background image

12

© 2016 Emerson Climate Technologies, Inc.

AE5-1412 R1

6.17. Crankcase Heater

The crankcase heater is energized when the ambient 

temperature is below 50°F and the compressor is off. 

If  an  ambient  sensor  fails,  the  crankcase  heater  is 

energized when the compressor is off. 

6.18. Suction Pressure Control

The compressor is operated based on the suction 

pressure cut-in (

Cin

) and cut-out (

CoU

). If the suction 

pressure  rises  above  the  cut-in,  the  compressor  is 

turned on using the startup procedure (See Section 

6.14). If the suction pressure then falls below the cut-

out,  it  turns  the  compressor  off  using  the  shutdown 

procedure (See section 6.16).

The compressor remains off for a minimum 120 

seconds (

2oF

) after shutdown, which is adjustable in 

the advanced options menu (See section 6.3). 

If the suction pressure transducer fails, the compressor 

will run in limp along mode. The compressor will stay 

off for 3 minutes (

CoF

) then run for 3 minutes (

Con

). 

These values are adjustable from the advanced options 

menu (See section 6.3).

The cut-in and cut-out settings are adjustable between 

0 PSIG and 135 PSIG.

IMPORTANT:  At  initial  power  up,  depending  on  the 

suction  pressure  transducer,  the  suction  pressure 

could be higher than the rating of the transducer. For 

15 minutes after power up, any over pressure errors 

generated by the suction pressure transducer should be 

ignored, and the display will flash 135. If the transducer 

is still in an error state after the time has expired, the 

control will alarm that the suction pressure transducer 

signal is lost, and go into limp along mode.

6.19. Fan Control 

The The X-line uses variable speed PSC condenser 

fan motors to maintain the head pressure values that 

allow the system to operate within the compressor 

operating envelope and maintain the minimum pressure 

differential across the expansion device to allow it to 

operate properly.

The controller uses a Proportional-Integral (PI) control 

algorithm to determine the fan speed.  The fans will 

not run any slower than 40% before turning off. When 

a fan first turns on it will run for 3 seconds at full speed 

before it begins modulating. Fans will run for at least 

10 seconds before turning off and stay off for at least 

10 seconds before being turned back on.  

Since the X-Line controller knows the current suction 

pressure,  the  controller  can  determine  the  minimum 

condensing point for the condition the unit is actually 

running,  and  will  adjust  the  fan  control  set  point  to 

maintain that temperature or higher.

The XFAP/XFAM and XFAL models have different 

compressors and different refrigerant options.  

Therefore,  during  commissioning,  it  is  important  to 

identify the seleted refrigerant so the controller will 

operate the fans properly.

Low ambient operation

The condensing unit can operate in outdoor ambient 

temperatures as low as -40°F. The unit will automatically 

adjust condenser fan speed to maintain head pressure.  

At extremely low ambient temperature the condenser 

fan  might  not  run,  but  the  condenser  coil  is  still 

discharging heat. Parameter LAS sets the ambient 

temperature required to initiate low ambient on time.  

The default value is -20°F. Parameter LMO sets the 

low ambient minimum on time.  The default value is 6 

seconds. Below -20°F ambient, when the condensing 

unit runs it will run for a minimum of 6 seconds.

IMPORTANT NOTE:

  To fully utilize low condensing 

options  below  70°F  condensing,  an  electronic 

expansion valve (EXV) is normally required to handle 

the larger variation in mass flows. As a result, the unit 

is shipped with a default minimum condensing override 

value of 70°F (80°F for XFAL). The fans will still follow 

the map of the selected refrigerant, but the map will 

not be allowed to run below the override value. If you 

have a system with an EXV installed, you can adjust 

the value by changing parameter MCS in the advanced 

options menu.

6.19.1. Fan Overrides and Error Handling

If the discharge line temperature is above 205°F the 

fans will run at full speed.

If the condenser mid-coil temperature sensor fails, the 

fan speed is determined by outdoor ambient. If both 

the outdoor ambient sensor and the condenser mid-coil 

temperature sensor fail, all fans will run at full speed.

Summary of Contents for Copeland Scroll XFAL Series

Page 1: ...Copeland Scroll Outdoor Refrigeration Unit Installation and reference manual Models XFAL XFAM XFAP 1 5 to 6 HP ...

Page 2: ...20 Defrost Controls 13 6 20 1 Holiday Defrosts 13 6 20 2 Defrost Functionality 13 6 20 3 Liquid Line Solenoid Control 13 6 21 Enhanced Vapor Injection EVI for Low Temperature Units 13 6 21 1 Low Temp EVI Discharge Line Temperature Protection Mode 13 6 21 1 1 Low Temp EVI Discharge Line Temperature Protection Error Handling 14 TABLE OF CONTENTS Section Page Section Page 6 21 2 EVI SYSTEM CHECKS XFA...

Page 3: ...ced on the user s safety Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3 These instructions should be retained throughout the lifetime of the compessor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serio...

Page 4: ...t must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury or pr...

Page 5: ...its 0 F to 45 F saturated suction include all the standard features Discharge line temperature control is accomplished by suction line liquid injection Extended medium temp XFAP units 25F to 45F saturated suction feature an accumulator Discharge line temperature control is accomplished by suction line liquid injection The Dixell XCM25D Electronic Control Module with CoreSense technology control mo...

Page 6: ...6 7 40 5 33 1 1 2 S 7 8 S 10 7 10 5 9 1 10 10 9 1 9 7 9 7 16 8 25 40 219 XFAM 017Z TFC ZS11KAE TF5 1 16 7 40 5 33 1 1 2 S 7 8 S 10 7 10 5 9 1 10 10 9 1 9 7 9 7 14 05 20 40 219 XFAM 022Z CFV ZS15KAE PFV 1 16 7 40 5 33 1 1 2 S 7 8 S 10 7 10 5 9 1 10 10 9 1 9 7 9 7 20 68 35 40 220 XFAM 022Z TFC ZS15KAE TF5 1 16 7 40 5 33 1 1 2 S 7 8 S 10 7 10 5 9 1 10 10 9 1 9 7 9 7 14 3 20 40 219 XFAM 030Z CFV ZS21K...

Page 7: ... 2016 Emerson Climate Technologies Inc AE5 1412 R1 6 5 Quick Setup Guide ...

Page 8: ...nt A b C d E F H i L M n o P q r S T U Y 0 1 2 3 4 5 6 7 8 9 The letters G J K Q V W X and Z are not used on the 7 segment display LED MODE FUNCTION ON Compressor enabled Flashing Anti short cycle delay enabled ON Condensing fans enabled ON Display temperature value in degrees F Flashing Programming mode ON Display pressure value in PSI ON Browsing service menu Flashing Fast access menu Viewing se...

Page 9: ...e is stored even when the procedure is exited by waiting for the time out to expire NOTE If a menu does not have any parameters available noP will be displayed 6 3 Entering the Advanced Options Menu 1 Hold down keys for 3 seconds or until the F LED starts blinking to enter the module s programming menu 2 Use or to select the PAr menu 3 Press to enter the PAr menu 4 Use or to select the PAS paramet...

Page 10: ...Access Menu Use or arrows to select an entry then press to see the value or to go on with other value TO EXIT Press or wait 60 seconds without pressing the keys 6 9 1 List of Fast Access Parameters P1P Suction pressure P2t Condenser temperature P2P Not Used P3t Discharge line temperature P4t EVI heat exchanger vapor inlet temperature XFAL only PSt EVI heat exchanger vapor outlet temperature XFAL o...

Page 11: ...failed programming operation In this case push the again if you want to restart the upload again or remove the HOT KEY to abort the operation 6 12 How to Program a Controller Using a HOT KEY Download A hot key is included with each unit for factory reset and replacement control programming Remove power from the unit Insert a pre programmed HOT KEY into the 5 PIN receptacle labeled H K and reapply ...

Page 12: ...g on the compressor or any other device Once the controller calls for the compressor to run and there are no active alarms the controller will then turn on the compressor utilizing bump start if needed per Section 6 15 and control the fans and compressor 6 15 Bump Start Control Operation If the ambient temperature sensor reads less than 95 F when the controller is first turned on or after the comp...

Page 13: ... than 40 before turning off When a fan first turns on it will run for 3 seconds at full speed before it begins modulating Fans will run for at least 10 seconds before turning off and stay off for at least 10 seconds before being turned back on Since the X Line controller knows the current suction pressure the controller can determine the minimum condensing point for the condition the unit is actua...

Page 14: ...ng the solenoid and the compressor will start running once the suction pressure is above the cut in If a pump down solenoid is not present or the unit should not pump down when entering a defrost parameter tLS should be set to no TLS is set to YES by default 6 21 Enhanced Vapor Injection EVI For Low Temperature Units The injection valve is a key part of the EVI system It regulates vapor injection ...

Page 15: ...atures In addition the unit liquid line should be insulated since the liquid line temperature will be lower than the ambient temperature See the table on page 28 for specifics regarding balanced port sizing recommendations Applied with the low temp units it is recommended that a balanced port expansion valve be used along with a complete review of the distributor and nozzle orifice that is supplie...

Page 16: ... parameter PEn is set to 0 the unit will always automatically reset 6 26 Open Run Circuit Single Phase Only After the compressor is started and runs for 6 seconds if the there is no run circuit current and the start current is still greater than 1 amp the controller will display an E24 error for open run circuit and shut down the compressor The compressor will not restart for 3 minutes in the even...

Page 17: ...l reset or the unit power to be reset Error code L40 means the compressor tripped on high pressure and is locked out If the parameter HPn is set to 0 the unit will always automatically reset 6 32 Alarm Contact The alarm contact A1 and A2 on terminal block is a dry contact that can be wired to an external warning device such as a buzzer or light This relay has a 5 Amp limit up to 250V The alarm con...

Page 18: ...17 AE5 1412 R1 2016 Emerson Climate Technologies Inc Single Fan Unit 1 5 3 HP Dual Fan Unit 4 6 HP Bottom View All Models Figure 1 8 Physical and Installation Requirements ...

Page 19: ... Max Current 16A Max Each Spade Provides Power for Defrost Heater and Evaporator Fan Relays D01 Spade Connector 16A Relay Operates 40A Evaporator Fan Relay D02 Spade Connector 16A Relay Operates 40A Defrost Heater Relay C2 Spade Connector 16A Max Current Provides Power to Compressor Relay and CCH RH Relays D03 Spade Connector 5A Relay Operates Compressor Contactor D04 Spade Connector 8A Relay Powe...

Page 20: ...ow Temp Only 10k NTC See Section 12 for values DI3 Future Use Future Use EV Liquid or Vapor Injection Valve 12VDC Stepper Other Connections Label Functions VNR Remote Display Connection Connect to and to RS485 RS 485 Communications CANBUS Future Use B BKP Future Use H K Hotkey programming use with part 043 0171 01 to reset control Label Connector s Electrical Limit 250VAC Max Function Neutral Spad...

Page 21: ...20 2016 Emerson Climate Technologies Inc AE5 1412 R1 9 Wiring Diagrams 3 X A 2 G 4 N L1 L2 A 1 052 7287 00 Low Temp 1 Phase 2 0 3 5 HP 1 Condenser Fan ...

Page 22: ...21 AE5 1412 R1 2016 Emerson Climate Technologies Inc 3 X A 2 G 4 N L1 L2 A 1 052 7287 01 Low Temp 1 Phase 4 5 HP 2 Condenser Fans ...

Page 23: ...22 2016 Emerson Climate Technologies Inc AE5 1412 R1 052 7287 02 Medium Temp 1 Phase 1 5 3 HP 1 Condenser Fan ...

Page 24: ...23 AE5 1412 R1 2016 Emerson Climate Technologies Inc 3 X A 2 G 4 N L2 A 1 L1 L3 052 7287 04 Medium Temp 3 Phase 4 5 6 HP 2 Condenser Fans ...

Page 25: ...24 2016 Emerson Climate Technologies Inc AE5 1412 R1 3 X A 2 G 4 N L2 A 1 L1 L3 052 7287 05 Low Temp 3 Phase 2 3 HP 1 Condenser Fans ...

Page 26: ...25 AE5 1412 R1 2016 Emerson Climate Technologies Inc 3 X A 2 G 4 N L2 A 1 L1 L3 052 7287 13 Low Temp 3 Phase 4 6 HP 2 Condenser Fans ...

Page 27: ...26 2016 Emerson Climate Technologies Inc AE5 1412 R1 3 X A 2 G 4 N L2 A 1 L1 L3 052 7287 14 Medium Temp 3 Phase 1 5 3 HP 1 Condenser Fan ...

Page 28: ...27 AE5 1412 R1 2016 Emerson Climate Technologies Inc 3 X A 2 G 4 N L1 L2 A 1 052 7287 15 Medium Temp 1 Phase 4 5 5 HP 2 Condenser Fans ...

Page 29: ...0 1 30 1 20 1 10 1 00 0 90 0 80 0 70 0 50 R 134a 1 70 1 63 1 56 1 49 1 42 1 36 1 29 1 21 1 14 1 07 1 00 0 93 0 85 0 78 0 71 R 407A 1 75 1 68 1 61 1 53 1 46 1 39 1 31 1 24 1 16 1 08 1 00 0 92 0 84 0 76 0 68 R 407C 1 69 1 62 1 55 1 49 1 42 1 35 1 28 1 21 1 14 1 07 1 00 0 93 0 86 0 79 0 72 These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on a...

Page 30: ... Liquid line temperature sensor error XFALs only Alarm Check wire connection to the top of the controller A7 Replace faulty temperature sensor E09 E10 Current sensor error Alarm Check wires are properly routed through controller current transducers per wiring diagram Replace faulty controller E11 E13 Voltage sensor error Alarm Check wires are connected to voltage sensing connections R S T per wiri...

Page 31: ...e wiring diagram and C2 is receiving power Verify high pressure switch is working properly or needs replaced E44 L44 Discharge line temperature alarm lockout Alarm Lockout Check system cause of high DLT Faulty temperature sensor Check sensor values versus section 12 E46 High condenser temperature alarm Alarm Check to see what is causing the system to run at a higher condensing temperature Faulty t...

Page 32: ...9 320 1 25 329 1 12 338 1 01 347 0 92 356 0 83 F Resistance kOhms 55 302 2 50 254 9 45 221 7 40 188 5 35 160 2 30 140 4 25 120 2 20 105 7 15 90 8 10 80 3 5 69 4 0 61 5 5 53 4 10 46 5 15 41 5 20 36 3 25 32 4 30 28 5 35 25 6 40 22 5 45 20 3 50 18 0 55 15 9 60 14 4 65 12 8 70 11 6 75 10 4 80 9 46 85 8 47 F Resistance kOhms 90 7 73 95 6 94 100 6 25 105 5 73 110 5 17 115 4 75 120 4 30 125 3 96 130 3 59...

Page 33: ...efrost start 1 hour 6 00 nu 0 00 23 50 Ld2 Workday defrost start 2 hour 13 00 nu 0 00 23 50 Ld3 Workday defrost start 3 hour 21 00 nu 0 00 23 50 Ld4 Workday defrost start 4 hour nu nu 0 00 23 50 Ld5 Workday defrost start 5 hour nu nu 0 00 23 50 Ld6 Workday defrost start 6 hour nu nu 0 00 23 50 Real Time Clock Min Current minute 0 59 Hr Current hour 0 23 MdY day of month 1 31 Mon month 1 12 YEr yea...

Page 34: ...e compressor lock 5 0 15 bMP Bump start enable YES no yes dLn Number of activation of DLT in a hour to lock compressor 4 0 15 Condenser Fan MCS Minimum Condenser set point F 70 XFAP 80 XFAL 40 230 Low Side Control dFd Display during defrost dEF DEF Setpoint Initial Pressure End Pressure Fdt Drip time min 0 0 120 dPo Defrost at power on NO no yes Sd1 Holiday defrost start 1 hour 6 00 nu 0 00 23 50 ...

Page 35: ...2015ECT 53 R1 4 17 Emerson Copeland Scroll and CoreSense are trademarks of Emerson Electric Co or one of its affiliated companies 2017 Emerson Climate Technologies Inc All rights reserved Emerson com ...

Reviews: