13. Parameters
Label
Description
Default
Range
Default Display Value
Current Suction Pressure (PSIG)
Adjustable in Programming Menu
Compressor
Cin /
Compressor cut in pressure set point (PSIG)
25.0
Cou - 135
CoU /
Compressor cut out pressure set point (PSIG)
15.0
0 - Cin
rEF /
Refrigerant Selection for Regulation
R404A
All unit Refs
Low Side Control
idF /
interval between defrost cycles (hour)
8
0 - 120
MdF /
Maximum length for defrost (min)
45
0 - 255
EdF /
Defrost interval mode
in
nu, in, RTC
Ld1 /
Workday defrost start 1 (hour)
6:00
nu, 0:00 - 23:50
Ld2 /
Workday defrost start 2 (hour)
13:00
nu, 0:00 - 23:50
Ld3 /
Workday defrost start 3 (hour)
21:00
nu, 0:00 - 23:50
Ld4 /
Workday defrost start 4 (hour)
nu
nu, 0:00 - 23:50
Ld5 /
Workday defrost start 5 (hour)
nu
nu, 0:00 - 23:50
Ld6 /
Workday defrost start 6 (hour)
nu
nu, 0:00 - 23:50
Real Time Clock
Min /
Current minute
0 - 59
Hr /
Current hour
0 - 23
MdY /
day of month
1 - 31
Mon /
month
1 - 12
YEr /
year
0 - 99
Password
PAS /
Enter into PR2 level
321
(blank)
Adjustable from Advanced Options Menu
Probe Configuration
P1F /
Probe P1 calibration (PSIG)
0.0
-12.0 - 12.0
Display
Lod /
Remote Display visualization
P1
P1 - P7
Compressor
LAS /
Ambient temperature required to initiate low
ambient on time (°F)
-20
-40 - 230
LMO /
Low ambient minimum on time (sec)
6
0 - 255