1592023130 XM670K_XM679K GB r4.2 26.06.2017.docx 

XM670K - XM679K  

          3/10 

 

Value 

modification 

 or 

 

With the arrows it’s possible to change the value within the LS and US 

parameters value. 

EXIT 

 

By pressing SET it is possible to confirm the value that will blink for 

about 2 sec. 

 

In any case, it is possible to wait for about 10 sec to exit. In order to show the air temperature set is sufficient to 

press and release the SET button, the value is displayed for about 60 sec.

KEY COMBINATIONS 

 

8.

 

HOW TO PROGRAM THE PARAMETERS (PR1 AND PR2) 

The device provide 2 programming levels: 

Pr1

 with direct access and 

Pr2

 protected with a password (intended 

for experts). 

 

ACCESS to 

Pr1 

 

Press and hold for about 3 sec to have access to the first 

programming level (

Pr1

).  

Select item 

 or 

 

Select the parameter or submenu using the arrows. 

Show value

 

 

Press 

SET 

button. 

Modify 

 or 

 

Use the arrows to modify the value. 

Confirm and 

store 

 

Press 

SET 

key: the value will blink for 3 sec, and then the display 

will show the next parameter. 

EXIT 

 

Instantaneous exit from the programming mode, otherwise wait for 

about 10 sec (without press any button). 

8.1

 

HOW TO HAVE ACCESS T

O “PR2”

 

To enter 

Pr2

 programming menu: 

1.

 

Access to a 

Pr1

 menu by pressing both 

SET+DOWN 

keys for 3 sec, the first parameter label will be 

showed; 

2.

 

Press 

DOWN 

key till the 

Pr2

 label will be showed, then press 

SET

3.

 

The blinking 

PAS

 label will be showed, wait some seconds; 

4.

 

Will be showed “

0 - -

” with blinking 0: insert the password [

321

] using the keys 

UP

 and 

DOWN 

and 

confirming with 

SET

 key. 

GENERAL STRUCTURE: 

The first two item 

rtC

 and 

EEV

 are related to submenus with others parameters. 

 

 

SET+UP

 keys on 

rtC

 or 

EEV

 submenus allow coming back to parameter list, 

 

SET+UP

  keys on parameter list allow immediate exit. 

8.2

 

HOW TO MOVE PARAMETER FROM PR1 TO PR2 AND VICE VERSA 

Enter on 

Pr2

; select the parameter; press together [

SET

 + 

DOWN

]; a left side LED ON gives to the parameter the 

presence on 

Pr1

 level, a left side LED OFF means that the parameter is not present on 

Pr1

 (only 

Pr2

). 

9.

 

FAST ACCESS MENU 

This menu contains the list of probes and some values that are automatically evacuate by the board such as the 

superheat and the percentage of valve opening. The values: 

nP

 or 

noP

 stands for probe not present or value not 

evacuate, 

Err

 value out of range, probe damaged not connected or incorrectly configured. 

 

Entering fast 

access menu 

 

By press and release the 

UP arrow

. The duration of the menu in 

case of inactivity is about 3 min. 

The values that will be showed depend on the configuration of the 

board. 

Use  

 

 

 or 

 

 

arrows to 

select an 

entry, 

then press 

  

 

to see the 

value or to 

go on with 

other value. 

HM

 

Access to clock menu or reset of the RTC alarm; 

An

 

Value of analog output; 

SH

 

Value of superheat. 

nA

 = not Available; 

oPP   

Percentage of valve opening. 

dP1

   (Pb1) Value read by probe 1. 

dP2

   (Pb2) Value read by probe 2. 

dP3

   (Pb3) Value read by probe 3. 

dp4

   (Pb4) Value read by probe 4. 

dP5

  (Pb5) Temperature read by probe 5 or value obtained from pressure transducer. 

dP6

   (Pb6) Value read by probe 6. 

dPP

   Pressure value read by (Pb5) transducer. 

rPP  

 Virtual pressure probe, only on slave. 

L°t

 

Minimum room temperature; 

H°t

 

Maximum room temperature; 

dPr

  Virtual probe for room temperature regulation [

rPA

 and 

rPb

]; 

dPd

   Virtual probe for defrost management [

dPA

]; 

dPF

   Virtual probe for fan management [

FPA

]; 

rSE

  Real thermoregulation set point: the value includes the sum of 

SET

HES

 and/or the 

dynamic set point if the functions are enabled. 

Exit 

 

Pressed together or wait the timeout of about 60 sec 

10.

 

MENU FOR MULTIMASTER FUNCTION: SEC 

The function “section” 

SEC

 is enabled when icon 

 is lit. It allows entering in the remote programming mode, 

from a keyboard not physically connected to the board, through the LAN functionality. 

 

 

 

Action 

Button or display 

Notes 

Enter menu 

 

Press UP arrow for about 3 sec, the 

 icon will be ON. 

Waiting for action 

SEC 

The menu to change the section will be entered. 

SEC 

label 

will be displayed. 

Enter section list 

 

Press 

SET 

to confirm. The following list will be available to 

select the proper network function. 

Select proper 

function 

 

 

Or 

 

 

 

LOC 

ALL 

SE1 

SEn 

SE8 

To gain access only to the local device. 

To gain access to all the devices connected to the LAN. 

To gain access to the device with 1st 

Adr

 (*) 

 

To gain access to the device with 8th 

Adr

 (*) 

Confirm 

 

Select and confirm an entry by pressing 

SET

 button. 

Exit menu 

 

Press 

SET

 and 

UP

 together or wait about 10 seconds. 

(*) The devices on the LAN are indexed by using the 

Adr

 parameter (in ascending order).  

 

EXAMPLES: 

1.

 

To modify the same parameter values in all the devices connected to the LAN: enter multimaster menu. 

Select and confirm 

ALL

. Exit from multimaster menu. Enter the programming menu and change the 

required parameter values. 

The new values will be changed on all devices connected to the LAN. 

2.

 

To modify a parameter value in the device with [

Adr = 35

]: find the relevant indexed section (the one 

linked to [

Adr = 35

]). Enter multimaster menu. Select and confirm this section from the multimaster menu. 

Exit from multimaster menu. Enter the programming menu and change the required parameter value. 

3.

 

If the alarm 

nod

 is present: enter the multimaster menu. Select and confirm the 

LOC 

section. Exit from 

multimaster menu. 

 

 AT THE END OF THE PROGRAMMING PROCEDURE, SELECT TH

E SECTION “LOC”. IN THIS WAY 

THE ICON 

 

WILL BE SWITCHED OFF!! 

10.1

 

SYNCHRONIZED DEFROST 

The synchronized defrost allow to manage multiple defrost from different boards connected through the LAN 

connection.  In  this  way,  the  boards  can  perform  simultaneous  defrosts  with  the  possibility  to  end  them  in  a 

synchronized way. 

 The 

Adr

 parameter cannot be duplicated because in this case the defrost cannot be correctly managed. 

 

BEGIN 

 

Press for 3 seconds, the 

rtC

 or other will be showed. The 

measurement unit blinks. 

Find Adr 

 

Press more than once the DOWN arrow to find the 

Adr 

parameter, 

the press 

SET

Modify Adr 

 or 

 

Set the value of 

Adr

 parameter, then press 

SET

 to confirm the 

parameter. 

EXIT 

 

Press the two keys together to exit from menu or wait for about 10 

seconds. 

 

The 

LSn

  and 

LAn

  parameter  are  only  to  show  the  actual  settings  (read  only).  Se  the  following  example  of 

configuration

 

DAILY DEFROST FROM RTC: : [cPb = y] & [EdF = rtC]

 

 

IdF

 

Parameter

: for safety reason force the value of 

Idf

 at +1 respect to the interval between two 

Ld

 parameters. 

The 

IdF

 timer is reinitialized after defrost and at every power-on. 

DEFROST START:

 at the time selected by the parameters 

Ld1 

to 

Ld6

 or 

Sd1 

to 

Sd6

DEFROST END: 

if the probes reach the 

dtE

 temperature

 

or for maximum 

MdF

 time. 

SAFETY and RtC or RtF ALARM: 

with clock alarm

 

the device will use the parameter 

IdF, dtE

 and 

MdF

 

WARNING: 

don’t set [EdF = rtC] and [CPb = n].

 

 

MULTIMASTER DEFROST

: all the probes with clock 

Table for example 

Par. 

Unit A (RTC)

 

Unit B (RTC)

 

Unit C (RTC) 

Adr 

N + 1 

N + 2 

EdF 

rtC (clock) 

rtC (clock) 

rtC (clock) 

IdF 

9 hours safety 

9 hours safety 

9 hours safety 

MdF 

45 min safety 

45 min safety 

45 min safety 

dtE 

12°C safety 

12°C safety 

12°C safety 

Ld1 

06:00    1°  

06:00    1°  

06:00    1°  

Ld2 

14:00    2°  

14:00    2°  

14:00    2°  

Ld3 

22:00   3°  

22:00   3°  

22:00   3°  

 

Summary of Contents for Dixell XM670K

Page 1: ...nstruments are equipped with the HOTKEY connector that permits to be programmed in a simple way Direct serial output RS485 ModBUS RTU compatible permits a simple XWEB interfacing RTC are available as options The HOTKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with D...

Page 2: ... to 10Vdc Use CABCJ15 to perform the connections It s located near the terminal 39 on a 2 pin connector It s possible to use the output to control anti sweat heaters through a chopped phase controller XRPW500 500watt or family XV D or XV K 6 QUICK REFERENCE GUIDE HOW TO RUN THE SELF ADAPTIVE REGULATION IN 4 STEPS 1 After wiring the XM679K set the proper gas via Fty parameter Pre set gas is R404A 2...

Page 3: ...c set point if the functions are enabled Exit Pressed together or wait the timeout of about 60 sec 10 MENU FOR MULTIMASTER FUNCTION SEC The function section SEC is enabled when icon is lit It allows entering in the remote programming mode from a keyboard not physically connected to the board through the LAN functionality Action Button or display Notes Enter menu Press UP arrow for about 3 sec the ...

Page 4: ...of regulation parameter SFd percentage and SFd time Forced opening of the valve after defrost parameter oPd percentage and Pdd time 12 4 MINIMUM STABLE SUPERHEAT SEARCH AMS YES ATU YES With the parameter ATU the minimum stable superheat search function is enabled With ATU yES controllers start searching the mimimum stable value for the SH the minimum admitted value in any case is LSH 2 C 4 F Pleas...

Page 5: ...ing to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low thermal exchange is detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtc the maximum duration of defrost is obtained ...

Page 6: ...pressure exceeds maximum operating pressure value instrument signals situation with MOP alarm related to PrM parameter LOP Lowest Operating Pressure threshold PA4 P20 bar psi kPA 10 if the suction pressure comes down to this value a low pressure alarm is signalled with LOP alarm related to PrM parameter dML delta MOP LOP 0 100 when a MOP alarm occurs valve will close of the dML percentage every cy...

Page 7: ...ion dor door open dEF defrost activation AUS auxiliary activation LiG light activation OnF switch on off the instrument Htr change type of action FHU not used ES activate energy saving Hdy activate holiday function d3d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i3F PAL If i3F EAL or bAL external alarms d3d para...

Page 8: ... for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 18 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KEY 1 When the XM unit is ON insert the Hot key and push UP key 2 The UPLOAD begins the uPL message is blinking 3 Remove the Hot Key At the end of the data transfer phase the instrument displays the foll...

Page 9: ...5 F Fod 0 Pr1 Fan activation time after defrost without compressor 0 255 min Fon 0 Pr1 Fan ON time 0 15 min FoF 0 Pr1 Fan OFF time 0 15 min trA UAL Pr2 Kind of regulation for modulating output UAL 0 rEG 1 AC 2 SOA 80 Pr2 Fixed speed for fan AMi AMA SdP 30 0 Pr2 Default Dew Point value 55 0 C 50 0 C 67 F 122 F ASr 1 0 Pr2 Differential for fan offset for anti sweat heater 25 5 C 25 5 C 45 F 45 F PbA...

Page 10: ...ving ESP P1 Pr1 Energy saving probe selection nP 0 P1 1 P2 2 P3 3 P4 4 P5 5 tEr 6 HES 0 0 Pr1 Temperature increasing during Energy Saving 30 0 C 30 0 C 54 F 54 F PEL n Pr1 Energy saving activation when Light switched off n 0 Y 1 L A N Management LMd y Pr2 Defrost Synchronisation n 0 Y 1 dEM y Pr2 Defrost end Synchronisation n 0 Y 1 LSP n Pr2 SET POINT Synchronisation n 0 Y 1 LdS n Pr2 Display Sync...

Reviews: