IEC 62591 Wireless Interface Instruction Manual (for ControlWave Micro)
Revised October-2019
Configuration and Commissioning
3-21
4.
Using DataView or through ControlWave Designer in online
operation, change the value of the
ioaiMode
parameter to
2
to start
the firmware download.
5.
Monitor the
odiStatus
parameter on the IEC62591 function block.
While the download progresses, status code
51005
is reported.
When the download completes the success code of
51006
appears
momentarily; then
0
appears which means the firmware upgrade is
complete. The upgrade takes approximately five minutes.