Condensing Unit For Refrigeration Networks
4.4 Maximum compressor cycle
Maximum start per hour: 10 times
4.5 Checks before starting & during operation
Please check that all Rotalock valves are fully opened.
Check that the electrical panel is closed.
After starting and operation conditions are stabilised, we recommend to check the oil
level in compressor(s) and if needed add oil to insure a sufficient oil level (middle of oil
sight glass).
5
Maintenance & Repair: Replacing a compressor
De-energize the condensing unit before any intervention.
Unscrew and lift the housing top panel to get access from the top to the
compressor.
Close Rotalock valves or ball valve to isolate the compressor from the system
and unscrew the flare Rotalock connector from the compressor.
Release the compressor mounting parts and then lift it to replace with a new
compressor.
6
Certification and Approval
The piping is in compliance with the Pressure Equipment Directive 97/23/EEC
(Art.3§3 - Sound Engineering Practice)
Components of the condensing units carry a CE mark as far as required and
thereby establish conformity with the relevant directives.
Conformity Declarations for components are available as far as required.
The units are in conformity with the low voltage directive. The applied harmonised
standard is EN 60335-1 (Safety Household and Similar Electrical Appliance, Part
1: General Requirements)
To incorporate these products into a machine the Manufacturer's Declaration of
incorporation has to be respected.
7
Dismantling and Disposal
Removing oil and refrigerant:
Do not disperse it in the environment.
Use the correct equipment and method of removal.
Dispose oil and refrigerant properly.
Dispose the compressor properly.