![Emerson CSI 9420 Reference Manual Download Page 102](http://html.mh-extra.com/html/emerson/csi-9420/csi-9420_reference-manual_104608102.webp)
Note
The appropriate alerts for a given machine will be a function of its design, service, and turning speed.
Utilizing the embedded PeakVue technology, the CSI 9420 identified developing problems
at a couple of test sites during early field trials. In both cases, the problem was not visible
with conventional low-frequency analysis. The following examples provide sample data
from one of the sites. Notice in the example that the velocity measurement is indicating
less than 0.1 in/s. The PeakVue trend, however, indicates high-frequency vibration that is
regularly in excess of 6 g's.
Example 1: 4600 HP fan motor - OH (Overall)
Figure 5-5:
Example 2: 4600 fan motor - OH (PeakVue)
Figure 5-6:
Velocity, PeakVue, and temperature
96
MHM-97408, Rev 15
Summary of Contents for CSI 9420
Page 4: ......
Page 10: ...Revision numbers in AMS Device Manager Figure 1 2 Introduction 4 MHM 97408 Rev 15 ...
Page 60: ...PeakVue spectrum Figure 2 35 Configuration 54 MHM 97408 Rev 15 ...
Page 92: ...Setup 86 MHM 97408 Rev 15 ...
Page 134: ...Product certifications 128 MHM 97408 Rev 15 ...