Emerson Copeland Scroll ZR K3 Series Application Engineering Bulletin Download Page 3

AE4-1312 R2

© 2010 Emerson Climate Technologies

Printed in the U.S.A.

3

and determine if the accumulator design is adequate, 

please see the section entitled 

Excessive Liquid Flood 

back Tests 

at the end of this bulletin. The accumulator 

oil return orifice should be from .040 to .055 inches (1 – 

1.4 mm) in diameter depending on compressor size and 

compressor flood back results. A large-area protective 

screen no finer than 30 x 30 mesh (0.6 mm openings) 

is required to protect this small orifice from plugging. 

Tests have shown that a small screen with a fine mesh 

can easily become plugged causing oil starvation to the 

compressor bearings.

Screens  

The use of screens finer than 30 x 30 mesh (0.6mm 

openings) anywhere in the system should not be 

used with these compressors. Field experience has 

shown that finer mesh screens used to protect thermal 

expansion valves, capillary tubes, or accumulators 

can become temporarily or permanently plugged with 

normal system debris and block the flow of either oil or 

refrigerant to the compressor. Such blockage can result 

in compressor failure. 

Crankcase Heat - Single Phase

Crankcase heaters are not required on single phase 

compressors when the system charge is not over the 

120% limit shown in 

Table 5

. A crankcase heater is 

required for systems containing more than 120% of the 

compressor refrigerant charge limit listed in 

Table 5

This includes long line length systems where the extra 

charge will increase the standard factory charge above 

the 120% limit. 

Experience has shown that compressors may fill with 

liquid refrigerant under certain circumstances and 

system configurations, notably after longer off cycles 

when the compressor has cooled. This may cause 

excessive start up clearing noise or the compressor 

may lock up and trip on protector several times before 

starting. The addition of a crankcase heater will reduce 

customer noise and dimming light complaints since the 

compressor will no longer have to clear out liquid during 

start.  

Table 6 

lists the crankcase heaters recommended 

for the various models and voltages.

Crankcase Heat – Three-Phase

A crankcase heater is required for three-phase 

compressors when the system charge exceeds the 

compressor charge limit listed in 

Table 5

 and an 

accumulator cannot be piped to provide free liquid 

drainage during the off cycle (See 

Figure 2

 and 

Table 

6

).

Pump down Cycle

A pump down cycle for control of refrigerant migration 

is not recommended for scroll compressors of this size. 

If a pump down cycle is used, a separate external 

check valve must be added.

 The scroll discharge 

check valve is designed to stop extended reverse 

rotation and prevent high-pressure gas from leaking 

rapidly into the low side after shut off. The check 

valve will in some cases leak more than reciprocating 

compressor discharge reeds, normally used with pump 

down, causing the scroll compressor to recycle more 

frequently. Repeated short-cycling of this nature can 

result in a low oil situation and consequent damage to 

the compressor. The low-pressure control differential 

has to be reviewed since a relatively large volume of 

gas will re-expand from the high side of the compressor 

into the low side on shut down. 

Minimum Run Time

There is no set answer to how often scroll compressors 

can be started and stopped in an hour, since it is 

highly dependent on system configuration. Other 

than the considerations in the section on Brief Power 

Interruptions, there is no minimum off time because 

scroll compressors start unloaded, even if the 

system has unbalanced pressures. The most critical 

consideration is the 

minimum run time required 

to return oil to the compressor after startup

. To 

establish the minimum run time obtain a sample 

compressor equipped with a sight tube (available from 

Emerson Climate Technologies) and install it in a system 

with the longest connecting lines that are approved for 

the system. The minimum on time becomes the time 

required for oil lost during compressor startup to return 

to the compressor sump and restore a minimal oil 

level that will assure oil pick up through the crankshaft. 

Cycling the compressor for a shorter period than this, 

for instance to maintain very tight temperature control, 

will result in progressive loss of oil and damage to the 

compressor. See Application Engineering Bulletin 17-

1262 for more information on preventing compressor 

short cycling. 

Reversing Valves

Since Copeland Scroll compressors have very high 

volumetric  efficiency,  their  displacements  are  lower 

than those of comparable capacity reciprocating 

compressors. As a result, Emerson recommends that 

the capacity rating on reversing valves be no more than 

2 times the nominal capacity of the compressor with 

which it will be used in order to ensure proper operation 

of the reversing valve under all operating conditions.

Summary of Contents for Copeland Scroll ZR K3 Series

Page 1: ... the high side and the low side of the compressor It is designed to open when the discharge to suction differential pressure exceeds 375 to 450 psid 26 32 kg cm2 When the valve opens hot discharge gas is routed back into the area of the motor protector to cause a trip During developmental blocked fan testing it is sometimes noted that the valve opens but the compressor does not shut off while the ...

Page 2: ...e shutdown sound for acceptability in a particular system Also refer to section on Brief Power Interruption Discharge Check Valve Alow mass disc type check valve in the discharge fitting of the compressor prevents the high side high pressure discharge gas from flowing rapidly back through the compressor This check valve was not designed to be used with recycling pump down because it is not entirel...

Page 3: ...ng the off cycle See Figure 2 and Table 6 Pump down Cycle A pump down cycle for control of refrigerant migration is not recommended for scroll compressors of this size If a pump down cycle is used a separate external check valve must be added The scroll discharge check valve is designed to stop extended reverse rotation and prevent high pressure gas from leaking rapidly into the low side after shu...

Page 4: ... muffler should be located a minimum of six inches 15 cm to a maximum of 18 inches 46 cm from the compressor for most effective operation The further the muffler is placed from the compressor within these ranges the more effective it may be If adequate attenuation is not achieved use a muffler with a larger cross sectional area to inlet area ratio The ratio should be a minimum of 20 to 1 with a 30...

Page 5: ...ls and permanent damage to the scroll tips drive bearings and internal seal See AE24 1105 for proper system evacuation procedures Nomenclature The model numbers of the Copeland Scroll compressors include the approximate nominal 60 HZ capacity at standard operating conditions An example would be the ZR24K3 TFD which has 24 500 Btu hr 7 kw cooling capacity at the ARI high temperature air conditionin...

Page 6: ...s ready for assembly to the unit It is suggested that the larger suction plug be removed first to relieve the internal pressure Removing the smaller discharge plug could result in a spray of oil out of this fitting since some oil would accumulate in the head of the compressor after Emerson test runs the compressor The inside of both fittings should we wiped with a lint free wipe to remove residual...

Page 7: ... could ignite when it escapes and contacts the brazing flame It is important to check both the high pressure and low pressure side with manifold gauges before unbrazing Instructions should be provided in appropriate product literature and assembly line repair areas If compressor removal is required the compressor should be cut out of system rather than unbrazed See Figure 6 for proper compressor r...

Page 8: ...e filter drier recommendations It is highly recommended that the suction accumulator be replaced if the system contains one This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure Start up of a New or Replacement Compresso...

Page 9: ...igerant flood back To test for repeated excessive liquid flood back during normal system off cycles perform the Field Application Test Obtain a sample compressor with a side sight tube to measure liquid level in the compressor Set the system up in a configuration with the indoor unit elevated several feet above the outdoor unit with twenty five feet 8 meters of connecting tubing with no traps betw...

Page 10: ... heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Liquid Level Drainage In Off Cycle Scroll Accumulator Figure 2 To prevent flooded start damage on 3 phase scrolls due to off cycle migration the accumulator may be configured on some systems to allow free drainage from the co...

Page 11: ...ications Timer Opens 1 Electrical cycle Timer Closes Greater than 5 seconds later 016 sec with 60 HZ operation power is restored or not after power is removed Typical Solid State Timer if used Fuse Discharge Line Thermostat if used Compressor Contactor Condenser Fan Contactor if used Other Protective Devices if used System Operating Thermostat 230 240 VAC C1 C ...

Page 12: ...ections Figure 4 Terminal Fusite Connection 70 80 90 100 110 120 130 140 150 160 170 20 10 0 10 20 30 40 50 60 Condensing Temp C Evaporating Temp C Condensing Temp F Evaporating Temp F R22 Scroll Operating Envelope 20 15 10 5 0 5 10 25 15 70 60 50 40 30 ZR__KA Limited Envelope All Other Scroll Products Figure 5 ...

Page 13: ... braze temperature is attained moving torch up and down and rotating around tube as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around cir cumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with a...

Page 14: ...AE4 1312 R2 2010 Emerson Climate Technologies Printed in the U S A 14 Operating Principle of Scroll Figure 7 ...

Page 15: ...uired Not Required Required Required Not Required Required Required Required Other 1 Nominal System Charage 2 Table 1 Scroll Compressor Application Diagram 1 Other includes bleed type TXVs capillary tubes and fixed orifices 2 Nominal System Charge is defined as the design charge for a system Note See text for crankcase heater requirements 120 Times Compressor refrigerant charge limit in Table 5 ...

Page 16: ...onent Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Suction muffler May be required Acts as dampening mass Table 3 K1 K2 K3 K4 KC ZR18 25µf 370 volt 30µf 370 volt 35µf 370 volt 30µf 370 volt ZR23 30µf 370 volt 40µf 370 volt 35µf 370 volt 35µf 370 volt ZR26 35µf 370 volt 40µf 370 volt 30µf 440 volt ZR28 35µf 370 volt 45µf 370 volt 35µf 440 vol...

Page 17: ...KC 4 ZR16KA ZR34KA 53 018 0052 00 240 40 02 6319 00 21 53 018 0052 01 120 40 02 6319 02 21 ZR18K3 ZR48K3 ZR26KC ZR48KC ZR38KA ZR54KA 63 018 0041 00 240 40 02 6307 00 21 63 018 0041 01 120 40 02 6307 02 21 63 018 0041 02 480 40 02 6307 03 21 63 018 0041 03 575 40 02 6307 06 21 63 018 0041 04 240 40 02 6311 00 48 63 018 0041 05 480 40 02 6311 03 48 63 018 0041 06 240 40 02 6313 00 32 ZR54K3 ZR61K3 Z...

Page 18: ...Model MFD Volts Part Number G E p n Emerson p n Pick up Volts Drop out Volts Coil Voltage ZR16K x to ZR48K x PFV 88 108 330 014 0036 03 3ARR3CT3P5 040 0001 79 170 180 40 90 332 ZR46K x to ZR68K x PFV 270 324 330 014 0006 10 3ARR3CT3P5 040 0001 79 170 180 40 90 332 x C 3 4 or CE 3E 4E ZR_KA Start components still in development ...

Reviews: