IEC 62591 Wireless Interface Instruction Manual (for ControlWave Micro)
Revised October-2019
Troubleshooting
4-9
4.5 Data Updates
If you notice that data updates for process variables are slow, this can
occur if the IEC 62591 device cannot process a data request fast enough.
If this happens it generates a delayed response message, and the RTU
re-requests the data.
To see if you are receiving delayed response messages, look for a 9
(Delayed Response Received) status on the
ousDevCommishStatus
parameter of the Commission List entry.