3
ESDS Manual
S14006
4/15/92
Table 1
Typical Electrostatic Voltages
Electrostatic Voltages
Means of Static
10-20 Percent
65-90 Percent
Generation
Relative Humidity
Relative Humidity
Walking across carpet
35,000
1,500
Walking over vinyl floor
12,000
250
Worker at bench
6,000
100
Vinyl envelopes for work instructions
7,000
600
Poly bag picked up from bench
20,000
1,200
Work chair padded with poly foam
18,000
1,500
2.
General Rules
(1)
ESD-sensitive components shall only be removed from their static-shielding
bags by a person who is properly grounded.
(2)
When taken out of their static-shielding bags, ESD-sensitive components shall
never be placed over, or on, a surface which has not been properly grounded.
(3)
ESD-sensitive components shall be handled in such a way that the body does
not come in contact with the conductor paths and board components. Handle
ESD-sensitive components in such a way that they will not suffer damage from
physical abuse or from electric shock.
(4)
EPROMS/PROMS shall be kept in anti-static tubes until they are ready to use
and shall be removed only by a person who is properly grounded.
(5)
When inserting and removing EPROMS/PROMS from PC boards, use a chip
removal tool similar to the one shown in the figure following. Remember, all work
should be performed on a properly grounded surface by a properly-grounded
person.
Summary of Contents for Bristol 2808 Series
Page 12: ...BLANK PAGE ...
Page 14: ...1 2 Introduction 2808B Figure 1 1 2808 XXB Transmitters ...
Page 16: ...BLANK PAGE ...
Page 30: ...BLANK PAGE ...
Page 32: ...1B 2 DP Transmitters 2808B Figure 1B 1 Model 2808 35B Figure 1B 2 Transmitter Assemblies ...
Page 40: ...1B 10 DP Transmitters 2808B Figure 1B 6 Transmitter Housing Rotation Diagram ...
Page 54: ...BLANK PAGE ...
Page 57: ...2808B Calibration 3 3 Figure 3 2 Calibration Adjustments ...
Page 60: ...3 6 Calibration 2808B TABLE 3 A COARSE ZERO SWITCH SETTINGS Elevation ...
Page 61: ...2808B Calibration 3 7 TABLE 3 B COARSE ZERO SWITCH SETTINGS Suppression ...
Page 66: ...BLANK PAGE ...
Page 68: ...4 2 Service 2808B Figure 4 1 Using Internal TEST Terminals to Measure Current ...
Page 72: ...BLANK PAGE ...
Page 74: ...BLANK PAGE ...
Page 90: ...BLANK PAGE ...
Page 92: ...BLANK PAGE ...
Page 100: ...BLANK PAGE ...
Page 128: ...BLANK PAGE ...
Page 139: ...BLANK PAGE ...