Safety
Instructions
Product
Description
Installat
io
n
Electrical
Connection
Starting up &
Operation
Maintenance
& Repair
Dismantling &
Disposal
Condensing Unit For Refrigeration Networks
2.4 Nomenclature
The model designation contains the following technical information about the condensing
unit:
OM T Q 90 D
N L O
TFD
1 2 3 4 5
6 7 8
9
Specific for Network
models
1 - Condensing unit family:
OM = Medium temperature Copeland EazyCool™ unit
OL = Low temperature Copeland EazyCool™ unit
2 - Number of compressor: “blank” = single compressor, “T” = two compressors
3 - Quiet version
4 - Compressor size: 90 = 1 x ZBD45KCE (digital), 1 x ZB45KCE
5 - D = Copeland Digital Scroll™
- V = Low temperature:Copeland Scroll™ with vapour injection (EVI)
6 - N = Unit suitable for creation of a refrigeration network
7 -
L
=
Liquid receiver
included (only for 2 unit network)
8 -
O
=
Oil reservoir
included (always Master)
9 - Motor version: TFD or TWD: 380-420V/3Ph/50H
2.5 Application
range
2.5.1 Qualified refrigerants and oils
OMQ-56-Nxx
~
OMQ-110-Nxx
OMTQ-60(D)-Nxx
OMTQ-76-Nxx
OMTQ-90(D)-Nxx
OLQ-24V-Nxx ~ OLQ-48V-Nxx
OLTQ-26V-Nxx & OLTQ-36V-Nxx
Qualified refrigerant
R404A/R507
R134a,R407C
R22
R404A/R507
R22
R404A/R507
R22
ICI Emkarate RL 32 CF
Mobil EAL Artic 22 CC
Qualified Servicing Oil
Table 1:
Qualified refrigerants and oils
2.5.2 Application limits
For Application envelope, please refer to the Compressor application envelope available
in Copeland Selection Software version 6.
Medium temperature range
Evaporating Temperature: from –30°C up to 12.5°C
Low temperature range
Evaporating Temperature: from –40°C up to 7°C
C6.1.4/0305/E
5
Part no: 3136433