background image

AE4-1312 R2

© 2010 Emerson Climate Technologies

Printed in the U.S.A.

2

operation since backup heat will make up the deficit. A 

low pressure control is recommended for loss of charge 

protection in heat pumps for the highest level of system 

protection. A cut out setting no lower than 25 psig (2 

kg/cm2) for air conditioning and 7 psig (0.5 kg/cm2) for 

heat pumps is recommended. The low pressure cut-out, 

if installed in the suction line to the compressor, can 

provide additional protection against a TXV failed in the 

closed position, outdoor fan failure in heating, a closed 

liquid line or suction line service valve, or a blocked liquid 

line screen, filter, orifice, or TXV. All of these can starve 

the compressor for refrigerant and result in compressor 

failure. The low pressure cut-out should have a manual 

reset feature for the highest level of system protection. If 

a compressor is allowed to cycle after a fault is detected, 

there is a high probability that the compressor will be 

damaged and the system contaminated with debris from 

the failed compressor and decomposed oil. If current 

monitoring to the compressor is available, the system 

controller can take advantage of the compressor TOD 

and internal protector operation. The controller can lock 

out the compressor if current draw is not coincident with 

the contactor energizing, implying that the compressor 

has shut off on its internal protector. This will prevent 

unnecessary compressor cycling on a fault condition 

until corrective action can be taken.  

Quiet Shut down

All scrolls in this size range have one of several 

types of “quiet” shutdown solutions. The ZR..KC/K3/

K4 Scrolls up to four tons use a cam-type device that 

separates the scrolls when they are driven backwards 

as high-pressure gas equalizes from the high side 

of the compressor to the low side during shutdown. 

Larger scrolls with 70 frame motors through ZR61 use 

a different type of cam that stops backward rotation 

during shut down. Models ZR68KC through ZR81KC 

will  continue  to  be  built  with  the  fluid  brake  design, 

so a momentary reverse rotation sound will be heard 

from these compressors. The newer ZR..KA scrolls 

incorporate a non dynamic discharge port check valve 

that prevents high pressure gas trapped in the dome 

from returning through the scroll set. All of these quiet 

shut down solutions allow the scroll compressor to 

restart immediately even if the system is not equalized 

eliminating the need for a time delay. Development 

testing should include a review of the shutdown sound 

for acceptability in a particular system.

 

Also refer to 

section on “Brief Power Interruption”.

Discharge Check Valve

A low mass, disc-type check valve in the discharge fitting 

of the compressor prevents the high side, high pressure 

discharge  gas  from  flowing  rapidly  back  through  the 

compressor. This check valve was not designed to be 

used with recycling pump down because it is not entirely 

leak-proof.

Motor Protector

Conventional internal line break motor protection is 

provided. The protector opens the common connection 

of a single-phase motor and the center of the Y 

connection on three-phase motors. The three-phase 

protector provides primary single-phase protection. Both 

types of protectors react to current and motor winding 

temperature. 

Field Replacement of obsolete Single Phase ZR*K1 

or ZR*K2 with Equivalent Capacity ZR*K3/K4/KA/

KC, Scroll Compressors

The discharge and suction fitting sizes

 as well as the 

mounting foot pattern of the new models are identical 

to the ZR*K1 or ZR*K2. Tubing location is identical in 

most  cases  for  easy  field  replacement.  The  ZR*K1 

has an external top cap thermostat to limit discharge 

temperature. This feature has been replaced by the 

Therm-O-Disc

®

 located inside the new scrolls. When 

replacing the ZR*K1, the top cap thermostat wires 

must be removed and the control circuit wires spliced 

together. See section on 

Compressor Replacement 

after Motor Burn 

for further tips on field replacement. 

The replacement compressor will need a new run 

capacitor if the old capacitor is more than 5 microfarads 

different or the voltage rating of the old capacitor is 

lower than the new one. See 

compressor nameplate 

or Table 4 

for recommended run capacitor. Note that 

the ZR*KA may only be used to replace compressors 

used for A/C, not heat pumps.

Application Considerations

The Copeland Scroll compressor has a number of 

application characteristics that are different from those 

of the traditional reciprocating compressor. These are 

detailed below.

Accumulators

The use of accumulators is very dependent on the 

application. The Copeland Scroll’s inherent ability to 

handle liquid refrigerant during occasional operating 

flood back situations make the use of an accumulator 

unnecessary in standard designs such as condensing 

units. Applications,  such  as  heat  pumps  with  orifice 

refrigerant control, that allow large volumes of liquid 

refrigerant  to  flood  back  to  the  compressor  during 

normal steady operation can dilute the oil to such an 

extent that bearings are inadequately lubricated and 

wear will occur. In such a case an accumulator must 

be used to reduce flood back to a safe level that the 

compressor can handle. To test for flood back conditions 

Summary of Contents for Copeland Scroll ZR K3 Series

Page 1: ... the high side and the low side of the compressor It is designed to open when the discharge to suction differential pressure exceeds 375 to 450 psid 26 32 kg cm2 When the valve opens hot discharge gas is routed back into the area of the motor protector to cause a trip During developmental blocked fan testing it is sometimes noted that the valve opens but the compressor does not shut off while the ...

Page 2: ...e shutdown sound for acceptability in a particular system Also refer to section on Brief Power Interruption Discharge Check Valve Alow mass disc type check valve in the discharge fitting of the compressor prevents the high side high pressure discharge gas from flowing rapidly back through the compressor This check valve was not designed to be used with recycling pump down because it is not entirel...

Page 3: ...ng the off cycle See Figure 2 and Table 6 Pump down Cycle A pump down cycle for control of refrigerant migration is not recommended for scroll compressors of this size If a pump down cycle is used a separate external check valve must be added The scroll discharge check valve is designed to stop extended reverse rotation and prevent high pressure gas from leaking rapidly into the low side after shu...

Page 4: ... muffler should be located a minimum of six inches 15 cm to a maximum of 18 inches 46 cm from the compressor for most effective operation The further the muffler is placed from the compressor within these ranges the more effective it may be If adequate attenuation is not achieved use a muffler with a larger cross sectional area to inlet area ratio The ratio should be a minimum of 20 to 1 with a 30...

Page 5: ...ls and permanent damage to the scroll tips drive bearings and internal seal See AE24 1105 for proper system evacuation procedures Nomenclature The model numbers of the Copeland Scroll compressors include the approximate nominal 60 HZ capacity at standard operating conditions An example would be the ZR24K3 TFD which has 24 500 Btu hr 7 kw cooling capacity at the ARI high temperature air conditionin...

Page 6: ...s ready for assembly to the unit It is suggested that the larger suction plug be removed first to relieve the internal pressure Removing the smaller discharge plug could result in a spray of oil out of this fitting since some oil would accumulate in the head of the compressor after Emerson test runs the compressor The inside of both fittings should we wiped with a lint free wipe to remove residual...

Page 7: ... could ignite when it escapes and contacts the brazing flame It is important to check both the high pressure and low pressure side with manifold gauges before unbrazing Instructions should be provided in appropriate product literature and assembly line repair areas If compressor removal is required the compressor should be cut out of system rather than unbrazed See Figure 6 for proper compressor r...

Page 8: ...e filter drier recommendations It is highly recommended that the suction accumulator be replaced if the system contains one This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure Start up of a New or Replacement Compresso...

Page 9: ...igerant flood back To test for repeated excessive liquid flood back during normal system off cycles perform the Field Application Test Obtain a sample compressor with a side sight tube to measure liquid level in the compressor Set the system up in a configuration with the indoor unit elevated several feet above the outdoor unit with twenty five feet 8 meters of connecting tubing with no traps betw...

Page 10: ... heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Liquid Level Drainage In Off Cycle Scroll Accumulator Figure 2 To prevent flooded start damage on 3 phase scrolls due to off cycle migration the accumulator may be configured on some systems to allow free drainage from the co...

Page 11: ...ications Timer Opens 1 Electrical cycle Timer Closes Greater than 5 seconds later 016 sec with 60 HZ operation power is restored or not after power is removed Typical Solid State Timer if used Fuse Discharge Line Thermostat if used Compressor Contactor Condenser Fan Contactor if used Other Protective Devices if used System Operating Thermostat 230 240 VAC C1 C ...

Page 12: ...ections Figure 4 Terminal Fusite Connection 70 80 90 100 110 120 130 140 150 160 170 20 10 0 10 20 30 40 50 60 Condensing Temp C Evaporating Temp C Condensing Temp F Evaporating Temp F R22 Scroll Operating Envelope 20 15 10 5 0 5 10 25 15 70 60 50 40 30 ZR__KA Limited Envelope All Other Scroll Products Figure 5 ...

Page 13: ... braze temperature is attained moving torch up and down and rotating around tube as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around cir cumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with a...

Page 14: ...AE4 1312 R2 2010 Emerson Climate Technologies Printed in the U S A 14 Operating Principle of Scroll Figure 7 ...

Page 15: ...uired Not Required Required Required Not Required Required Required Required Other 1 Nominal System Charage 2 Table 1 Scroll Compressor Application Diagram 1 Other includes bleed type TXVs capillary tubes and fixed orifices 2 Nominal System Charge is defined as the design charge for a system Note See text for crankcase heater requirements 120 Times Compressor refrigerant charge limit in Table 5 ...

Page 16: ...onent Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Suction muffler May be required Acts as dampening mass Table 3 K1 K2 K3 K4 KC ZR18 25µf 370 volt 30µf 370 volt 35µf 370 volt 30µf 370 volt ZR23 30µf 370 volt 40µf 370 volt 35µf 370 volt 35µf 370 volt ZR26 35µf 370 volt 40µf 370 volt 30µf 440 volt ZR28 35µf 370 volt 45µf 370 volt 35µf 440 vol...

Page 17: ...KC 4 ZR16KA ZR34KA 53 018 0052 00 240 40 02 6319 00 21 53 018 0052 01 120 40 02 6319 02 21 ZR18K3 ZR48K3 ZR26KC ZR48KC ZR38KA ZR54KA 63 018 0041 00 240 40 02 6307 00 21 63 018 0041 01 120 40 02 6307 02 21 63 018 0041 02 480 40 02 6307 03 21 63 018 0041 03 575 40 02 6307 06 21 63 018 0041 04 240 40 02 6311 00 48 63 018 0041 05 480 40 02 6311 03 48 63 018 0041 06 240 40 02 6313 00 32 ZR54K3 ZR61K3 Z...

Page 18: ...Model MFD Volts Part Number G E p n Emerson p n Pick up Volts Drop out Volts Coil Voltage ZR16K x to ZR48K x PFV 88 108 330 014 0036 03 3ARR3CT3P5 040 0001 79 170 180 40 90 332 ZR46K x to ZR68K x PFV 270 324 330 014 0006 10 3ARR3CT3P5 040 0001 79 170 180 40 90 332 x C 3 4 or CE 3E 4E ZR_KA Start components still in development ...

Reviews: