1592012000 XF330M XF331M XF332M GB REL1.0 31.08.2015
XF330M XF331M XF332M
8/12
12.
Parameters programming
12.1
How to enter the first level menu Pr1 and
modify a parameter.
To change the parameter’s value operate as follows:
1.
Enter the Programming mode by pressing the
PRG
+
SET
keys for 3s. The ceiling display shows the label of
the first parameters, the bottom display its values.
2.
Select the required parameter using “
UP
” or “
DOWN”
keys on the right of the ceiling display.
3.
Use “
UP
” or “
DOWN
” of the bottom display to change
its value.
To exit
: Press and release the
PRG
key or wait 30s
without pressing any keys.
NOTE
: the set value is stored even when the procedure is
exited by waiting the time-out to expire.
12.2
How to enter the hidden menu Pr2
The hidden menu Includes all the parameters of the
instrument.
1.
Enter the first level menu Pr1.
2.
Hold pressed the
PRG
+
SET
keys for more than 7s,
till the Pr2 label.
3.
Release the keys, the first parameter and its value
will be displayed.
4.
Modify the parameter value according to the
procedure described in previous paragraph.
To exit
: Press and release the
PRG
key or wait 30s
without pressing any keys.
NOTE
: the set value is stored even when the procedure is
exited by waiting the time-out to expire.
12.3
How to move a parameter from the hidden
menu to the first level and viceversa.
Each parameter present in the HIDDEN MENU can be
removed or put into “THE FIRST LEVEL” (Pr1l).
1.
Enter the Pr2 menu.
2.
Hold pressed the
key.
3.
Push the
DOWN
key of
ceiling display
.
In HIDDEN MENU when a parameter is present in First
Level the LED of the
key in on.
13.
Parameters list
Hy1 Ceiling differential (
-99 ÷ 99 °C) Intervention
differential for the ceiling set point. Output is activated
when the ceiling temperature is less than Set Point
+Hy1.
LS1 Minimum set point limit for ceiling:
(Down scale
set1) Sets the minimum acceptable value for the set
point of ceiling.
US1 Maximum set point limit for ceiling:
(SET1
End
scale) Set the maximum acceptable value for set
point of ceiling.
Hy2 Bottom differential
(-99 ÷ 99 °C) Intervention
differential for the bottom set point. Output is
activated when the bottom temperature is less than
Set Point + Hy2.
LS2 Minimum set point limit for bottom:
(Down scale
set2) Sets the minimum acceptable value for the set
point of bottom.
US2 Maximum set point limit for bottom:
(SET2
End
scale) Set the maximum acceptable value for set
point of bottom.
PbC Type of probe:
it allows to set the kind of probe used
by the instrument: (
J
=TCJ,
c
=TCK;
P
=PT100)
oF1 Ceiling probe calibration
(-99 ÷ 99 °C)
oF2 Bottom probe calibration
(-99 ÷ 99 °C)
CF measurement unit (°C
= Celsius /
°F
= Fahrenheit)
diS Default display (tP
= temperature /
SEt
= Set Point)
It established the displaying during the cooking: set
points or temperatures.
ccY Steam injection setting
(
Sin
= single injection,
riP
=repetitive injection) See par. 8.2 Steam injection,
AcY Steam injection activation
(
MAn
= manual
activation;
AUt
= automatic activation) See par. 8.2
tcY Inhibition time between 2 following steam
injections
(0÷250s) ) At the end of a injection cycle,
start this timer. During this time all the steam injection
requests are ignored.
tco Steam injection time (
0 ÷ HSi seconds) it sets the
duration of a steam injection cycle
HSi Maximum time for steam injection:
(0÷60sec) it
sets the maximum value for tco parameter (steam
injection time). With HSi = 0 the steam is injected as
long as the key is pressed.
tES Automatic activation of the steam extractor before
the end of cooking (not for the XF331M)
(0÷90min)
tFS Fan restarting delay after steam injection (only for
XF332M)
(0÷90min)
AC1 Ceiling temperature alarm configuration
rE
=
related to Ceiling Set Point
High and Low
temperature alarms are signalled when the
temperature exceeds the following values:
“SET+AU1” and “SET+AL1”.