 Fan OFF time 0 15 min trA UAL Pr2 Kind of regulation for modulating output UAL 0 rEG 1 AC 2 SOA 80 Pr2 Fixed speed for fan AMi AMA SdP 30 0 Pr2 Default Dew Point value 55 0 C 50 0 C 67 F 122 F ASr 1 0 Pr2 Differential for fan offset for anti sweat heater 25 5 C 25 5 C 45 F 45 F PbA...

Page 10: ...ving ESP P1 Pr1 Energy saving probe selection nP 0 P1 1 P2 2 P3 3 P4 4 P5 5 tEr 6 HES 0 0 Pr1 Temperature increasing during Energy Saving 30 0 C 30 0 C 54 F 54 F PEL n Pr1 Energy saving activation when Light switched off n 0 Y 1 L A N Management LMd y Pr2 Defrost Synchronisation n 0 Y 1 dEM y Pr2 Defrost end Synchronisation n 0 Y 1 LSP n Pr2 SET POINT Synchronisation n 0 Y 1 LdS n Pr2 Display Sync...

Reviews: