Section 2 - Protection
Page 2-3
S1400T-2808B
Table 2-2 - Equipment Protection Site Safety Evaluation Guide (Continued)
#
Guide
Reference Section
5
Are there overhead or underground power or com-munication
cables in the immediate area?
See Section 2.3
6
Is there an antenna in the immediate area?
See Section 4.1.2
7
If pipe mounted, is a cathodic charge present on the pipe?
Should the 2808 Transmitter be isolated?
See Section 3.4
8
How close is other equipment? Can someone safely touch this
equipment and a 2808 Transmitter simultaneously?
See Section 2.3
9
Determine equipment ground requirements. How will the
2808 Transmitter and its related wiring be grounded?
Consider Earth Ground, Circuit Ground, Conduit Ground, Site
Grounds, Manifold grounded or not?
See Section 3
10 Are there any obviously faulty or questionable power or
ground circuits?
See Section 2.3
2.3
OTHER SITE SAFETY CONSIDERATIONS
Overhead or underground power or communication cables must be identified prior to
installing a new unit. Accidentally cutting, shorting or simply just contacting power,
ground, communication or process control I/O wiring can have potentially devastating
effects on site equipment, the process system and or personnel.
Don’t assume that it is safe to touch adjacent equipment, machinery, pipes, cabinets or even
the earth itself. Adjacent equipment may not have been properly wired or grounded, may be
defective or may have one or more loose system grounds. Measure between the case of a
questionable piece of equipment and its’ earth ground for the presence of any voltage. If a
voltage is present, something is wrong.
AC powered equipment with a conductive case should have the case grounded. If you don’t
see a chassis ground wire, don’t assume that it is safe to touch this equipment. If you notice
that equipment has been grounded to pipes, conduit, structural steel, etc., you should be
leery.
Note: AWWA’s policy on grounding of electric circuits on water pipes states,
“The American Water Works Association (AWWA) opposes the grounding of
electrical systems to pipe systems conveying water to the customer’s premises….”
Be sure that the voltage between any two points in the instrument system is less than the
stand-off voltage. Exceeding the stand-off voltage will cause damage to the instrument and
will cause the instrument to fail.
Summary of Contents for Bristol 2808 Series
Page 12: ...BLANK PAGE ...
Page 14: ...1 2 Introduction 2808B Figure 1 1 2808 XXB Transmitters ...
Page 16: ...BLANK PAGE ...
Page 30: ...BLANK PAGE ...
Page 32: ...1B 2 DP Transmitters 2808B Figure 1B 1 Model 2808 35B Figure 1B 2 Transmitter Assemblies ...
Page 40: ...1B 10 DP Transmitters 2808B Figure 1B 6 Transmitter Housing Rotation Diagram ...
Page 54: ...BLANK PAGE ...
Page 57: ...2808B Calibration 3 3 Figure 3 2 Calibration Adjustments ...
Page 60: ...3 6 Calibration 2808B TABLE 3 A COARSE ZERO SWITCH SETTINGS Elevation ...
Page 61: ...2808B Calibration 3 7 TABLE 3 B COARSE ZERO SWITCH SETTINGS Suppression ...
Page 66: ...BLANK PAGE ...
Page 68: ...4 2 Service 2808B Figure 4 1 Using Internal TEST Terminals to Measure Current ...
Page 72: ...BLANK PAGE ...
Page 74: ...BLANK PAGE ...
Page 90: ...BLANK PAGE ...
Page 92: ...BLANK PAGE ...
Page 100: ...BLANK PAGE ...
Page 128: ...BLANK PAGE ...
Page 139: ...BLANK PAGE ...