background image

 

 

1592023130 XM670K_XM679K GB r4.2 26.06.2017.docx 

XM670K - XM679K  

          2/10 

 

5.7

 

SENSORS FOR SUPERHEAT CONTROL 

 ONLY FOR XM679K 

 

Temperature probe:

 

Pb6

 terminals [

19

] - [

20

] without any polarity. 

 

Select the kind of sensor with 

P6C 

parameter. 

 

Pressure transducer: Pb5 

terminals: 

[

21

] = input of the signal; [

22

] = Power Supply for 4to20mA transducer; 

[

20

]  =  GND;  [

23

]  =  +5Vdc  power  supply  for  ratiometric  pressure 

transducer. 

 

 

Select the configuration of the transducer with parameter 

P5C

5.8

 

HOW TO USE ONLY ONE PRESSURE TRANSDUCER ON MULTIPLEXED APPLICATIONS 

 

 

 

A working LAN connection is required (green LED lit on all XM670-XM679K boards of the same LAN). Connect 

and  configure  a  pressure  transducer  only  on 

one

  XM670-XM679K  of  the  network.  Afterwards,  the  value  of 

pressure read by the unique transducer connected will be available to each device connected to the same LAN. 

 

By pressing 

UP ARROW

 button, the user will be able to enter a fast selection menu and to read the value of the 

following parameters: 

 

dPP 

= measured pressure (only on master device); 

dP5 

= value of temperature obtained from pressure

 temperature conversion; 

rPP

 = pressure value read from remote location (only for slave devices). 

 

Examples of error messages: 

 

dPP = Err

 

 the local transducer read a wrong value, the pressure is out of the bounds of the pressure 

transducer or the 

P5C

 parameter is wrong. Check all these options and eventually change the transducer; 

 

rPF

 

 the remote pressure transducer is on error situation. Check the status of the onboard GREEN LED: if 

this LED is OFF the LAN is not working, otherwise check the remote transducer. 

 

LAST CHECKS ABOUT SUPERHEAT 

On the fast access menu: 

dPP 

is the value read by the pressure gauge; 

dP6 

is the value read by the temperature probe, temperature of the gas on the outlet section of the evaporator; 

SH

 is the value of the superheat. The 

nA

 or 

Err

 messages mean that the superheat has no sense in that 

moment and its value is not available. 

 

5.9

 

HOW TO CONNECT MONITORING SYSTEM 

 

1)

 

Terminals [

36

] [-] and [

37

] [+]. 

2)

 

Use shielded twisted cable. For example Belden® 

8762 o 8772 or cat 5 cables. 

3)

 

Maximum distance 1Km. 

4)

 

Don’t connect the shield to the earth or to GND 

terminals of the device, avoid accidental contacts by 

using insulating tape. 

 

Only one device for each LAN has to be connected to the RS485 connection. 

 

 

 

The 

Adr

 parameter is the number to identify each electronic board. 

Address duplication is not permitted

, in 

this case the synchronized defrost and the communication with monitoring system is not guaranteed (the 

Adr

 is 

also the ModBUS address). 

5.10

 

DIGITAL INPUTS 

 

1)

 

The terminals from [

30

] to [

33

] are all free of voltage; 

2)

 

Use shielded cable for distance higher than one 

meter; 

 

For each input, has to be configured: the polarity of 

activation, the function of the input and the delay of 

signaling.  

 

The parameters to perform this configuration are 

i1P

i1F

i1d

 respectively for polarity, functioning and delay. The 

i1P

 can be: 

cL

 = active when closed; 

oP

 = active when opened. The 

i1F

 parameter can be: 

EAL

 = external alarm, 

bAL

 = serious lock alarm, 

PAL

 = pressure switch alarm, 

dor

 = door switch, 

dEF

 = external defrost, 

AUS

 = auxiliary 

activation  command, 

LiG

  =  light  activation, 

OnF

  =  board  On/OFF, 

FHU

 

=  don’t  use  this  configuration, 

ES

  = 

day/night, 

HdY

 

= don’t use this configuration. Then there is 

i1d

 parameter for delay of activation. For the others 

digital inputs there are a set of the same parameters: 

i2P

i2F

i2d

i3P

i3F

i3d

5.11

 

ANALOG OUTPUT 

 

 

Selectable between 4 to 20mA and  

0 to 10Vdc. 

 

Use CABCJ15 to perform the connections 

 

It’s located near the terminal [

39

] on a 2-

pin connector. It’s possible to

 use the output to control anti-sweat heaters 

through a chopped phase controller XRPW500 (500watt) or family XV...D or XV...K. 

 

6.

 

QUICK  REFERENCE  GUIDE:  HOW  TO  RUN  THE  SELF  ADAPTIVE 

REGULATION IN 4 STEPS. 

1.

 

After wiring the XM679K, 

set the proper gas

 via 

Fty

 parameter. Pre-set gas is R404A. 

 

2.

 

Configure the probes

:  

Regulation and evaporator

 probe are preset as NTC. If another kind of sensors is used, set it via 

P1c and P2c parameters.  

Superheat evaporator outlet probe

 is pre-set as Pt1000, if another kind of sensor is used, set it 

via P6c parameter.  

The 

PP11

 (-0.5÷11bar) is pre-set as 

pressure probe. 

It operates at relative pressure (

Pru

 = rE). 

If you’re using a ratiometric transducer, set 

P5c = 0-5

, then use parameters 

PA4

 and 

P20

 to set 

the range 

NOTE: 

check the pressure gauge reading with the value of dPP, press the 

UP

 arrow once to enter 

the 

Fast Access Menu

. If ok, proceed; otherwise solve the situation before proceeding acting on 

par. Pru, PA4 and P20. 

 

3.

 

Set the parameters for self adaptive regulation of superheat 

NOTE: 

the parameters

 Pb 

(regulation band) and 

Int 

(integral time) are automatically calculated by the 

controller 

 

Set 

CrE = no, 

this disable the continuos regulation of the temperature. Default is CrE = no. 

Set 

SSH

superheating setpoint

: a value between 4 and 8 is acceptable. Default is SSH=8 

Set 

AMS = y

 to start the 

self adaptive regulation

. Default is AMS = y 

Set 

ATU = y

 to start the search of the 

lowest stable superheat

. Default is ATU = y. This function 

reduces automatically the setpoint in order to optimize the use of the evaporator, keeping, at the 

same time, the superheating regulation stable. The minimum allowed SH set point is LSH+2°C. 

Set 

LSH

low superheating limit

: a value between 2-4 is acceptable. Default is LSH = 3 

Set 

SUb, pressure filter

: Default is SUb = 10. The value can be increased up to 20 in case of too 

fast response of the pressure variations. 

 

4.

 

Set the parameters for the temperature regulation

 

Set the temperature 

setpoint

. Default is -5°C 

Set 

the differential HY

: Default is 2°C.  

If the 

capacity of the valve

 is higher than requested, it can be reduced by the par. 

MNF

  (Default 

is 100). A proper setting of MnF will reduce the time that the algorithm takes to reach the stability. 

MNF 

value doesn’t affect the band witdh

 

7.

 

USER INTERFACE 

 

 

7.1

 

ICONS 

Cooling output 

 

     

 

With  icon  ON  the  output  is 

active, while with blinking icon 

there is a delay. 

 

MEASUREMENT UNIT 
°C,  Bar 

and

 

  (time)

 

are

 

ON  depending  on  the 

selection. 

Light  

   

 

 

 

 Fan 

Defrost  

 

 

AUX

 

  Auxiliary relay 

Energy saving  

 

 

 

  Multimaster Enabled 

Generic alarm 

 

 

 

  Clock / time 

DURING PROGRAMMING

:  blink the measurement units of temperature and pressure 

7.2

 

KEYBOARD COMMANDS 

Single commands: 

LIGHT relay 

Press light button.

 

AUX relay 

Press down arrow.

 

Manual defrost 

Press and hold for 3 sec the defrost button

 

ON/OFF 

Press for 3 sec the 

ON/OFF

 button (if the function is enabled).

 

Energy Saving 

Press for 3 sec the 

ON/OFF

 button (if the function is enabled).

 

 

Double commands: 

 

Press and hold for about 3 sec to lock (

Pon

) or unlock (

PoF

) the keyboard. 

 

Pressed together to exit from programming mode or from menu; on submenus 

rtC

 and 

EEV

 

this combination allow to come back to previous level. 

 

Pressed together for 3 sec allow to access to first level of programming mode. 

7.3

 

HOW TO MODIFY THE SET POINT FOR AIR TEMPERATURE REGULATION 

The thermostat set point is the value that will be used to regulate the air temperature. The regulation output is 

controlled by the electronic valve or by the relay. 

 

BEGIN 

 

Press SET button for 3 sec, the measurement units will blink together.  

Summary of Contents for Dixell XM670K

Page 1: ...nstruments are equipped with the HOTKEY connector that permits to be programmed in a simple way Direct serial output RS485 ModBUS RTU compatible permits a simple XWEB interfacing RTC are available as options The HOTKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with D...

Page 2: ... to 10Vdc Use CABCJ15 to perform the connections It s located near the terminal 39 on a 2 pin connector It s possible to use the output to control anti sweat heaters through a chopped phase controller XRPW500 500watt or family XV D or XV K 6 QUICK REFERENCE GUIDE HOW TO RUN THE SELF ADAPTIVE REGULATION IN 4 STEPS 1 After wiring the XM679K set the proper gas via Fty parameter Pre set gas is R404A 2...

Page 3: ...c set point if the functions are enabled Exit Pressed together or wait the timeout of about 60 sec 10 MENU FOR MULTIMASTER FUNCTION SEC The function section SEC is enabled when icon is lit It allows entering in the remote programming mode from a keyboard not physically connected to the board through the LAN functionality Action Button or display Notes Enter menu Press UP arrow for about 3 sec the ...

Page 4: ...of regulation parameter SFd percentage and SFd time Forced opening of the valve after defrost parameter oPd percentage and Pdd time 12 4 MINIMUM STABLE SUPERHEAT SEARCH AMS YES ATU YES With the parameter ATU the minimum stable superheat search function is enabled With ATU yES controllers start searching the mimimum stable value for the SH the minimum admitted value in any case is LSH 2 C 4 F Pleas...

Page 5: ...ing to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low thermal exchange is detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtc the maximum duration of defrost is obtained ...

Page 6: ...pressure exceeds maximum operating pressure value instrument signals situation with MOP alarm related to PrM parameter LOP Lowest Operating Pressure threshold PA4 P20 bar psi kPA 10 if the suction pressure comes down to this value a low pressure alarm is signalled with LOP alarm related to PrM parameter dML delta MOP LOP 0 100 when a MOP alarm occurs valve will close of the dML percentage every cy...

Page 7: ...ion dor door open dEF defrost activation AUS auxiliary activation LiG light activation OnF switch on off the instrument Htr change type of action FHU not used ES activate energy saving Hdy activate holiday function d3d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i3F PAL If i3F EAL or bAL external alarms d3d para...

Page 8: ... for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 18 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KEY 1 When the XM unit is ON insert the Hot key and push UP key 2 The UPLOAD begins the uPL message is blinking 3 Remove the Hot Key At the end of the data transfer phase the instrument displays the foll...

Page 9: ...5 F Fod 0 Pr1 Fan activation time after defrost without compressor 0 255 min Fon 0 Pr1 Fan ON time 0 15 min FoF 0 Pr1 Fan OFF time 0 15 min trA UAL Pr2 Kind of regulation for modulating output UAL 0 rEG 1 AC 2 SOA 80 Pr2 Fixed speed for fan AMi AMA SdP 30 0 Pr2 Default Dew Point value 55 0 C 50 0 C 67 F 122 F ASr 1 0 Pr2 Differential for fan offset for anti sweat heater 25 5 C 25 5 C 45 F 45 F PbA...

Page 10: ...ving ESP P1 Pr1 Energy saving probe selection nP 0 P1 1 P2 2 P3 3 P4 4 P5 5 tEr 6 HES 0 0 Pr1 Temperature increasing during Energy Saving 30 0 C 30 0 C 54 F 54 F PEL n Pr1 Energy saving activation when Light switched off n 0 Y 1 L A N Management LMd y Pr2 Defrost Synchronisation n 0 Y 1 dEM y Pr2 Defrost end Synchronisation n 0 Y 1 LSP n Pr2 SET POINT Synchronisation n 0 Y 1 LdS n Pr2 Display Sync...

Reviews: