1592012000 XF330M XF331M XF332M GB REL1.0 31.08.2015
XF330M XF331M XF332M
12/12
21.
Parameters – Pre set Values
XF330M
XF331M
XF332M
Description
Range
Val Lev Val Lev Val Lev
Set1
Ceiling Set Point
LS1 ÷ US1
200 Pr1 200 Pr1 200 Pr1
Set2
Bottom Set Point
LS2 ÷ US2
200 Pr1 200 Pr1 200 Pr1
Hy1
Ceiling differential
-99 ÷ 99
-5
Pr1 -5 Pr1 -5 Pr1
LS1
Minimum set point limit for ceiling
Start Scale ÷ Set 1
0
Pr2
0
Pr2
0
Pr2
US1
Maximum set point limit for ceiling
Set 1 ÷ End Scale
600 Pr2 600 Pr2 600 Pr2
Hy2
Bottom differential
-99 ÷ 99
-5
Pr2 -5 Pr2 -5 Pr2
LS2
Minimum set point limit for bottom
Start Scale ÷ Set 2
0
Pr2
0
Pr2
0
Pr2
US2
Maximum set point limit for bottom
Set 2 ÷ End Scale
600 Pr2 600 Pr2 600 Pr2
Pbc
Type of probe
J=TCJ; c=TCK; P = PT100
J
Pr2
J
Pr2
J
Pr2
oF1
Ceiling probe calibration
-99 ÷ 99 °C
0
Pr1
0
Pr1
0
Pr1
oF2
Bottom probe calibration
-99 ÷ 99 °C
0
Pr1
0
Pr1
0
Pr1
CF
Measurement unit
°C = Celsius /
°F = Fahrenheit
°C
Pr2 °C Pr2 °C Pr2
diS
Default display
tP = temp. / SEt = Set Point tP
Pr2 tP Pr2 tP Pr2
ccY
Steam injection setting
Sin= single / riP = repetitive Sin Pr1 Sin Pr1 Sin Pr1
AcY
Steam injection activation
MAn=manual/AUt=autom. MAn Pr1 MAn Pr1 MAn Pr1
tcY
Inhibition time between 2 following steam injections
1 ÷ 250 sec
10
Pr1 10 Pr1 10 Pr1
Tco
Steam injection time
0 ÷ 60 min
3
Pr1
3
Pr1
3
Pr1
HSi
Maximum time for steam injection
0 ÷ 60 sec
10
Pr1 10 Pr1 10 Pr1
TES
Automatic activation of the steam extractor before the
end of cooking
0 ÷ 99 min
0
Pr1
-
-
0
Pr1
tFS
Fan restarting delay after steam injection
0 ÷ 99 min
-
-
-
-
0
Pr1
Ac1
Ceiling temperature alarm configuration
Ab = absolute / rE = relative Ab
Pr2 Ab Pr2 Ab Pr2
AL1
Low temperature alarm for the ceiling
0 ÷ 120 / Start Scale ÷ Au1
0
Pr2
0
Pr2
0
Pr2
Au1
High temperature alarm for the bottom
0 ÷ 120/AL1 ÷ End Scale 600 Pr2 600 Pr2 600 Pr2
DA1
Temperature alarm delay for the ceiling temperature
0 ÷ 120 min
0
Pr2
0
Pr2
0
Pr2
HA1
Differential for temperature alarm returns
1 ÷ 15
2
Pr2
2
Pr2
2
Pr2
Ac2
Bottom temperature alarm configuration
Ab = absolute / rE = relative Ab
Pr2 Ab Pr2 Ab Pr2
AL2
Low temperature alarm for the bottom
0 ÷ 120 / Start Scale ÷ Au2
0
Pr2
0
Pr2
0
Pr2
Au2
High temperature alarm for the bottom
0 ÷ 120 / AL2÷End Scale 600 Pr2 600 Pr2 600 Pr2
DA2
Temperature alarm delay for the bottom temperature
0 ÷ 120 min
0
Pr2
0
Pr2
0
Pr2
HA2
Temperature alarm differential
1 ÷ 15 °C
2
Pr2
2
Pr2
2
Pr2
tcE
Energy Saving cycle time
1 ÷ 999 sec
120 Pr1 120 Pr1 120 Pr1
dcy
Switching on percentage for the ceiling output during
the Energy Saving cycle
0 ÷ 100 %
50
Pr1 50 Pr1 50 Pr1
i1P
Digital input polarity to enabling steam injection
oP÷CL
-
-
OP Pr2
-
-
Ptb
Parameter table code
-
-
Pr2
-
Pr2
-
Pr2
rEL
Software release
-
-
Pr2
-
Pr2
-
Pr2