Emerson Copeland Scroll ZR K3 Series Application Engineering Bulletin Download Page 8

AE4-1312 R2

© 2010 Emerson Climate Technologies

Printed in the U.S.A.

8

15% of the average on the three phases of a three-

phase compressor should be investigated further. A 

more comprehensive trouble-shooting sequence for 

compressors and systems can be found in Section 

H of the Emerson Climate Technologies Electrical 

Handbook.

7.  Before replacing or returning a compressor

:

 

Be 

certain that the compressor is actually defective. As 

a minimum, recheck a compressor returned from 

the  field  in  the  shop  or  depot  for  Hipot,  winding 

resistance, and ability to start before returning to 

Emerson Climate Technologies. More than one-third 

of compressors returned to Emerson for warranty 

analysis are determined to have nothing found 

wrong. They  were  misdiagnosed  in  the  field  as 

being defective. Replacing working compressors 

unnecessarily costs everyone. 

Tandem Scroll Compressors

 

The refrigerant charge limit for tandem compressors 

is shown in 

Table 5.

 A three-phase unit with a charge 

over this limit must have crankcase heaters added to 

both compressors.  The ZRT90 – ZRT122 compressors 

are mounted on rails using rubber mounting parts. The 

ZRT136 – ZRT162 compressors are rigidly mounted 

on rails using solid steel mounting parts. These 

mounts are installed at the factory and should not be 

loosened. Tighten to 125 inch pounds (14 NM) if it 

becomes necessary to tighten these mounts. Holes 

in the mounting rails may be used to mount isolation 

grommets under the entire tandem.

A discharge check valve must be placed in the 

common discharge line when pump down is used. Both 

compressors must be at the same level to prevent oil 

from migrating to the lowest compressor through the 

oil equalization line.

Compressors may be individually cycled. Individual 

compressors should not be replaced in the field. The 

entire tandem compressor unit must be replaced if 

it becomes necessary to replace one compressor. 

Individual compressors configured for tandem usage 

may not be available for field replacement. See 

section below for further tips on field replacement of 

compressors. 

Compressor Replacement after Motor Burn

In the case of a motor burn, the majority of contaminated 

oil will be removed with the compressor. The rest of the 

oil is cleaned through use of suction and liquid line filter 

dryers. A 100% activated alumina suction filter drier is 

recommended but must be removed after 72 hours. See 

AE24-1105

 for clean up procedures and 

AE11-1297

 

for liquid line filter-drier recommendations. 

It is highly 

recommended that the suction accumulator be 

replaced if the system contains one. 

This is because 

the  accumulator  oil  return  orifice  or  screen  may  be 

plugged with debris or may become plugged shortly after 

a compressor failure. This will result in starvation of oil 

to the replacement compressor and a second failure. 

Start-up of a New or Replacement Compressor

It is good service practice, when charging a system, 

to charge liquid refrigerant into the high side only and 

charge the low side of the system with vapor only. It is 

not good for any compressor to have liquid refrigerant 

dumped from a refrigerant cylinder into the crankcase 

of the compressor. 

Do not start the compressor while 

the system is in a deep vacuum.

 Internal arcing may 

occur when a scroll compressor is started in a vacuum. 

Do not operate compressor without enough system 

charge to maintain at least 7 psig (0.5 kg/cm2) 

suction pressure. Do not operate with a restricted 

suction. Do not operate with the low pressure 

cut-out disabled. 

Allowing suction pressure to drop 

below 7 psig (0.5 kg/cm2) for more than a few seconds 

may overheat scrolls and cause early drive bearing 

damage. Never install a system in the field and leave it 

unattended with no charge, a holding charge, or with the 

service valves closed without securely locking out the 

system. This will prevent unauthorized personnel from 

accidentally operating the system for comfort cooling 

and potentially ruining the compressor by operating 

with no refrigerant flow.   

Excessive Liquid Flood back Tests

The following tests are for those system configurations 

and charge levels identified in 

Table 1

 that need special 

testing to verify exemption from need of an accumulator. 

Figure 1 

should be used to determine the effectiveness 

of an accumulator. The compressor sump temperature 

during any test where the return gas superheat is near 

zero must always meet the guidelines of 

Figure 1

To test for 

excessive continuous liquid refrigerant 

flood back

, it is necessary to operate the system in a test 

room at conditions where steady state flood back may 

occur (low ambient heating operation). Thermocouples 

should be attached with glue or solder to the center of 

the bottom shell and to the suction and discharge lines 

approximately 6 inches (15 cm from the shell). These 

thermocouples should be insulated from the ambient air 

with Permagum® or other thermal insulation to be able 

to record true shell and line temperatures. If the system 

is designed to be field charged, it should be overcharged 

by 15% in this test to simulate overcharging commonly 

found in field installations.

Summary of Contents for Copeland Scroll ZR K3 Series

Page 1: ... the high side and the low side of the compressor It is designed to open when the discharge to suction differential pressure exceeds 375 to 450 psid 26 32 kg cm2 When the valve opens hot discharge gas is routed back into the area of the motor protector to cause a trip During developmental blocked fan testing it is sometimes noted that the valve opens but the compressor does not shut off while the ...

Page 2: ...e shutdown sound for acceptability in a particular system Also refer to section on Brief Power Interruption Discharge Check Valve Alow mass disc type check valve in the discharge fitting of the compressor prevents the high side high pressure discharge gas from flowing rapidly back through the compressor This check valve was not designed to be used with recycling pump down because it is not entirel...

Page 3: ...ng the off cycle See Figure 2 and Table 6 Pump down Cycle A pump down cycle for control of refrigerant migration is not recommended for scroll compressors of this size If a pump down cycle is used a separate external check valve must be added The scroll discharge check valve is designed to stop extended reverse rotation and prevent high pressure gas from leaking rapidly into the low side after shu...

Page 4: ... muffler should be located a minimum of six inches 15 cm to a maximum of 18 inches 46 cm from the compressor for most effective operation The further the muffler is placed from the compressor within these ranges the more effective it may be If adequate attenuation is not achieved use a muffler with a larger cross sectional area to inlet area ratio The ratio should be a minimum of 20 to 1 with a 30...

Page 5: ...ls and permanent damage to the scroll tips drive bearings and internal seal See AE24 1105 for proper system evacuation procedures Nomenclature The model numbers of the Copeland Scroll compressors include the approximate nominal 60 HZ capacity at standard operating conditions An example would be the ZR24K3 TFD which has 24 500 Btu hr 7 kw cooling capacity at the ARI high temperature air conditionin...

Page 6: ...s ready for assembly to the unit It is suggested that the larger suction plug be removed first to relieve the internal pressure Removing the smaller discharge plug could result in a spray of oil out of this fitting since some oil would accumulate in the head of the compressor after Emerson test runs the compressor The inside of both fittings should we wiped with a lint free wipe to remove residual...

Page 7: ... could ignite when it escapes and contacts the brazing flame It is important to check both the high pressure and low pressure side with manifold gauges before unbrazing Instructions should be provided in appropriate product literature and assembly line repair areas If compressor removal is required the compressor should be cut out of system rather than unbrazed See Figure 6 for proper compressor r...

Page 8: ...e filter drier recommendations It is highly recommended that the suction accumulator be replaced if the system contains one This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure Start up of a New or Replacement Compresso...

Page 9: ...igerant flood back To test for repeated excessive liquid flood back during normal system off cycles perform the Field Application Test Obtain a sample compressor with a side sight tube to measure liquid level in the compressor Set the system up in a configuration with the indoor unit elevated several feet above the outdoor unit with twenty five feet 8 meters of connecting tubing with no traps betw...

Page 10: ... heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Liquid Level Drainage In Off Cycle Scroll Accumulator Figure 2 To prevent flooded start damage on 3 phase scrolls due to off cycle migration the accumulator may be configured on some systems to allow free drainage from the co...

Page 11: ...ications Timer Opens 1 Electrical cycle Timer Closes Greater than 5 seconds later 016 sec with 60 HZ operation power is restored or not after power is removed Typical Solid State Timer if used Fuse Discharge Line Thermostat if used Compressor Contactor Condenser Fan Contactor if used Other Protective Devices if used System Operating Thermostat 230 240 VAC C1 C ...

Page 12: ...ections Figure 4 Terminal Fusite Connection 70 80 90 100 110 120 130 140 150 160 170 20 10 0 10 20 30 40 50 60 Condensing Temp C Evaporating Temp C Condensing Temp F Evaporating Temp F R22 Scroll Operating Envelope 20 15 10 5 0 5 10 25 15 70 60 50 40 30 ZR__KA Limited Envelope All Other Scroll Products Figure 5 ...

Page 13: ... braze temperature is attained moving torch up and down and rotating around tube as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around cir cumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with a...

Page 14: ...AE4 1312 R2 2010 Emerson Climate Technologies Printed in the U S A 14 Operating Principle of Scroll Figure 7 ...

Page 15: ...uired Not Required Required Required Not Required Required Required Required Other 1 Nominal System Charage 2 Table 1 Scroll Compressor Application Diagram 1 Other includes bleed type TXVs capillary tubes and fixed orifices 2 Nominal System Charge is defined as the design charge for a system Note See text for crankcase heater requirements 120 Times Compressor refrigerant charge limit in Table 5 ...

Page 16: ...onent Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Suction muffler May be required Acts as dampening mass Table 3 K1 K2 K3 K4 KC ZR18 25µf 370 volt 30µf 370 volt 35µf 370 volt 30µf 370 volt ZR23 30µf 370 volt 40µf 370 volt 35µf 370 volt 35µf 370 volt ZR26 35µf 370 volt 40µf 370 volt 30µf 440 volt ZR28 35µf 370 volt 45µf 370 volt 35µf 440 vol...

Page 17: ...KC 4 ZR16KA ZR34KA 53 018 0052 00 240 40 02 6319 00 21 53 018 0052 01 120 40 02 6319 02 21 ZR18K3 ZR48K3 ZR26KC ZR48KC ZR38KA ZR54KA 63 018 0041 00 240 40 02 6307 00 21 63 018 0041 01 120 40 02 6307 02 21 63 018 0041 02 480 40 02 6307 03 21 63 018 0041 03 575 40 02 6307 06 21 63 018 0041 04 240 40 02 6311 00 48 63 018 0041 05 480 40 02 6311 03 48 63 018 0041 06 240 40 02 6313 00 32 ZR54K3 ZR61K3 Z...

Page 18: ...Model MFD Volts Part Number G E p n Emerson p n Pick up Volts Drop out Volts Coil Voltage ZR16K x to ZR48K x PFV 88 108 330 014 0036 03 3ARR3CT3P5 040 0001 79 170 180 40 90 332 ZR46K x to ZR68K x PFV 270 324 330 014 0006 10 3ARR3CT3P5 040 0001 79 170 180 40 90 332 x C 3 4 or CE 3E 4E ZR_KA Start components still in development ...

Reviews: