11. Alarm Codes
Code
Description
Alarm Level
Diagnostic Resolution
Possible Fix
E01
Suction pressure
transducer error
Alarm
Check wire connection to the
top of the controller (A1)
Check to ensure suction
pressure is below 135 PSIG
Replace faulty suction pressure
transducer
E02
Condenser
temperature sensor
error
Alarm
Check wire connection to the
top of the controller (A2)
Replace faulty temperature
sensor
E03
Discharge line
temperature sensor
error
Alarm
Check wire connection to the
top of the controller (A3)
Replace faulty temperature
sensor
E04
EVI heat exchanger
vapor inlet temperature
error (XFALs only)
Alarm
Check wire connection to the
top of the controller (A4)
Replace faulty temperature
sensor
E05
EVI heat exchanger
vapor outlet
temperature error
(XFALs only)
Alarm
Check wire connection to the
top of the controller (A5)
Replace faulty temperature
sensor
E06
Ambient temperature
sensor error
Alarm
Check wire connection to the
top of the controller (A6)
Replace faulty temperature
sensor
E07
Liquid line temperature
sensor error (XFALs
only)
Alarm
Check wire connection to the
top of the controller (A7)
Replace faulty temperature
sensor
E09-E10
Current sensor error
Alarm
Check wires are properly routed
through controller current
transducers per wiring diagram
Replace faulty controller
E11-E13
Voltage sensor error
Alarm
Check wires are connected to
voltage sensing connections (R,
S, T) per wiring diagram
Replace faulty controller
E20
L20
Lost phase error/
lockout (Three phase
only)
Alarm
Lockout
Check power to unit
Check wires are connected to
voltage sensing connections (R,
S, T) per wiring diagram
E21
L21
Phase sequence error
/ lockout (Three phase
only)
Alarm
Lockout
Reverse two phases incoming
power to unit
Check wires are connected to
voltage sensing connections (R,
S, T) per wiring diagram
E22
Phase imbalance
(Three phase only)
Alarm
Check incoming electrical power Correct incoming voltage supply
E23
L23
Over current error/
lockout
Alarm
Lockout
Confirm system operation to
find out what is causing the
compressor to pull excessive
current
E24
L24
Open run circuit error/
lockout
Alarm
Lockout
Check run capacitor
Check start component wiring
per diagram
Check wires are properly routed
through controller current
transducers per wiring diagram