2808B
Specifications / 5-3
Humidity Limits:
Specified with Transmitter electronic
housing cover installed.
15-95% RH to 140
°
F (60
°
C)
15-50% RH to 185
°
F (85
°
C)
EMI Effect:
+1% of URL @ 10 V/M, 20 MHz to 500 MHz
Meets /SAMA PMC-33-1C with Transmitter
cover in place and all wiring contained in
grounded conduit.
Surge Protection:
Bipolar, differential surge
1000 watts for 1 ms (without digital
indicator option)
May be used with purchased surge
protector for additional protection (for non-
hazardous, non-approved installations
only).
Vibration Effect:
Less than +0.1% of URL for 10 to 500 Hz at
1 g on any axis. Meets SAMA PMC-31-1
5.4
PHYSICAL SPECIFICATIONS
Fill Media:
DC 200 Silicone
Electronics Housing:
Low copper aluminum, epoxy finish, NEMA
4X rating
Electrical Connections:
1/2 NPT conduit connection with internal
field wiring terminals.
Summary of Contents for Bristol 2808 Series
Page 12: ...BLANK PAGE ...
Page 14: ...1 2 Introduction 2808B Figure 1 1 2808 XXB Transmitters ...
Page 16: ...BLANK PAGE ...
Page 30: ...BLANK PAGE ...
Page 32: ...1B 2 DP Transmitters 2808B Figure 1B 1 Model 2808 35B Figure 1B 2 Transmitter Assemblies ...
Page 40: ...1B 10 DP Transmitters 2808B Figure 1B 6 Transmitter Housing Rotation Diagram ...
Page 54: ...BLANK PAGE ...
Page 57: ...2808B Calibration 3 3 Figure 3 2 Calibration Adjustments ...
Page 60: ...3 6 Calibration 2808B TABLE 3 A COARSE ZERO SWITCH SETTINGS Elevation ...
Page 61: ...2808B Calibration 3 7 TABLE 3 B COARSE ZERO SWITCH SETTINGS Suppression ...
Page 66: ...BLANK PAGE ...
Page 68: ...4 2 Service 2808B Figure 4 1 Using Internal TEST Terminals to Measure Current ...
Page 72: ...BLANK PAGE ...
Page 74: ...BLANK PAGE ...
Page 90: ...BLANK PAGE ...
Page 92: ...BLANK PAGE ...
Page 100: ...BLANK PAGE ...
Page 128: ...BLANK PAGE ...
Page 139: ...BLANK PAGE ...