Emerson Copeland Scroll ZR K3 Series Application Engineering Bulletin Download Page 7

AE4-1312 R2

© 2010 Emerson Climate Technologies

Printed in the U.S.A.

7

semi-hermetic compressors which can have horizontal 

motors partially submerged in oil and refrigerant. When 

Copeland Scroll compressors are Hipot tested with liquid 

refrigerant in the shell, they can show higher levels of 

leakage current than compressors with the motor on top. 

This phenomenon can occur with any compressor when 

the motor is immersed in refrigerant. The level of current 

leakage does not present any safety issue. To lower the 

current leakage reading, the system should be operated 

for a brief period of time to redistribute the refrigerant 

to a more normal configuration and the system Hipot 

tested again. See AE Bulletin 4-1294 for Megohm testing 

recommendations. Under no circumstances should the 

Hipot test be performed while the compressor is under 

a vacuum.

Final Run Test

Single phase scrolls with an electrical characteristic of 

PFV

” (208-230 volt, 1Ô, 60 Hertz) at the end of the 

model number may not be started at a voltage lower 

than 187 volts and must have a voltage no lower than 

197 volts once the compressor is running under load. 

Variable transformers used on assembly lines are often 

not capable of starting larger compressors at a particular 

voltage setting. To test for voltage sag during the initial 

locked  rotor  starting  phase  the  first  compressor  in  a 

production run should be used to preset the voltage. 

Remove the start wire from the compressor and apply 

200 volts to the compressor. With the start winding 

removed the compressor will remain in locked rotor long 

enough to read the voltage supply. If the voltage sags 

below the minimum guaranteed starting voltage the 

variable transformer must be preset to a higher voltage 

to start the compressor at a higher voltage.

Other compressor voltages

. All other compressor 

voltages, both single and three phase are guaranteed 

to start and run at 10% below the lowest voltage shown 

on the nameplate.

Unbrazing System Components
Caution! Before opening a system it is important 

to remove all refrigerant from both the high and 

low side. 

If the refrigerant charge is removed from a 

scroll-equipped unit by bleeding one side only, it is very 

possible that either the high or low side of the system 

remains pressurized. If a brazing torch is then used 

to disconnect tubing, the pressurized refrigerant and 

oil mixture could ignite when it escapes and contacts 

the brazing flame. 

It is important to

 

check both the 

high pressure and low pressure side

 

with manifold 

gauges before unbrazing.

 Instructions should be 

provided in appropriate product literature and assembly 

(line repair) areas. If compressor removal is required, 

the compressor should be cut out of system rather 

than unbrazed.  See 

Figure 6

 for proper compressor 

removal procedure. 

Copeland Scroll Functional Check

A functional compressor test during which the suction 

service valve is closed to check how low the compressor 

will pull suction pressure is not a good indication of 

how well a compressor is performing.  

Such a test will 

damage a scroll compressor.

 The following diagnostic 

procedure should be used to evaluate whether a 

Copeland Scroll compressor is functioning properly:

1.  Proper voltage to the unit should be verified. 

Determine if the internal motor overload protector 

has opened or if an internal motor short or ground 

fault has developed. If the protector has opened, 

the compressor must be allowed to cool sufficiently 

to allow it to reset.

2.  Check that the compressor is correctly wired.
3.  Proper indoor and outdoor fan/blower operation 

should be verified.

4.  With service gauges connected to suction and 

discharge pressure fittings, turn on the compressor. 

If suction pressure falls below normal levels the 

system is either low on charge or there is a flow 

blockage in the system.

5.  Single Phase Compressors

If the compressor starts and the suction pressure 

does not drop and discharge pressure does not rise 

to normal levels, either the reversing valve (if so 

equipped) or the compressor is faulty. Use normal 

diagnostic procedures to check operation of the 

reversing valve.

Three Phase Compressors

If suction pressure does not drop and discharge 

pressure does not rise to normal levels, reverse 

any two of the compressor power leads and reapply 

power to make sure the compressor was not wired 

to run in reverse. If pressures still do not move 

to normal values, either the reversing valve (if so 

equipped) or the compressor is faulty. Reconnect 

the compressor leads as originally configured 

and use normal diagnostic procedures to check 

operation of the reversing valve.

6.  To test if the compressor is pumping properly, the 

compressor current draw must be compared to 

published compressor performance curves using 

the operating pressures and voltage of the system. 

If the measured average current deviates more than 

±15% from published values, a faulty compressor 

may be indicated. A current imbalance exceeding 

Summary of Contents for Copeland Scroll ZR K3 Series

Page 1: ... the high side and the low side of the compressor It is designed to open when the discharge to suction differential pressure exceeds 375 to 450 psid 26 32 kg cm2 When the valve opens hot discharge gas is routed back into the area of the motor protector to cause a trip During developmental blocked fan testing it is sometimes noted that the valve opens but the compressor does not shut off while the ...

Page 2: ...e shutdown sound for acceptability in a particular system Also refer to section on Brief Power Interruption Discharge Check Valve Alow mass disc type check valve in the discharge fitting of the compressor prevents the high side high pressure discharge gas from flowing rapidly back through the compressor This check valve was not designed to be used with recycling pump down because it is not entirel...

Page 3: ...ng the off cycle See Figure 2 and Table 6 Pump down Cycle A pump down cycle for control of refrigerant migration is not recommended for scroll compressors of this size If a pump down cycle is used a separate external check valve must be added The scroll discharge check valve is designed to stop extended reverse rotation and prevent high pressure gas from leaking rapidly into the low side after shu...

Page 4: ... muffler should be located a minimum of six inches 15 cm to a maximum of 18 inches 46 cm from the compressor for most effective operation The further the muffler is placed from the compressor within these ranges the more effective it may be If adequate attenuation is not achieved use a muffler with a larger cross sectional area to inlet area ratio The ratio should be a minimum of 20 to 1 with a 30...

Page 5: ...ls and permanent damage to the scroll tips drive bearings and internal seal See AE24 1105 for proper system evacuation procedures Nomenclature The model numbers of the Copeland Scroll compressors include the approximate nominal 60 HZ capacity at standard operating conditions An example would be the ZR24K3 TFD which has 24 500 Btu hr 7 kw cooling capacity at the ARI high temperature air conditionin...

Page 6: ...s ready for assembly to the unit It is suggested that the larger suction plug be removed first to relieve the internal pressure Removing the smaller discharge plug could result in a spray of oil out of this fitting since some oil would accumulate in the head of the compressor after Emerson test runs the compressor The inside of both fittings should we wiped with a lint free wipe to remove residual...

Page 7: ... could ignite when it escapes and contacts the brazing flame It is important to check both the high pressure and low pressure side with manifold gauges before unbrazing Instructions should be provided in appropriate product literature and assembly line repair areas If compressor removal is required the compressor should be cut out of system rather than unbrazed See Figure 6 for proper compressor r...

Page 8: ...e filter drier recommendations It is highly recommended that the suction accumulator be replaced if the system contains one This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure Start up of a New or Replacement Compresso...

Page 9: ...igerant flood back To test for repeated excessive liquid flood back during normal system off cycles perform the Field Application Test Obtain a sample compressor with a side sight tube to measure liquid level in the compressor Set the system up in a configuration with the indoor unit elevated several feet above the outdoor unit with twenty five feet 8 meters of connecting tubing with no traps betw...

Page 10: ... heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Liquid Level Drainage In Off Cycle Scroll Accumulator Figure 2 To prevent flooded start damage on 3 phase scrolls due to off cycle migration the accumulator may be configured on some systems to allow free drainage from the co...

Page 11: ...ications Timer Opens 1 Electrical cycle Timer Closes Greater than 5 seconds later 016 sec with 60 HZ operation power is restored or not after power is removed Typical Solid State Timer if used Fuse Discharge Line Thermostat if used Compressor Contactor Condenser Fan Contactor if used Other Protective Devices if used System Operating Thermostat 230 240 VAC C1 C ...

Page 12: ...ections Figure 4 Terminal Fusite Connection 70 80 90 100 110 120 130 140 150 160 170 20 10 0 10 20 30 40 50 60 Condensing Temp C Evaporating Temp C Condensing Temp F Evaporating Temp F R22 Scroll Operating Envelope 20 15 10 5 0 5 10 25 15 70 60 50 40 30 ZR__KA Limited Envelope All Other Scroll Products Figure 5 ...

Page 13: ... braze temperature is attained moving torch up and down and rotating around tube as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around cir cumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with a...

Page 14: ...AE4 1312 R2 2010 Emerson Climate Technologies Printed in the U S A 14 Operating Principle of Scroll Figure 7 ...

Page 15: ...uired Not Required Required Required Not Required Required Required Required Other 1 Nominal System Charage 2 Table 1 Scroll Compressor Application Diagram 1 Other includes bleed type TXVs capillary tubes and fixed orifices 2 Nominal System Charge is defined as the design charge for a system Note See text for crankcase heater requirements 120 Times Compressor refrigerant charge limit in Table 5 ...

Page 16: ...onent Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Suction muffler May be required Acts as dampening mass Table 3 K1 K2 K3 K4 KC ZR18 25µf 370 volt 30µf 370 volt 35µf 370 volt 30µf 370 volt ZR23 30µf 370 volt 40µf 370 volt 35µf 370 volt 35µf 370 volt ZR26 35µf 370 volt 40µf 370 volt 30µf 440 volt ZR28 35µf 370 volt 45µf 370 volt 35µf 440 vol...

Page 17: ...KC 4 ZR16KA ZR34KA 53 018 0052 00 240 40 02 6319 00 21 53 018 0052 01 120 40 02 6319 02 21 ZR18K3 ZR48K3 ZR26KC ZR48KC ZR38KA ZR54KA 63 018 0041 00 240 40 02 6307 00 21 63 018 0041 01 120 40 02 6307 02 21 63 018 0041 02 480 40 02 6307 03 21 63 018 0041 03 575 40 02 6307 06 21 63 018 0041 04 240 40 02 6311 00 48 63 018 0041 05 480 40 02 6311 03 48 63 018 0041 06 240 40 02 6313 00 32 ZR54K3 ZR61K3 Z...

Page 18: ...Model MFD Volts Part Number G E p n Emerson p n Pick up Volts Drop out Volts Coil Voltage ZR16K x to ZR48K x PFV 88 108 330 014 0036 03 3ARR3CT3P5 040 0001 79 170 180 40 90 332 ZR46K x to ZR68K x PFV 270 324 330 014 0006 10 3ARR3CT3P5 040 0001 79 170 180 40 90 332 x C 3 4 or CE 3E 4E ZR_KA Start components still in development ...

Reviews: