2808B
Calibration / 3-11
3.8.1 Zero Suppression Example (see Figure 3-3 & Table 3-B)
The full water tower of Figure 3-3, produces 53.5 psi of pressure due to the 125 foot head,
i.e 10.7 psi plus 42.8 psi. To determine the Coarse Span Rotary Switch (SW1) setting, divide
the pressure produced by the 25 feet of water in the tank by the Transmitter’s range; in this
case 50 psi, i.e., 10.7/50 = 21.4%. Therefore, the SW1 should be set to position 8 (18.5% -
23%).
To determine the zero suppression necessary for this example, divide the pressure produced
by 100 feet of water (height of tower to bottom of tank) by the Transmitter’s range; in this
case 50 psi, i.e., 42.8/50 = 85.6%. With the Coarse Span Rotary Switch SW1 set to its SW1-8
position, set the value of the Coarse Zero Switch (S1) to either -80% (00001100) or -90%
(00001010), or to a binary value between the two e.g., 00001011 (-85%).
Use Fine Adjustment Screw A2 to set 1.000V (4.00mA) @ 42.8 psi and use Fine Adjustment
Screw A1 to set 5.000V (20.00mA) @ 53.5 psi.
Note: When Zero Suppression is used, the maximum applied pressure may be up
to 125% of the URL.
3.9 SELECTABLE DAMPING
The damping feature provides compensation for applications with severe pressure pulsation
that will cause the DC output of the Transmitter to seem unstable. Controlling the response
time of the Transmitter output can minimize this condition. Do not use damping when the
application requires dynamic pressure measurement.
Jumper JP9 can be set to apply damping to the output. With jumper JP9 in place, the
damping is on. If the jumper does not connect the two pins together, the damping is off.
Summary of Contents for Bristol 2808 Series
Page 12: ...BLANK PAGE ...
Page 14: ...1 2 Introduction 2808B Figure 1 1 2808 XXB Transmitters ...
Page 16: ...BLANK PAGE ...
Page 30: ...BLANK PAGE ...
Page 32: ...1B 2 DP Transmitters 2808B Figure 1B 1 Model 2808 35B Figure 1B 2 Transmitter Assemblies ...
Page 40: ...1B 10 DP Transmitters 2808B Figure 1B 6 Transmitter Housing Rotation Diagram ...
Page 54: ...BLANK PAGE ...
Page 57: ...2808B Calibration 3 3 Figure 3 2 Calibration Adjustments ...
Page 60: ...3 6 Calibration 2808B TABLE 3 A COARSE ZERO SWITCH SETTINGS Elevation ...
Page 61: ...2808B Calibration 3 7 TABLE 3 B COARSE ZERO SWITCH SETTINGS Suppression ...
Page 66: ...BLANK PAGE ...
Page 68: ...4 2 Service 2808B Figure 4 1 Using Internal TEST Terminals to Measure Current ...
Page 72: ...BLANK PAGE ...
Page 74: ...BLANK PAGE ...
Page 90: ...BLANK PAGE ...
Page 92: ...BLANK PAGE ...
Page 100: ...BLANK PAGE ...
Page 128: ...BLANK PAGE ...
Page 139: ...BLANK PAGE ...